background image

3

GENERAL INFORMATION

GENERAL INFORMATION

 

9

The system must be installed by specialist personnel. Use 

only the assembly material supplied with the solar collec-

tor. The supporting framework and all masonry or brickwork 

fixing points must be checked by a person expert in static 

loading, and must be suitable for the nature of the instal-

lation site.

 

9

The solar collector must only be installed on roofs or frames 

that are strong enough to support its weight. The strength 

of the roof or frame must be verified on site by a person 

expert in static loading before the solar collector is installed. 

During this process, it is important to verify the suitability 

of the supporting frame to hold the screw fasteners that fix 

the solar collector in place. An expert in static loading must 

verify that the entire frame complies with relevant stand-

ards, especially in areas liable to snow and areas exposed 

to high winds. Conditions (gusts of wind, formation of wind 

vortices, etc.) at the point where the solar collector is to be 

installed must be carefully considered since these can in-

crease the loads on the supporting structure.

 

9

Solar collector pipes must be connected through a (yel-

low-green) connector of at least 16 mm

2

 Cu (H07 V-U o R) 

to the potential compensation main bar. If a lighting rod is 

already installed, collectors can be integrated in the exist-

ing system. If this is not the case, it is possible to carry out 

earthing with a buried earth cable. The earth duct must be 

laid outside the house. Furthermore, the earth cable must 

be connected to the compensation bar through a duct hav-

ing the same diameter.

 

9

All pipes in the water circuit must be insulated in conform-

ity to relevant standards. Lagging and insulation must be 

protected against damage by the weather and birds and 

animals.

 

9

The collector is suitable for a minimum inclination of 15°, up 

to a maximum of 75°.

 

9

This instruction manual is an integral part of the product. It 

must be kept safe and must ALWAYS accompany the product, 

even if it is sold to another owner or transferred to another 

user or to another installation. If you lose this manual, or-

der a replacement immediately. Keep the product purchase 

documents to be presented to the 

R

 authorised Technical 

Assistance Service to request a service call under warranty.

 

9

Size the solar expansion tank so as to ensure complete ab-

sorption of the expansion of the fluid contained within the 

system, with reference to the prevailing regulations on the 

matter. In particular, consider fluid characteristics, consid-

erable fluctuation of service temperature and vapour that 

might be generated during solar collector stagnation stage. 

Proper size of expansion tank ensures setting off of all vol-

ume changes of the heat transfer fluid, avoiding excessive 

pressure increase. Limited pressure changes avoid reach-

ing safety valve opening pressure and the consequent fluid 

drainage.

PRECAUTIONS

 

9

Always wear safety goggles when drilling. Always wear safe-

ty shoes, cut-proof protective gloves and a safety helmet 

when performing installation work.

 

9

Before beginning installation work on roofs, install the nec-

essary fall prevention and fall arrest devices and ensure that 

all applicable safety standards are applied. Use only tools 

and materials that conform to the safety standards that are 

applicable in the place of work.

 

9

Use only overalls with harness (with lacing or restraining 

belt, connection ropes or bands, fall dampeners, heat sinks) 

certified for the risk detected according to the type of cover-

ing and allowing operating in complete safety.

 

9

The use of ladders leaned against walls can lead to serious 

falls if the ladder slips, slides of falls. When using ladders, 

always ensure that they are stable, and that suitable ladder 

stops are present. If possible secure the ladder with hooks. 

Make sure that there are no live electrical wires near the 

ladder.

 

0

Never attempt to install the system without using suitable 

personal  protection  equipment  and without  following  all 

applicable occupational safety standards.

 

0

Do not touch the product when barefoot or wet if it has any 

electrical accessories installed in it.

 

0

Never  clean  or  service  the  storage  cylinder  without  first 

turning the mains power switch OFF to disconnect all elec-

trical accessories (if fitted) from the mains electricity supply.

 

0

If solar plant pressure decreases, it is forbidden to top up 

with only water as there is a danger of freezing and over-

heating.

 

0

Do not dispose of packaging material into the environment, 

or leave it within the reach of children, since it can become 

a potential hazard. Dispose of packaging material in com-

pliance with applicable legislation.

Содержание 20127137

Страница 1: ...cod 20134586 rev 1 10 2017 RPS 25 4 EN INSTALLER TECHNICAL ASSISTANCE SERVICE AND USER MANUAL ...

Страница 2: ...manual and that it con forms to all applicable laws and standards 9 9This product must only be used for the purpose for which it is designed and made as specified by R R declines all responsibility contractual or other for damage to prop erty or injury to persons or animals caused by improper in stallation adjustment maintenance or use 9 9All servicing and repairs must be performed by a qualified ...

Страница 3: ...Assistance Service to request a service call under warranty 9 9Size the solar expansion tank so as to ensure complete ab sorption of the expansion of the fluid contained within the system with reference to the prevailing regulations on the matter In particular consider fluid characteristics consid erable fluctuation of service temperature and vapour that might be generated during solar collector s...

Страница 4: ... 20127468 CODICE TIPO CP25TSS S N FABBRICATO IN ITALIA da Riello S p A 13000000 BAR CODE 128B Anno di produzione SERIALE PROGRESSIVO EN 12975 1 ISO 9806 Certif Serial N Model Codice Modello Matricola Codice Tipo Dimensioni Superficie lorda Superficie di apertura Superficie assorbitore Peso a vuoto Massima pressione di esercizio Contenuto liquido Massima concentrazione glicole Liquido termovettore ...

Страница 5: ...IPTION RPS 25 4 Total area 2 301 m2 Exposed area 2 152 m2 Effective absorption area 2 140 m2 Water connections 2x 1 M 2x 1 F Ø Empty weight 44 0 kg Liquid content 1 7 l Recommended flow rate for each line per m2 of collector 30 l h x m2 Minimum flow rate for each line per m2 of collector 20 l h x m2 Maximum flow rate for each line per m2 of collector 200 l h x m2 Glass thickness 3 2 mm Thickness o...

Страница 6: ...he surrounding air and with total solar radiation of 1000 W m2 referred to the exposed area Pressure drop in solar collectors PRESSURE DROP mbar 10 0 20 30 40 50 0 100 200 300 400 500 600 700 800 900 1000 15 10 5 0 0 50 100 150 200 250 300 350 400 FLOW RATE l h With antifreeze water mix of 33 3 66 7 and heat transfer medium temperature 20 C WIND AND SNOW LOADS ON COLLECTORS The maximum allowable l...

Страница 7: ...tallation 8 HANDLING Separate the solar collector from the wooden pallet by removing the film wrapping Apply the data label provided in the document enve lope to the back of the solar collector Once you have removed the outer packaging proceed as follows to unpack and handle the solar collector Tilt the solar collector slightly and grip it at the four points shown A to lift it Use a hoist or other...

Страница 8: ... or sloping roof mounting frames to install any other equipment They are designed only for use with R solar water heating systems The installation of the solar field changes the pre existing struc ture of the roof It is necessary to check and possibly adapt all the roof elements to prevent any seepages or damages caused by wind and or snow 1 5 m 1 5 m 9 9Collectors must be installed at a safety di...

Страница 9: ...cannot be drilled use ballasts not supplied fairly distributed on all the bearing points as shown in the figure kg Wind speed km h Inclination angle of solar collectors Mass in kg distributed on the various bearing points to secure a collector from wind lifting 100 30 45 135 130 30 45 255 150 30 45 355 The indicated values are valid both for vertical and horizontal installation ...

Страница 10: ...t When tightening a fitting HOLD THE OPPOSITE FITTING STEADY WITH A SECOND TOOL to avoid damage seal ring Plug captive nut captive nut seal ring seal ring Plug captive nut seal ring Union captive nut When tightening a fitting HOLD THE OPPOSITE FITTING STEADY WITH A SECOND TOOL to avoid damage sensor pocket toward the heat transfer circuit from the heat transfer circuit captive nut Ring nut seal ri...

Страница 11: ...t exchange circuit towards the exchanger must be made on the side of probe socket T of the last collector of the series see figure Lines of solar collectors can be connected either in series pro vided each line contains no more than 6 collectors or in paral lel The complete circuit must always be hydraulically balanced See the following sample layouts Connection between collectors must be carried ...

Страница 12: ...ccessory 17 Heat transfer fluid recovery M Collector outlet R Collector return 3 1 1 R M C M 4 4 4 9 8 11 17 10 13 14 2 6 12 Valve group 5 7 15 16 T 9 9If copper pipes are used joints must be hot brazed 9 9We recommend the use of stainless steel pipes specially made for solar collectors for the outlet return and probe pipes The probe cable should be of the shielded type 9 9Do not use plastic or mu...

Страница 13: ...tem R M M T 14 DEVICE CLEANING AND MAINTENANCE 9 9The following operations must be exclusively performed by Technical Assistance Service It is recommended to clean the glass once a year as the deposit of dust and leaves reduces system efficiency The collector must be cleaned with water or water and soap Dry the collector at the end of cleaning operations 0 0Do not use abrasive products petrol or t...

Страница 14: ...To clean the glass once a year as the deposit of dust and leaves reduces system efficiency To check the heat transfer fluid to verify its effectiveness every two years To check the integrity of solar collector insulations and any expansion joints every two years For cleaning operations and solar collector efficiency check contact the nearest Technical Assistance Service End user ...

Страница 15: ...15 END USER END USER ...