4
GENERAL INFORMATION
GENERAL INFORMATION
5
SYSTEM LAYOUT
UAC
EAF
SB
1
5
6
7
2
3
3
3
4
M
P
2
4
1
Storage cylinder
2
Probe/electronic anode pit (optional)
3
Flange for inspection/insertion of additional exchang-
ers
4
Probe pit
5
Thermometer connection
6
Insulation
7
Cover
M
Guide
UAC
Domestic hot water outlet
EAF
Domestic cold water inlet
P
Socket
SB
Storage cylinder drain
6
TECHNICAL SPECIFICATIONS
DESCRIPTION
7200/3F HV PLUS
800
1000
1500
2000
3000
Type of storage cylinder
Vertical, glazed
Heat exchanger layout
Horizontal
Storage cylinder capacity
749
955
1430
1990
2959
l
Useful non-solar volume (Vbu) (*)
420
490
790
1210
1745
l
Solar usable volume (Vsol) (**)
329
465
640
780
1214
l
Diameter of storage cylinder with insulation
990
990
1200
1300
1450
mm
Diameter of storage cylinder without insulation
790
790
1000
1100
1250
mm
Height with insulation
1875
2205
2185
2470
2680
mm
Height without insulation
1810
2140
2120
2425
2650
mm
Insulation thickness
100
mm
Total net weight
150
190
305
325
543
kg
First magnesium anode (Ø x length)
32x700
mm
Second magnesium anode (Ø x length)
-
32x400
32x700
mm
Flange diameter (external/internal)
290/220
mm
Diameter/length of sensor sockets
8/200
mm
Sleeve for electric heating element (***)
1" 1/2
Ø
Maximum operating pressure of storage cylinder
10
8
bar
Maximum operating temperature
99
°C
Discharges according to EN 12897:2006
∆
T=45 °C (am-
bient 20°C and storage at 65°C)
130
142
162
186
344
W
3,12
3,408
3,888
4,464
8,26
kWh/24h
Energy class
C
C
C
C
-
Insulation type
Soft PU shells
Vbu (*)
The non-solar usable volume indicates the quantity of water (in litres) heated directly by the thermal integration coil. It
is calculated as the volume between the upper part of the heater and the lower part of the thermal integration element
(integration coil lower turn). The value shown in the tale refers to the coil located in the central part of the puffer. The
position of the coil can be changed and the volume changes as a result.
Vsol (**)
The usable solar volume indicates the quantity of water (in litres) heated directly by the solar coil (placed in the lower
part of the heater) minus the non-solar volume (Vbu).
(***)
Electrical heating element (not supplied).