2915847
14
GB
Installation
4.7
Ignition pilot adjustment
Place the pilot and electrode as shown in Fig. 11.
The pilot works correctly at pressures ranging from 5 - 12” WC.
IMPORTANT
To set the pilot without main burner operation, proceed as follows:
–
Move the jumper from terminals
"30-V11"
to terminals
"30-
VP"
, as given in Fig. 12, this way the main valve is cut out.
–
With the burner in the manual position, hold the air damper in
the minimum position and make the setting.
–
When the setting is correct, replace the jumper on
“30-V11”
.
WARNING
Measures must be respected.
Fig. 11
Probe
Electrode
Ignition pilot
Fig. 12
MB - Burner terminal strip
D2317
Содержание C9541000