TECHNICAL ASSISTANCE SERVICE
38
WARNING LEDS AND ERRORS
THE MAIN CONTROL PANEL
Green LED (3)
Off = boiler in stand-by, burner out
On = burning lit, boiler functioning normally.
Red LED (5)
Safety shutdown:
an error code flashes on the display.
Burner lockout:
the red LED lights and an error code
flashes on the display.
No error code is shown in OFF/RESET mode (
0
). To
visualise any system errors, turn the function selector to
"
}
" or "
{
".
Error codes are displayed normally in combustion analy-
sis and frost protection modes.
To restore normal functioning, turn the function selector
to “
0
” (OFF/RESET) then return it to its previous position:
Summer "
}
", or Winter "
{
".
If the boiler does not restart after a number of resets, call
your local Technical Assistance Centre.
3
5
0
bar
4
1
3
2
°C
0
120
20
100
40
80
60
CODE
DESCRIPTION OF ERROR
STATUS
AL10
Ignition attempts finished (no flame/condensate detected)
Lockout
AL20
Temperature threshold error
Lockout
AL21
Low temperature thermostat/condensate pump safety error
Lockout
AL29
Flue gas sensor overtemperature error
Lockout
AL60
Storage cylinder temperature sensor error
Signalling
AL71
CH flow temperature sensor error (open/short circuit)
Shutdown
AL73
CH return temperature sensor error (open/short circuit)
Shutdown
AL74
Overtemperature for no water circulation
Lockout
AL91
Primary heat exchanger needs cleaning (call Technical Assistance)
Signalling
AL28
CH flow/return sensors temperature differential error
Lockout
AL26
CH return overtemperature
Lockout
AL79
CH flow overtemperature, or flow/return sensors temperature differential error
Lockout
AL41
Low CH water pressure
Shutdown
AL40
Low CH water pressure (after 10 minutes)
Lockout
AL34
Fan speed error
Lockout
AL52
Generic electronic error
Lockout
AL55
Boiler configuration error (configuration jumper missing)
Lockout
Содержание 20044965
Страница 51: ...TECHNICAL ASSISTANCE SERVICE 51 ...