46
T
ABLES OF STATES
,
MEASUREMENTS
,
NOMINAL DATA AND COMMANDS
REGISTER
(1)
STATES
BIT
(2)
NUMBER
ADDRESS
NUMBER
ADDRESS
1
0
1
0
Test in progress
[0=No / 1=YES]
2
1
3
2
Shutdown active
[0=No / 1= YES]
4
3
5
4
Battery charged
[0=No / 1= YES]
6
5
Battery charging
[0=No / 1= YES]
7
6
Bypass bad
[0=No / 1= YES]
8
7
9
8
Normal operation
[0=No / 1= YES]
10
9
11
10
On bypass
[0=No / 1= YES]
12
11
Battery low
[0=No / 1= YES]
13
12
Battery working
[0=No / 1= YES]
14
13
UPS locked
[0=No / 1= YES]
15
14
Output powered
[0=No / 1= YES]
16
15
2
1
17 28
16 27
Input Mains present
[0=No / 1= YES]
29
28
Alarm temperature
[0=No / 1= YES]
30
29
Alarm overload
[0=No / 1= YES]
31
30
UPS failure
[0=No / 1= YES]
32
31
3
2
33 48
32 47
4
3
49 63
48 62
Communication lost with UPS
[0=No / 1= YES]
64
63
5 8
4 7
65 128
64 127
(1)
The register number
n
must be addressed
n-1
in the data packet
(2)
The bit number
n
must be addressed
n-1
in the data packet.
REGISTER
(1)
MEASUREMENTS
UNIT
NUMBER
ADDRESS
9 11
8 10
12
11
Input mains star voltage V1
V
13
12
Input mains star voltage V2
V
14
13
Input mains star voltage V3
V
15
14
Input current phase L1
0.1*A
16
15
Input current phase L2
0.1*A
17
16
Input current phase L3
0.1*A
18
17
Input frequency
0.1*Hz
19 21
18 20
22
21
Bypass mains star voltage V1
V
23
22
Bypass mains star voltage V2
V
24
23
Bypass mains star voltage V3
V
25
24
Bypass frequency
0.1*Hz
26
25
Output star voltage V1
V
27
26
Output star voltage V2
V