INSTALLATION
Menu
Par.
No.
Description
Range
Default
setting
INSIEME
EVOe 25 K LN
Default
setting
INSIEME
EVOe 32 K LN
UM
Access
Zone 2 Heating Settings
3000
3200
Use of Zone 2 control accessory
0 = NO
1 = Yes
If Zone 2 control accessory is used, AT and OT inputs
are not enabled. AT input is used only to enable the
night reduction on all the active zones (Par. 2001= 2
and 3)
0…1
0
0
I
3000
3201
Zone 2 mode
0 = direct
1 = mixed
0…1
1
1
I
2000
2203
Zone 2 heating setpoint in 0 and 3 heating modes
The thermal unit adjustment determines the boiler
setpoint in heating mode, using the highest value
among the requests of all the active zones (Par. 1101,
1201, 1301)
If Zone 2 is configured as mixed, the value set in
parameter 1113 will be used as setpoint.
BT: (Par. 2221,
45)
AT: (Par.
2221,Par.
2024)
70 (AT)
45 (BT)
70 (AT)
45 (BT)
°C
U
2000
2219
Zone 2 maximum heating setpoint at the minimum
external temperature
The range of this parameter is limited by the values
of the Minimum (Par. 2023) and Maximum (Par. 2024)
setpoints.
BT: (Par. 2221,
45)
AT: (Par.
2221,Par.
2024)
82 (AT)
45 (BT)
82 (AT)
45 (BT)
°C
I
2000
2221
Zone 2 minimum heating setpoint at basic external
temperature (Par. 2222)
It sets the minimum heating setpoint when the
external temperature is equal to the value set in
parameter 2222 (basic external temperature).
BT: (20, Par.
2219)
AT: (Par.
2023,Par.
2219)
30 (AT)
20 (BT)
30 (AT)
20 (BT)
°C
I
2000
2220
Zone 2 minimum external temperature
It defines the minimum external temperature to
which the maximum heating setpoint Par. 2219 must
be associated.
-20…5
-20
-20
°C
I
2000
2222
Zone 2 basic external temperature
It sets the external temperature at which the boiler
setpoint must be reduced, according to the value de-
fined in parameter 2221.
5...30
20
20
°C
I
2000
2225
Zone 2 summer/winter switching
It blocks the heating request when the external tem-
perature is greater than this setpoint.
0...35
20
20
°C
I
2000
2230
Parallel shift of direct Zone/Zone 1 climatic curve
-10…10
0
0
°C
U
2000
2231
Zone 2 mild climate temperature compensation
0...20
0
0
°C
I
2000
2232
Zone 2 ambient temperature nominal value
When an OpenTherm (OT) ambient thermostat is con-
nected to the zone control accessory, this parameter
is not used.
5...35
20
20
°C
I
2000
2234
Compensation factor of Zone 2 external temperature
0...100
50
50
%
I
2000
2235
Zone 2 mixing valve closing time
0...240
140
140
sec
I
2000
2236
Zone 2 mixing valve PID P
0...99
5
5
I
2000
2237
Zone 2 mixing valve PID I
0...99
10
10
I
2000
2238
Zone 2 valve operating time
0...255
2
2
I
2000
2239
Supply Extra
Only for MIX Zone
0...20
5
5
°C
I
2000
2240
Zone 2 circulator post-circulating time
0...60
30
30
sec
I
2000
2241
Zone 2 delivery overtemperature protection
0...100
55
55
°C
I
2000
2242
Zone 2 overtemperature control time
0…240
0
0
min
I
2000
2243
Zone 2 overtemperature stand-by time
0…240
2
2
min
I
2000
2244
Zone 2 system reset time
0…240
2
2
min
I
Zone 3 Heating Settings
3000
3300
Use of Zone 3 control accessory
0 = NO
1 = Yes
If Zone 3 control accessory is used, AT and OT inputs
are not enabled. AT input is used only to enable the
night reduction on all the active zones (Par. 2001 = 2
and 3).
0…1
0
0
I
3000
3301
Zone 3 mode
0 = direct
1 = mixed
0…1
1
1
I