Diagnosis of fault causes:

After lock-out has occurred, the red signal lamp is steady on. In this status, the visual fault diagnosis according 
to the error code table can be activated by pressing the lock-out reset button for > 3 seconds. The interface 
diagnosis (with adapter) can be activated by pressing again the lock-out button for > 3 seconds.

The flashes of red LED are a signal with this sequence :

(e.g. signal with n° 3 flashes - faulty air pressure monitor)

 LED off         

3 sec.

3 sec.

3 sec.

Error code table

Possible cause of fault

Flash code

No establishment of flame at the end of safety 
time :

- faulty or soiled fuel valves
- faulty or soiled flame detector
- poor adjustment of burner, no fuel  
- faulty ignition equipment

2 flashes

Faulty air pressure monitor

3 flashes

Extraneous light or simulation of flame on burner start up

4 flashes

Loss of flame during operation :

- faulty or soiled fuel valves
- faulty or soiled flame detector
- poor adjustment of burner

7 flashes

Wiring error or internal fault

10 flashes

START UP CYCLE

0s  The burner begins the firing cycle; 

The motor starts: pre-purge phase; 
Ignition electrode sparks.

13s  Delivery valve opens.
28s  The spark goes out;  

Start up cycle is concluded.

0s  The burner begins the firing cycle.
2s  The motor starts: pre-purge phase.
3s  Ignition electrode sparks.
25s  Delivery valve opens.
30s  The spark goes out; 

start up cycle is concluded.

PRESS GV

0

TL

M

time (s)

1

0

25

25

30

2

2

3

PRESS G24

0

TL

M

time (s)

28

13

30

PRESS GV Series 

One Stage Light Oil Burners

10

Содержание G 24

Страница 1: ...www riello com PRESS GV Series One Stage Light Oil Burners PRESS G24 140 237 kW PRESS GV 178 356 kW LIGHT OIL TECHNICAL DATA LEAFLET...

Страница 2: ...out particular maintenance intervention Simplified maintenance is achieved by the slide bar system which allows easy access to all of the essential components of the combustion head All electrical com...

Страница 3: ...ed pump motor current A Pump motor start up current A Pump motor protection level IP Fan motor electrical power kW 0 25 Rated fan motor current A 2 1 Fan motor start up current A 10 Fan motor protecti...

Страница 4: ...PRESS GV Series One Stage Light Oil Burners Firing Rates Useful working field for choosing the burner Test conditions conforming to EN267 Temperature 20 C Pressure 1013 5 mbar Altitude 0 m a s l 4...

Страница 5: ...rom starting to operating phase For PRESS G24 at the start after pre purging phase the first delivery valve opens and the fuel is sprayed out through the first nozzle igniting when it comes into conta...

Страница 6: ...5 36 78 0 32 70 0 5 28 62 1 0 24 55 1 5 20 48 2 0 16 40 3 0 7 25 4 0 10 7 10 9 5 V P H H 8 1 4 10 cm 2 5 7 3 9 6 6 H Difference in height pump foot valve 0 Internal pipe diameter P Max height 10 m V...

Страница 7: ...that the penetration of the head into the combustion chamber is correct The internal position of the combustion head can easily be adjusted to the maximum defined output by adjusting a screw fixed to...

Страница 8: ...on element for visual diagnosis and interface diagnosis Switch Both elements are located under the transparent cover of lock out reset button as showed below There are two diagnostic choices for indic...

Страница 9: ...de table Operation status Color code table Stand by Pre purging Ignition phase Flame OK Poor flame Undervoltage built in fuse Fault alarm Extraneous light LED off Indication of operation In normal ope...

Страница 10: ...poor adjustment of burner no fuel faulty ignition equipment 2 flashes Faulty air pressure monitor 3 flashes Extraneous light or simulation of flame on burner start up 4 flashes Loss of flame during op...

Страница 11: ...the various models at maximum output according to EN 267 standard NO2 EMISSIONS 0 mg kWh 50 100 150 200 250 300 CO EMISSIONS 100 0 20 40 60 80 mg kWh PRESS G24 NOISE EMISSIONS 20 0 dB A 40 60 80 100 P...

Страница 12: ...33 PRESS GV 680 535 450 33 BURNER BOILER MOUNTING FLANGE BURNER Model A B C D E F F 1 H I L O O 1 PRESS G24 425 222 203 397 485 118 253 125 290 PRESS GV 439 234 205 397 473 185 320 140 292 59 690 825...

Страница 13: ...nd maintenance X X After drilling the boilerplate using the supplied gasket as a template dismantle the blast tube from the burner and fix it to the boiler X X Adjust the combustion head X X Refit the...

Страница 14: ...4 14 8 3 50 3042162 PRESS GV 17 4 00 3042172 PRESS GV 19 1 4 50 3042182 PRESS GV 21 2 5 00 3042192 PRESS GV 23 3 5 50 3042202 PRESS GV 25 5 6 00 3042212 PRESS GV 27 6 6 50 3042222 PRESS GV 29 7 7 00 3...

Страница 15: ...tandard A B C D E BURNER KIT CODE PRESS G24 GV 3002719 To connect the control box to a personal computer for the transmission of opera tion fault signals and detailed service information an interface...

Страница 16: ...TC Standard head TL Extended head Flame control system FS1 Standard 1 stop every 24 h FS2 Continuous working 1 stop every 72 h Electrical supply to the system 1 230 50 1 230V 50Hz 1 210 60 1 210V 60Hz...

Страница 17: ...ns for installing a pressure gauge and vacuometer internal by pass for single pipe installation Oil valves on the output circuit Photocell for flame detection Microprocessor based burner safety contro...

Страница 18: ...PRESS GV Series One Stage Light Oil Burners NOTES 18...

Страница 19: ...NOTES 19...

Страница 20: ...lo has been manufacturing premium quality burners for over 90 year The manufacturing plant is equipped with the most innovative systems of assembling lines and modern manufacturing cells for a quick a...

Отзывы: