BURNER OPERATION

BURNER STARTING
• Load control close.

Fan motor starts.

• Servomotor starts: 

130°  rotation  to  right,  until  contact  is  made  on  cam
1)(A) page 12.
The air damper is positioned to MAX. output.

• Pre-purge stage with air delivery at MAX. output. 
• After pre-purge stage, servomotor rotates to left up to

the angle set on cam 3)(A) page 12 for MIN. output.

• The air damper and the gas butterfly are positioned to

MIN. output.

• Ignition electrode strikes a spark.
• Pilot valve opens. The pilot flame is ignited.
• After  about  12  s  the  main  flame  ignites  and  starting

cycle ends.

STEADY STATE OPERATION
At  the  end  of  the  starting  cycle,  the  servomotor  control
then  passes  to  the  load  control  for  boiler  pressure  or
temperature.
(The  control  box  continues,  however,  to  check  that  the
flame is present and that the air pressure switch is in the
correct position.)
• If the temperature or pressure is low, the burner pro-

gressively increases its output to the MAX. value.

• If the temperature or pressure is high, the burner pro-

gressively decreases its output to the MIN. value.
And so on.

• The  burner  locks  out  when  demand  for  heat  is  less

than the heat supplied by the burner at min. output. 
Load control opens. The servomotor returns to the 0°
angle  limited  by  contact  with  cam  2.  The  air  damper
closes  completely  to  reduce  thermal  dispersion  to  a
minimum. 

Every time output is changed, the servomotor automati-
cally  modifies  gas  delivery  (gas  butterfly  valve)  and  air
delivery (fan air damper).

Switching  times  are  given  in  seconds,  in  the  burner
startup sequence.

Legend for the times
t1

Pre-purge time with air damper open

t2

Safety time

t3

Pre-ignition  time,  short  (ignition  transformer  on
terminal 16)

t4

Interval between start of t2 and release of valve
at terminal 19

t5

Interval  between  end  of  t4  and  release  of  load
controller or valve at terminal 20

t5

Running time of air damper into OPEN position

t6

Running time of air damper into low-flame posi-
tion (MIN)

t7

Permissible after-burn time 

t8

Interval until OPEN command for the air damper
is given 

FIRING FAILURE
If the burner does not fire, it locks out within 2.5 seconds
from opening the pilot  valve and then within 5 seconds
from opening the main valves.

BURNER FLAME GOES OUT DURING OPERATION
If the flame should accidentally go out during operation,
the burner will lock out within 1s.

LFL 1.335 Series 01

t1
t2
t3
t4

30

2
4

20

t5
t6
t7
t8

optional
optional

12

4

(A)

Full Modulation

D2273

Low - High

D2274

(B)

LFL 1.335 Series 01

Содержание 20011691

Страница 1: ...2915849 8 06 2014 Installation use and maintenance instructions Gas burners Low High Low or Modulating Operation CODE MODEL 20011691 RS 160 M LN 3788070 RS 160 M LN 3788075 RS 160 M LN GB...

Страница 2: ......

Страница 3: ...present check 13 MAINTENANCE 14 Burner operation 15 Burner faults 16 Procedure to refer burner operating condition in high altitude plants 17 APPENDIX Spare parts list 18 Burner start up report 21 WAR...

Страница 4: ...uel Natural gas max delivery SCFH 7046 pressure at max delivery 2 WC 7 Operation Low high or modulating Standard applications Boilers water steam thermal oil Ambient temperature F 32 104 0 40 C Combus...

Страница 5: ...ING TO UL STANDARDS see page 9 Model RBNA Code Riello Code Voltage Flame safeguard RS 160 M LN tbd 20011691 208 230 3 60 Burner mounted RS 160 M LN C9544000 3788070 460 3 60 Burner mounted RS 160 M LN...

Страница 6: ...iler mounting flange 26 Flame stability disk 27 Pilot burner Two types of burner failure may occur FLAME SAFEGUARD LOCK OUT if the flame relay 13 A pushbutton lights up it indi cates that the burner i...

Страница 7: ...nch length 6 6 ft COMMERCIAL BOILERS C IMPORTANT The RS 160 M LN burner is suitable for operation on ei ther flame inversion boilers or boilers with combustion chambers featuring flow from the base th...

Страница 8: ...output of the burner as follows subtract the combustion chamber pressure from the gas pressure measured at test point 1 B Find the nearest pressure value to your result in diaram A Read off the corre...

Страница 9: ...isengage the swivel joint 7 from the graduated sector 8 remove the screws 2 from the slide bars 5 remove the two screws 4 and pull the burner back on slide bars 5 by about 4 disconnect the wires from...

Страница 10: ...le always keep the ring nut closed notch 0 if air recovery is required the nut may be opened following the indications in diagram C Diagram C indicates an optimal regulation for a type of boiler seen...

Страница 11: ...trical layouts The manufacturer declines all responsibility for modifications or connections different from those shown in the electrical layouts Check that the electrical supply of the burner corre s...

Страница 12: ...following adjustments must also be made Open manual valves up stream from the gas train Adjust the low gas pressure switch to the start of the scale A Adjust the high gas pressure switch to the end of...

Страница 13: ...r the stroke end cam 2 to exploit as far as possible the variable profile cam Trim potentiometer POS Limits an intermediate operating position between MAX and MIN supplying power to the P terminal in...

Страница 14: ...profile cam 4 D If a lower modulation minimum is required than the level set on cam 3 of the servomotor 20 decrease the cam setting INTERMEDIATE OUTPUTS With the switch C in the AUTO position the sli...

Страница 15: ...burner adjustments with the maximum gas pressure switch set to the end of the scale B With the burner operating at MAX output reduce the adjustment pressure by slowly turning the adjustment dial antic...

Страница 16: ...ened Clean the outside of the burner taking special care with the swivel joints and cam Combustion Adjust the burner if the combustion values found at the beginning of the operation do not comply wit...

Страница 17: ...plied by the burner at min output Load control opens The servomotor returns to the 0 angle limited by contact with cam 2 The air damper closes completely to reduce thermal dispersion to a minimum Ever...

Страница 18: ...air pressure control Every air pressure failure after this moment in time leads to lock out too Lock out due to a fault in the flame supervision circuit Interruption of startup sequence because the po...

Страница 19: ...8977 9361 7500 7404 7500 7673 7955 8258 8564 8892 9238 9618 10029 8000 7897 8000 8185 8485 8809 9135 9484 9854 10259 10698 8500 8391 8500 8697 9016 9359 9705 10077 10470 10900 11367 9000 8885 9000 920...

Страница 20: ...8 27 42 41 73 5 23 68 70 49 51 65 69 24 62 22 6 19 13 52 1 2 29 12 9 17 21 20 4 3 44 28 48 50 65 66 63 65 64 14 8 7 39 38 36 30 31 40 32 10 37 33 35 34 54 53 56 57 59 58 55 61 60 45 16 45 46 71 72 67...

Страница 21: ...11 3012627 BAR EXTENSION 02356XXXXXX 11 3013686 BAR EXTENSION 02366XXXXXX 12 3012948 AIR PRESSURE SWITCH 13 3013127 BASE PLATE 13 3013205 BASE PLATE 14 C5360008 3012955 CONTROL BOX LFL 1 335 15 30120...

Страница 22: ...SLEEVE 56 3012641 BRACKET 57 3012642 SHUTTER 58 3012643 END CONE 59 3012647 CENTERING SUPPORT 60 3003322 CONNECTOR 61 3013096 MANIFOLD 02356XXXXXX 62 3006132 SHAFT AND RING 63 3012644 GRADUATE SECTOR...

Отзывы: