Diagnosis of fault causes:
After lock-out has occurred, the red signal lamp is steady on. In this status, the visual fault diagnosis according
to the error code table can be activated by pressing the lock-out reset button for > 3 seconds. The interface
diagnosis (with adapter) can be activated by pressing again the lock-out button for > 3 seconds.
The flashes of red LED are a signal with this sequence :
(e.g. signal with n° 3 flashes - faulty air pressure monitor)
LED off
3 sec.
3 sec.
3 sec.
Error code table
Possible cause of fault
Flash code
No establishment of flame at the end of safety
time :
- faulty or soiled fuel valves
- faulty or soiled flame detector
- poor adjustment of burner, no fuel
- faulty ignition equipment
2 flashes
Faulty air pressure monitor
3 flashes
Extraneous light or simulation of flame on burner start up
4 flashes
Loss of flame during operation :
- faulty or soiled fuel valves
- faulty or soiled flame detector
- poor adjustment of burner
7 flashes
Wiring error or internal fault
10 flashes
START UP CYCLE
0s The burner begins the firing cycle;
The motor starts: pre-purge phase;
Ignition electrode sparks.
13s Delivery valve opens.
28s The spark goes out;
Start up cycle is concluded.
0s The burner begins the firing cycle.
2s The motor starts: pre-purge phase.
3s Ignition electrode sparks.
25s Delivery valve opens.
30s The spark goes out;
start up cycle is concluded.
PRESS GV
1°
0
TL
M
time (s)
1
0
25
25
30
2
2
3
PRESS G24
0
TL
M
1°
time (s)
28
13
30
PRESS GV Series
One Stage Light Oil Burners
10