TECHNICAL FEATURES

 

DIMENSIONS 

Thermal output

520 - 1050 kW        447.200 - 903.000 kcal/h 

Fuel

Natural gas Pci 8 - 10 kWh/m

3

 = 7000 - 8600 kcal/m

3

Minimum gas pressure

For maximum output 12.3 mbar are needed measured at the coupling
with nil pressure in the combustion chamber and gas with calorific value
of 8600 kcal/m

3

Maximum gas pressure

150 mbar

Electrical supply

Three phase 380 V  + 10%  - 10%  ~ 60Hz with neutral

Motor

3.4 A / 380 V

Ignition transformer

Primary: 1.8A / 220V - Secondary: 1 x 8 kV - 30 mA

Absorbed electrical power

1.9 kW

1

√ Air shutter control

2

√ Air shutter lock-nut

3

√ Control box re-set button

4

√ Fair leads

5

√ Wiring terminal block

6

√ Re-set push-button of the

motor overload relay

7

√ Air pressure switch

8√

Gas pressure test-point

Fig. 1

8

7

5

4

3

2

1

S7513

6

*

Length available with special blast tube to be separately required.

Burner

410

770

227

*

360

48

5

131

37

0

19

5

ø 175

Rp 2

S7497

S7498

Boiler front-plate

drilling

195

19

5

185

M12

D1785

Содержание 3751882

Страница 1: ...2915862 1 Installation use and maintenance instructions Gas burner CODE MODEL TYPE 3751882 GAS 6 518 T80 ...

Страница 2: ...e phase 380 V 10 10 60Hz with neutral Motor 3 4 A 380 V Ignition transformer Primary 1 8A 220V Secondary 1 x 8 kV 30 mA Absorbed electrical power 1 9 kW 1 Air shutter control 2 Air shutter lock nut 3 Control box re set button 4 Fair leads 5 Wiring terminal block 6 Re set push button of the motor overload relay 7 Air pressure switch 8 Gas pressure test point Fig 1 8 7 5 4 3 2 1 S7513 6 Length avail...

Страница 3: ...nd withdrawing the group A from the holding bars 3 Fix the group B to the boiler front plate 4 using the gasket 5 provided as acces sory 2 3 5 4 1 A B S7499 1 Gas pipe line 7 Gas shut off valve 2 Cock valve 8 Burner 3 Filter 9 Gas safety shut off valve 4 Pressure stabilizer 10 Gas leak control device 5 Pressure test point 11 Isolator joint 6 Minimal gas pressure switch 5 8 7 9 5 6 4 3 10 2 1 S7514...

Страница 4: ...in 800 kW it is necessary a gas pressure of 11 mbar and the combustion head set as indicated at page 7 If the combustion chamber is pressurized at 2 mbar the pressure detected at the test point 8 is 11 2 13 mbar If this value is too high for very low gas pipework pressures the gas gear 6 page 7 could be more open Do not decrease the pressure at the coupling under the values shown in the diagram Ou...

Страница 5: ...ce K1 Relay MB Burner terminal strip MV Fan motor PA Air pressure switch RMG Control box RT Overload S Suppressor SO Ionisation probe TA Ignition transformer TB Burner earth KEY TO LAYOUT ATTENTION In the case of phase phase feed a bridge must be fitted on the control box terminal board between terminal 6 and the earth terminal ...

Страница 6: ...ving the metal weldnuts from the pre sheared holes and inserting a commun fair lead for the passage and the clamping of the leads NOTES Do not exchange the neutral wire with the phase avoid the plug pin connection Carry out a safe earth connection Check the stop of the burner by opening the boiler thermostat and the burner lock out by disconnecting the lead from the flame probe WARNING When closin...

Страница 7: ...ent pressure by turning slowly clockwise the knob till reaching the burner lock out Thereafter turn the knob anticlockwise for 1 mbar and repeat the burner start up for checking the regularity if lock out intervenes turn the knob anticlockwise for 0 5 mbar CAUTION do not turn the ionization probe maintain the drawing position should it be close to the ignition elec trode damage may occur to the co...

Страница 8: ... the plate 4 Tighten the screws 1 Gas setting Loosen the screw 5 move the ring 6 so that the pointer 7 is coincident with the desired set point 8 Tighten the screw 5 Attention the set point number is the same for air and gas setting and is given by the following diagram Example the burner is installed on a boiler of 810 kW assuming an efficiency of 90 the burner output should be 900 kW From the di...

Страница 9: ...he burner normally supplies a higher current value so that no check is needed However if a measurement of the ionization current is required it is necessary to disconnect the probe lead and insert a d c microamperometer MOTOR LOCK OUT This is caused by the thermal protector relay in case of overloading or by the lacking of the phase To clear pushdown the appropriate knob after having removed the p...

Страница 10: ...ailed The burner does not pass through the pre purge peri od and the control box goes to lock out The air pressure switch does not change over it has failed or the air pressure is too low combustion head bad set Flame simulation exists or the flame really lights The burner does not start at the thermostat closing be cause of Gas is not supplied The gas pressure switch does not close incorrectly ad...

Страница 11: ...lame signal Electrical supply lower than 170V Lock out Extraneous light Key Off Yellow Green Red SIGNAL PROBABLE CAUSE 2 flashes The flame does not stabilise at the end of the safety time faulty ionisation probe faulty or soiled gas valves neutral phase exchange faulty ignition transformer poor burner regulation insufficient gas 3 flashes Min air pressure switch does not close air pressure switch ...

Страница 12: ...RIELLO S p A Via degli Alpini 1 I 37045 Legnago VR Tel 39 0442 630111 Fax 39 0442 630375 http www rielloburners com Subject to modifications ...

Отзывы: