22 

 

 

 

 

 

assistance is required. Please complete this form, fax it or mail it at the address/fax  above, or send an e-mail 
with the information listed below to:  

[email protected]

 

 

 

INSTALLATION PRECAUTIONS 

 

AIR FOR COMBUSTION 

Do not install burner in room with insufficient air for combustion. Be sure there is an adequate air supply for 
combustion if the boiler/furnace room is enclosed. It may be necessary to create a window to permit sufficient 
air to enter the boiler/furnace room. The installer must follow local ordinances in this regard.  
CANADA: It is suggested that the installer follow CSA standard B139. 
USA: It is suggested that the installer follow NFPA manual #31. 

 

CHIMNEY 

Be sure chimney is sufficient to handle the exhaust gases. It is recommended that only the burner be connected 
to the chimney. Be sure that it is clean and clear of obstructions. 

 

OIL FILTER 

An external oil filter is REQUIRED, even though there is an internal strainer in the pump. The filter should be 
replaced at least once a year, and the filter container should be thoroughly cleaned prior to installing a new filter 
cartridge

 

DRAFT 

Follow the instructions furnished with the heating appliance.

 

 

The pressure in the combustion area should be kept as close to zero as possible. The burner will operate with a 
slight draft or pressure in the chamber. 

 

ELECTRICAL CONNECTIONS 

CANADA 
All electrical connections should be done in accordance with the C.E.C. Part 1, and all local codes. The system 
should be grounded. 
USA 
All electrical connections should be done in accordance with the National Electrical Code, and all local 
ordinances

The system should be grounded. 

 

CONTROL BURNER OPERATION 

Check out the burner and explain its operation to the homeowner. Be sure to leave the Owner’s Instruction sheet 
with the homeowner. 

 

FIRE EXTINGUSHER 

If required by local codes, install an approved fire extinguisher. 

 

 

ELECTRICAL CONNECTIONS 

 
In most localities, a number 14 wire should be used inside a metal conduit. The system should be grounded. A 
service switch should be placed close to the burner on a fireproof wall in an easily accessible location. 
 

 
 
 

 

Содержание RIELLO 40 F3

Страница 1: ......

Страница 2: ...ALLATION OPERATING MANUAL RESIDENTIAL OIL BURNERS NOTE The settings in this manual are for retrofit applications If this burner is being installed on a packaged unit burner comes with the boiler or fu...

Страница 3: ...em 13 Two Line Lift System 14 SETTING THE AIR ADJUSTMENT PLATE 14 BURNER ADJUSTMENT TABLES 15 AMULET INSTALLATION INSTRUCTIONS 16 SEQUENCE OF OPERATION 17 18 EXPLODED PARTS VIEW 19 PARTS LIST 20 START...

Страница 4: ...L FIRING RATE 0 50 to 0 95 US GPH EFFECTIVE OUTPUT 70 000 to 133 000 BTU h VOLTAGE Single Phase 120V 60Hz 10 15 ABSORBED ELECTRICAL POWER 155 Watts MOTOR rated 3250 rpm Run Current 2 2 AMP CAPACITOR 1...

Страница 5: ...UEL OIL FIRING RATE 0 75 to 1 65 US GPH EFFECTIVE OUTPUT 105 000 to 231 000 BTU h VOLTAGE Single Phase 120V 60Hz 10 15 ABSORBED ELECTRICAL POWER 175 Watts MOTOR rated 3250 rpm 2 2 AMP CAPACITOR 12 5 M...

Страница 6: ...ER SERIAL NUMBER IDENTIFICATION The Riello 15 character serial number example 99 A 8511111 00025 is identified as follows 99 last two digits of the year of manufacture A BI week of manufacture 8511111...

Страница 7: ...BOLTS 3 from FRONT PLATE 4 of the BURNER CHASSIS Align the two holes on the AIR TUBE HOLDING PATE 5 with the two holes on the BURNER CHASSIS FRONT PLATE with the BOLTS 3 removed Replace the BOLTS and...

Страница 8: ...e heating unit by insetting the AIR TUBE through the BURNER ACCESS HOLE 8 and into the appliance making sure the BOLTS 1 line up with the two HOLES 5 in the ADJUSTABLE COLLAR 9 Secure the burner in pl...

Страница 9: ...D WITH A REFRACTORY MATERIAL IT IS IMPERATIVE THAT THE END CONE NOT PROTRUDE INTO THE CHAMBER AREA AS EXCESSIVE HEAT AT BURNER SHUT DOWN MAY DAMAGE THE END CONE INTERNAL FACTORY WIRING M 1 2 3 4 5 6 7...

Страница 10: ...E N D E D F I E L D W I R I N G F O R TYPICAL APPLICATIONS 120VAC 60HZ L N A U X N L AIR SHUTTER M O T O R 1 2 0 V O P E R A T E D S Y S T E M S 24V OPERATED SYSTEMS 3 6 2 4 1 5 120VAC 60HZ L N A U X...

Страница 11: ...OZZLE into the NOZZLE ADAPTER and tighten securely Do not over tighten D Replace adapter with nozzle installed into drawer assembly and secure with screw 1 INSTALLATION REMOVAL OF DRAWER ASSEMBLY Remo...

Страница 12: ...ge to the pump shaft seal NOTE Pump pressure must be set at time of burner start up A pressure gauge is attached to the PRESSURE PORT 7 for pressure readings Two PIPE CONNECTORS 4 are supplied with th...

Страница 13: ...30 40 260 80 6 5 2 0 195 60 325 100 B Connect the pipe connector to the SUPPLY PORT 5 of the pump Attach the NPT adapter to the pipe connector Attach the required piping to this pipe adapter Be sure t...

Страница 14: ...etween the fuel tank and the burner pump PUMP PURGE NOTE To protect the pump gears it is advisable to lubricate the pump prior to purging a lift system Apply oil through the VACUUM PORT C A SINGLE LIN...

Страница 15: ...ly 1 is operated on a 120v 60Hz motor and the burner motor will not operate until the air shutter is in its fully open position Set the air plate 4 setting according to OEM setup information or by fol...

Страница 16: ...3 5 1 50 1 25 x 60 80 145 10 3 0 4 25 1 65 1 35 X 60 80 145 10 4 0 6 0 NOTE The above set up charts are a starting point only The burner and appliance must be properly set up using proper combustion t...

Страница 17: ...will not fit easily onto the tube remove a small amount of the inner diameter with a sharp knife to provide the necessary clearance The diagram below shows the proper position of the amulet after inst...

Страница 18: ...OPEN SWITCHES POWER TO BURNER MOTOR AIR SHUTTER BURNER MOTOR STOPS ELECTRIC AIR SHUTTER CLOSES open AC closed T X RIELLO 40 SERIES OIL BURNER EQUIPPED WITH ELECTRONIC AIR SHUTTER NORMAL OPERATIONAL S...

Страница 19: ...FOR CALL FOR HEAT MOTOR PREPURGE IGNITION OIL VALVE FLAME POWER LOCK OUT THERMOSTAT OR LIMIT CONTROL ELECTRIC AIR SHUTTER MODES 40 SERIES OIL BURNER MODES CONSTANT UNITERUPTED 120V POWER SUPPLY TO ELE...

Страница 20: ...C6501000 F3 F5 I O manual Rev4_3 19...

Страница 21: ...on Head 6 271T1 40 3948976 VSBT Combustion Head 3 40 3948973 Short Combustion Head 6 271T1 3006968 Turbulator Disc 3006968 Turbulator Disc 41 3006977 Turbulator Disc 41 3006977 Turbulator Disc 42 3006...

Страница 22: ...fo GAS Nozzle Info Gas Supply Pressure Pump Pressure Pump pressure Air Setting Turbulator setting Air Setting Head Setting Draft Over fire Draft breech Draft Over fire Draft breech CO2 CO O2 CO2 CO O2...

Страница 23: ...strainer in the pump The filter should be replaced at least once a year and the filter container should be thoroughly cleaned prior to installing a new filter cartridge DRAFT Follow the instructions f...

Страница 24: ...C6501000 F3 F5 I O manual Rev4_3 23...

Страница 25: ...02043 Phone 781 749 8292 Toll Free 800 992 7637 Fax 781 740 2069 www riellousa com 2165 Meadowpine Blvd Mississauga ON L5N 6H6 Phone 905 542 0303 Toll Free 800 387 3898 Fax 905 542 1525 www riellocan...

Отзывы: