Riello AARIA ONE Скачать руководство пользователя страница 14

RECyClING AND DISPOSAl

14

2.7

 

Troubleshooting

Power failure

If unit display does not turn on after you press 

 on remote 

control, and equipment does not turn on, ensure that:

 

equipment power plug, if any, is properly plugged

 

system main switch is set to “ON”

 

remote control batteries are well charged

If necessary, contact 

R

 Technical Support Service.

The climate control system does not sufficiently cool down or 
warm up the air

Check that:

 

the mesh filter is clean

 

doors or windows leading outdoors are closed

 

Unit air flow is free from obstructions

 

set temperature is the one actually required

If necessary, contact 

R

 Technical Support Service.

faults displayed on the control panel

Faults are communicated through a code on the unit’s control 
panel.

 Control panel

1

To restore operating conditions:

 

set the main switch to “Off”

 

allow 10 minutes

 

set main switch back to “ON”

 

press 

 on remote control

If the climate control system resumes normal operation, it means 
that shutdown was due to an erratic condition.

If  the  fault  occurs  again,  an  accurate  check  of  the  device 
components  is  required.  Contact 

R

  Technical  Support 

Service.

fault codes

Code

Description

Remarks

E1

Room probe fault

Cooling, Dehumidifying 
and Heating modes 
remain active
The adjustment only 
monitors the internal 
battery antifreeze

E2

Upper exchanger probe 
fault

The unit resets after 
problem resolution

E3

Outdoor air temperature 
probe fault

E4

Lower exchanger probe 
fault

Cooling, Dehumidifying 
and Heating modes 
remain active
Defrosting operates at 
fixed time cycles

E5

Upper fan motor fault

The unit resets after 
problem resolution

E6

Lower fan motor fault

E7

Communication error 
between unit and control 
panel
Communication error 
between electronic 
boards

E8

Compressor outlet probe 
fault

CP

Presence contact open

The unit resets upon 
contact closure

OF

Maximum level float 
triggering

The unit resets after 
problem resolution

In case of simultaneous failure of two probes, the unit turns 
off and resets after the resolution of the problem.

faults requiring intervention of the Technical Support Service

If any of these faults occurs:

 

the power cable is too hot or damaged

 

a strange noise is heard during operation

 

either the cut-out, a fuse or grounding switch is tripping 
all the time

 

a switch or a button is not operating properly

 

user smells burnt

 

water leakage from the unit

An accurate inspection of equipment components is required.

 

set the main switch to “Off”

 

immediately contact 

R

 Technical Support Service.

Normal noise during operation

During normal operation, the equipment may make particular 
noise linked to settling, expansion of the materials or refrigerant 
flow. This type of noise should not be considered a fault:

 

ticking  due  to  expansion  or  shrinking  of  materials  upon 
temperature changes

 

hiss due to refrigerant cycle inversion when changing op-
erating mode and toggling between Cooling and Heating 
or during defrost

 

swish similar to water flowing due to the refrigerant gas 
flowing in the unit

3

 

DISPOSAL

Packing materials must be disposed of separately, in order to be 
recovered and recycled. Equipment at end of life and flat bat-
teries  must  be  disposed  of  as  required  by  prevailing  law  and 

Содержание AARIA ONE

Страница 1: ...AARIA ONE INVERTER 02 2017 cod Doc 0083699 rev 0 EN USER INSTRUCTIONS ...

Страница 2: ...WEEE Directive 2012 19 EU ErP Directive 2009 125 EC and Regulation 2012 206 EC Dear Technician We would like to congratulate you on having recommended a R unit a modern product that is capable of ensuring maximum comfort at length with a high degree of reliability efficiency quality and safety While your technical skills and knowledge will certainly be more than sufficient this booklet contains al...

Страница 3: ...de p 9 Dehumidification mode p 9 Smart mode p 9 Ventilation mode p 10 Adjusting ventilation speed p 10 Maximum power function p 10 Motorised deflector p 11 Sleep function p 11 Timer function p 11 Hotel function p 12 button locking p 12 Auto restart function p 12 2 4 Temporary shutdown p 13 2 5 Stop for an extended period of time p 13 2 6 Maintenance p 13 Cleaning p 13 2 7 Troubleshooting p 14 3 DI...

Страница 4: ...of leaks please air the rooms thoroughly 9 According to EU Regulation no 517 2014 regarding certain fluorinated greenhouse gases the total amount of refrig erant contained within the installed system must be indi cated This information can be found on the unit technical data plate 9 This unit contains fluorinated greenhouse gases covered by the Kyoto protocol Maintenance and disposal activities mu...

Страница 5: ...ture is greater than 7 C temperature probe of the lower heat exchanger transmits the detected value to the main electronic board which activates cooling mode if the detected temperature is greater than 58 C increasing the speed of the lower fan until the tem perature is lower than 55 C cooling mode if the detected temperature is greater than 62 C turning off the unit which then restarts after 60 s...

Страница 6: ...n 8 Condensation discharge 9 Anti lifting bracket 10 Remote control 11 Terminal blocks 12 Air filter 13 Room air probe 14 Upper exchanger 15 Lower Fan 16 Condensation pump 17 Lower exchanger 18 Maximum level float 19 Level float 20 Condensation drain valve 21 Four way valve 22 Compressor 23 External air probe 4 12 23 22 3 6 7 8 9 1 13 5 2 10 11 14 15 16 17 19 18 20 21 ...

Страница 7: ...he selected parameter Decreases the value of the selected parameter Enables Automatic mode Enables Fan mode Enables Hotel function 1 Select required ventilation speed minimum medium maximum or automatic 2 Enables Maximum power function 1 Enables Timer function 2 Locks or unlocks key operation It activates the Sleep function It switches the device on and off It activates and deactivates the automat...

Страница 8: ...l with the contact being pro tected by a plastic film To remove the protective film 3V O L T S C R 2 0 2 5 remove the protective film Positioning The underside of the remote control has a magnet so it can be attached to the device or on any metal surface 2 2 Start up To switch on ON OFF set the system main switch to ON press A beep confirms receipt The unit s control panel turns on 9 Use the remot...

Страница 9: ...ess other buttons Switch off select another operating mode Alternatively press to turn unit off 9 In this mode the fan starts with a delay with respect to the compressor to prevent a jet of cold air in the environment 9 In this mode defrost cycles are periodically performed dur ing which the emission of hot air is stopped Dehumidification mode Dehumidification mode allows starting and using the sy...

Страница 10: ...perating mode Alternatively press to turn unit off Adjusting ventilation speed Ventilation speed can be adjusted in the following modes Cooling Heating Ventilation Set required ventilation speed as follows A Minimum speed B Medium speed C Maximum speed D Automatic speed bars light up in sequence E Maximum power function all bars flash A B C D E work Each press will select a different speed If sele...

Страница 11: ...pment any objects susceptible to get damaged in contact with water 9 When climate control system is turned off the horizontal deflector will close automatically 0 Do not manually move the deflector Sleep function The Sleep function allows user to select a time period through out which the equipment will change reference ambient tem perature A Sleep function on B Sleep function end and unit switch ...

Страница 12: ... cooling mode the temperature can be selected from 22 to 28 C in heating mode the temperature can be selected from 16 to 24 C To activate set the system main switch to ON use the control panel hold down for 10 seconds The symbol d5 flashes press The symbol En flashes The Hotel function is activated Not performing other operations for 3 seconds the setting is saved To deactivate hold down for 10 se...

Страница 13: ...ontrol the device cover the front panel and the mesh filter 9 All described operations MUST be carried out under the fol lowing conditions cold device device NOT supplied with electric power suitable personal protection equipment ON OFF 0 It is forbidden to open the access doors and carry out any cleaning operation before disconnecting the device from the power supply positioning the system main s...

Страница 14: ...Defrosting operates at fixed time cycles E5 Upper fan motor fault The unit resets after problem resolution E6 Lower fan motor fault E7 Communication error between unit and control panel Communication error between electronic boards E8 Compressor outlet probe fault CP Presence contact open The unit resets upon contact closure OF Maximum level float triggering The unit resets after problem resolutio...

Страница 15: ...RECyClING AND DISPOSAl 15 regulations ...

Страница 16: ...l 39 0442 630111 fax 39 0442 630371 www riello it As the manufacturer is constantly improving its products the aesthetic or dimensional features the technical data the equipment and accessories indicated could be subject to variations ...

Отзывы: