Riello UPS RB1-R-EMBS-32A-2P-RTY Скачать руководство пользователя страница 3

 

RBQS00062REV1 

I N T R O D U C T I O N

I N T R O D U C T I O N

I N T R O D U C T I O N

I N T R O D U C T I O N     

    

 

 

Thank you for purchasing the RMBS, this is a 19inch rack-mounted unit specifically designed to allow iso-
lation and removal UPS equipment, without causing interruption to the supply of power to connected 
loads. 

Please read this manual thoroughly and follow the instructions carefully. Before attempting to install or 
use the RMBS, familiarize yourself with the RMBS and its operation. 

Warning exposure to hazardous voltages may occur if the installation procedure is not followed. 

It is recommended that installation of this product is carried out by a qualified electrician 

32-63A RACK-MOUNT ROTARY BYPASS SWITCH 

 

WARNING! 

 

HAZARDOUS VOLTAGES MAY BE PRESENT WITHIN THIS UNIT 

THIS UNIT IS SUPPLIED FROM MULTIPLE SOURCES, ENSURE ALL SOURCES ARE 

ISOLATED BEFORE COMMENCING WORK  

WARNING! 

 

BEFORE OPERATION OF THIS BYPASS SWITCH 

ENSURE THE UPS IS IN NORMAL OPERATION AND NOT IN BATTERY MODE 

REFER TO UPS USER MANUAL 

WARNING! 

 

INCORRECTION OF OPERATION OF THIS SWITCH MAY RESULT IN DAMAGE TO 

THE UPS AND/OR INTERUPTION OF LOAD 

FOLLOW SWITCHING INSTRUCTIONS CAREFULLY 

Содержание RB1-R-EMBS-32A-2P-RTY

Страница 1: ...RBQS00062REV1 32 63A RACK MOUNT ROTARY BYPASS SWITCH INSTALLATION MANUAL ...

Страница 2: ...RBQS00062REV1 I N T R O D U C T I O N Contents Introduction Electrical Connections Operation Electrical Drawings Technical Specification 32 63A RACK MOUNT ROTARY BYPASS SWITCH ...

Страница 3: ...s operation Warning exposure to hazardous voltages may occur if the installation procedure is not followed It is recommended that installation of this product is carried out by a qualified electrician 32 63A RACK MOUNT ROTARY BYPASS SWITCH WARNING HAZARDOUS VOLTAGES MAY BE PRESENT WITHIN THIS UNIT THIS UNIT IS SUPPLIED FROM MULTIPLE SOURCES ENSURE ALL SOURCES ARE ISOLATED BEFORE COMMENCING WORK WA...

Страница 4: ...rear cover and secure Terminate the cables in the terminals marked UPS In on the cover plate Connection of the Output from the UPS Feed the UPS Output cable through the gland on the rear cover and secure Terminate the cables in the terminals marked UPS Out on the cover plate Connection of the Load Equipment Feed the Load cable through the gland on the rear cover and secure Terminate the cables in ...

Страница 5: ... ensure the unit is in internal bypass operation Rotate the switch to the UPS Bypass position the load is now powered by the RMBS The UPS still has mains supply voltage present for testing purposes 32 63A RACK MOUNT ROTARY BYPASS SWITCH Initial Switch On Ensure all connections are correct Ensure the rotary switch in the NORMAL position Ensure the rotary switch cover plate is attached firmly in pla...

Страница 6: ... Transfer From UPS to Bypass Operation For Maintenance with Complete Isolation of the UPS Remove the rotary switch cover plate using the two thumb screws If the interlock connections have been installed the UPS should automatically transfer to internal UPS by pass If however they have not been installed then follow the UPS instructions to transfer the UPS to in ternal bypass operation Check the UP...

Страница 7: ...RBQS00062REV1 E L E C T R I C A L D R A W I N G S 32 63A RACK MOUNT ROTARY BYPASS SWITCH ...

Страница 8: ...RBQS00062REV1 T E C H N I C A L T E C H N I C A L T E C H N I C A L T E C H N I C A L S P E C I F I C A T I O N 32 63A RACK MOUNT ROTARY BYPASS SWITCH DIMENSIO NS ...

Отзывы: