15
TECHNICAL DATA
The burner conforms to IP 40 level of insulation as per EN 60529.
FIRING RATE
Minimum output at 1st stage: 107 kW - 9 kg/h
MINIMUM GAS PRESSURE - 2nd STAGE OUTPUT
MODEL
GI / EMME 300
Typ
495 T1
Thermal power
107 / 175 - 332 kW
92.000 / 150.000 - 286.000 kcal/h
Fuels
Oil, max. viscosity at 20 °C: 6 mm
2
/s (1,5 °E)
Natural gas with Pci 8.600 kcal/m
3
LPG with Pci 22.200 kcal/m
3
Minimum gas pressure (measured at the test point)
Maximum capacity requires:
- 9.3 mbar with natural gas;
- 11 mbar with LPG.
Combustion chamber at 0 mbar.
Maximum gas pressure
35 mbar
Electrical supply
single-phase 230 V +/- 10% 50 Hz
Fan - capacitor motor
1.85 A / 230 V - 8 µF
Pump - capacitor motor
1.4 A / 230 V -
6.3
µF
Ignition transformer
primary 1.85 A / 230 V - secondary 1x 8 kV 30 mA
Pump
Output 50 kg/h at 12 bar - max. pressure 15 bar
Operation
Two stages
GB
D1936
kW
kcal/h
mbar
Pressure: measured at the test point with combustion chamber at 0 mbar
natural gas (G 20)
LPG (G 31)
Gas pressure test point
D1937
kW
kcal/h
mbar
D1956
Содержание GI/EMME 300