18
6
Maintenance
6.1
Problems and remedies
If the burner does not work properly, first you must:
1
check that the electric connections have been correctly performed;
2
ensure that the fuel is delivered correctly;
3
check that all the adjustment parameters (e.g. boiler water temperature or boiler steam pressure) are correctly set.
Fault
Possible cause
Recommended remedy
The burner does not start
• No electrical power supply . . . . . . . . . . . . . . . . . . . .Close all switches - Check connec-
tions
• A limiter or safety control device is open. . . . . . . . . .Adjust or replace
• Flame control lock-out. . . . . . . . . . . . . . . . . . . . . . . .Reset control box
• Control box fuses blown . . . . . . . . . . . . . . . . . . . . . .Replace
• Erroneous electrical connections . . . . . . . . . . . . . . .Check connections
• Defective flame control . . . . . . . . . . . . . . . . . . . . . . .Replace
• No gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Open the manual valves between
meter and train
• Mains gas pressure insufficient. . . . . . . . . . . . . . . . .Contact your GAS COMPANY
• Minimum gas pressure switch fails to close . . . . . . .Adjust or replace
• Air pressure switch in operating position . . . . . . . . .Adjust or replace
The burner does not start and a
function lock out occurs
• Flame simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . .Replace control box
The burner ignites but then
blocks
Air pressure switch inoperative due to insufficient air pressure:
• Air pressure switch adjusted badly . . . . . . . . . . . . . .Adjust or replace
• Pressure switch pressure point pipe blocked . . . . . .Clean
is blocked
• Head wrong adjusted . . . . . . . . . . . . . . . . . . . . . . . .Adjust
The burner starts and then locks
out
• Fault in flame detection circuit . . . . . . . . . . . . . . . . .Replace flame control
After pre-purge and safety time,
the burner goes to lock-out and
the flame does not appear
• The solenoid VR allows little gas through . . . . . . . . .Increase
• Solenoid valves VR or VS fail to open . . . . . . . . . . .Renew the coil or rectifier panel
• Gas pressure too low . . . . . . . . . . . . . . . . . . . . . . . .Increase on the regulator
• Defective ignition transformer . . . . . . . . . . . . . . . . .Replace
• Erroneous valve or transformer electrical . . . . . . . .Repeat connections
connections
• Defective control box . . . . . . . . . . . . . . . . . . . . . . . .Replace
• A cock down-line of the gas train is closed . . . . . . . .Open
• Air in pipework . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bleed air
The burner goes to lock-out right
after flame appearance
• The solenoid VR allows little gas through . . . . . . . . .Increase
• Max. gas pressure switch operates. . . . . . . . . . . . . .Adjust or replace
• Defective control box . . . . . . . . . . . . . . . . . . . . . . . .Replace
The burner repeats the starting
cycle without lock out
• Mains gas pressure is near the value to which . . . . .Reduce operating pressure
the min. gas pressure switch gas is adjusted.. . . . . .of minimum gas pressure switch.
The repeated drop in pressure which follows . . . . . .Replace the gas filter cartridge
valve opening causes temporary opening of the
pressure switch itself, the valve immediately
closes and theburner comes to a halt. Pressure
increases again, the pressure switch closes again
and the firing cycle is repeated. The sequence
repeats endlessly. And so on.
Содержание DB3 SM C01 TC FS1 A0 T250
Страница 2: ......
Страница 22: ......
Страница 42: ......
Страница 43: ...1...
Страница 51: ...9 3 3 1 1 2 3 M12 X 25 3 2 11 1 2 4 5 2 5 11 3 3 11 3 4 10 1 2 1 2 3 3 D12015 1 1 2 5 4 3 3 20084515 11...
Страница 52: ...10 3 3 4 12 1 2 3 9 10 13 12 1 1 2 5 4 3 3 20084515 12...
Страница 53: ...11 4 4 1 D7543 C GF HPG LPG MM PA PGM PGm RG SRV VE VPS VR VS 0 5 4 bar 500 mbar 13...
Страница 54: ...12 4 4 2 D9135 MB PA PGM SM UV UV TA TB...
Страница 56: ...14 5 5 3 1 4 2 3 5 6 7 1 2 0 3 20 4 5 20 130 1 4 5 4 130 19 18 D1500 3 2 4 1 19 1 2 3 4 D1499...
Страница 57: ...15 5 MAN 3 1 130 90 2 19 2 19 20 2 2...
Страница 58: ...16 5 5 5 20 20 CO 1 10 000 ppm CO 1 21 2 mbar 1 mbar 22 2 mbar 1 mbar 20 D2215 D3571 21 D3571 22...
Страница 59: ...17 5 5 6 70 A 187 V 100 A c c 100 F 1V c c 5 7 1 2 3 4 5 1 2 3 4 5 6 D1143 23...
Страница 60: ...18 6 6 1 1 2 3 VR VR VS VR...
Страница 61: ...19 6...
Страница 62: ......
Страница 63: ......