41
20155699
GB
Operating control and display
7.5
MANUAL menu path
Select MANUAL path to carry out actions as follows:
–
Switching burner ON and OFF
–
Presetting of burner firing rate
Display MANUAL menu
Use cursor keys
to select path
and press ENTER
to confirm.
The display shows the manual operation menu.
1
Pictogram manual operation
2
Start burner manually [off]
3
Adjust burner firing rate
4
Pictogram confirm settings
The “Burner ON” control loop does not need to be switched on to
start the burner from this menu. The user interface assumes con-
trol in this menu.
If there is no “Burner ON” signal from other sources (terminal
X10.2) software switches off the burner when you exit the menu.
NOTE:
leaving of window will terminate manual burner operation!
Adjust burner firing rate
Use cursor keys
to select adjustment of burner firing
rate in % and press ENTER
to confirm.
Change burner firing rate with the cursor keys
and
press ENTER
to confirm.
NOTE:
changes of burner firing rate are possible only while burner
is running.
If you want to adjust burner firing rate remember to start-up
the burner first.
7.5.1
Fault indication
Display burner faults
Use cursor keys
to select menu
and press ENTER
to confirm.
The display shows fault history selection menu.
1
Burner fault pictogram [selected]
Use keys
to select menu
and press ENTER
to confirm.
The display shows fault history menu.
1
Error code-display pictogram
2
Fault code (Last 10 faults are stored, no. 01 is the latest
fault)
3
Diagnostic code 1
4
Diagnostic code 2
5
Number of operating hours when fault has occurred
NOTE:
information concerning fault and diagnostic codes you may
find in the list of fault codes.
For fault analysis a fault code and diagnostic code D1 or D2
is required.
Fault unlock
Display unlocking faults
A fault is pending and the ERROR key is flashing.
Press ENTER-Taste.
BT300 is not locked anymore.
Changing from fault unlock to main menu
A fault is pending and the ERROR key is flashing
Press BACK key.
ENTER key isn't flashing any more. The display returns to
main menu.
An error number is flashing in the display on top left.
UI300 can be used as usual.
MANUAL
WARNING
If you carry out a manual start-up via display
BT300 no longer responds to “Burner ON” signal
input at connector X10.2.
Therefore that limiters, monitors and other similar
safety functions must not be operated with this in-
put!
Fig. 54
S9379
Fig. 55
S9355
Fig. 56
S9382
Содержание 20155654
Страница 2: ...Original instructions...
Страница 73: ...71 20155699 GB Appendix Electrical panel layout RS 310 410 E FGR...
Страница 74: ...20155699 72 GB Appendix Electrical panel layout RS 510 610 E FGR...
Страница 75: ...73 20155699 GB Appendix Electrical panel layout 01 2 3 4506 7 891 01...
Страница 76: ...20155699 74 GB Appendix Electrical panel layout...
Страница 77: ...75 20155699 GB Appendix Electrical panel layout 0 0 0 1 1 1 2 1 3 1 1 1 1 1 1 1 41 4 4 1 1 2 1...
Страница 78: ...20155699 76 GB Appendix Electrical panel layout 0 0 0 1 1 23 4567 23 4567...