FUEL OIL GRAVITY FEED SYSTEMS 

Gravity system (fuel oil with viscosity max. 7°E at 50°C)

Pump priming: loose the tap of the
vacuometer plug 5) (fig. 1) and wait
for the fuel flow.

H

: Difference in the pipes height.

L

: Length of the suction pipe.

SUCTION SYSTEM (fuel oil with viscosity max. 7°E at 50°C)

Not advised, to be used only in case of previously existing system.

Never overcome the max. de-
pression of 0.5 bar (38 cm Hg).
With higher values the fuel ema-
nates gas.
The pipes shall be perfectly
sealed. When the tank is placed
below of the burner level, the re-
turn pipe should reach the same
level of the suction pipe.
In this case the foot valve is not
required.

RING SYSTEM (for heavy oil with viscosity up to 65°E / 50°C)

1

 - Tank (properly heated for heavy oil)

5

 - Forwarding pump

2

 - Filter (with resistance for oil >7°E/50°C)

6

 - Manometer

3

 - Burner 

7

 - Burner pump

4

 - Couple of cocks (excluding the burner)

8

 - Pressure adjuster

Notice: All the pipes have to be properly seized, sealed and heated (elect. resistance or hot steam or water) to

let the fuel flow.

Warning: Before to put the burner in operation verify that no obstruction exists into the pipes, any obstruction may

damage the sealing of the pump.

H

meters

L meters

ø 1” 

gas

ø 1 1/4” 

gas

0

6

10

0.5

11

17

1

16

24

1.5

21

31

2

26

38

H

meters

L meters

ø 1 1/4” 

gas

ø 1 1/2” 

gas

0

22

45

0.5

19

39

1

16

33

1.5

13

27

2

10

21

2.5

7

15

3

0

8

Содержание 3434985

Страница 1: ...2915895 2 01 2009 Installation use and maintenance instructions Heavy oil burner CODE MODEL TYPE 3434985 PRESS 60 N 616 T80 3434986 PRESS 60 N 616 T80...

Страница 2: ......

Страница 3: ...ostat 17 Fair leads 14 Pre heater relay 18 Back pressure valve 15 Ignition transformer DIMENSIONS Thermal power Output 171 342 684 kW 15 30 60 kg h Operation Two stages Fuel Oil with max viscosity at...

Страница 4: ...ly one nozzle the pressurization conditions are improved and no problems arise Minimal fuel capacity with only one nozzle 15 kg h 171 kW Note for the extended combustion head version Apply the extensi...

Страница 5: ...the same level of the suction pipe In this case the foot valve is not required RING SYSTEM for heavy oil with viscosity up to 65 E 50 C 1 Tank properly heated for heavy oil 5 Forwarding pump 2 Filter...

Страница 6: ...gnition transformer TB Earth of the burner TE Start up and adjustment thermostat Tm Minimum value contact thermostat TM Maximum value contact thermostat V Electromagnetic valves Tm 1 2 4 6 95 96 A2 1...

Страница 7: ...for 380 V TWO STAGE OPERATION It can be achived by the thermostat connected to 14 15 wiring terminal board removing the bridge controlling 2nd valve PRE HEATER RESISTANCES CONNECTIONS D2644 220V 380V...

Страница 8: ...stat fair lead Pg 13 5 4 Control thermostat fair lead Pg 13 5 5 2nd stage thermostat fair lead Pg 13 5 6 Pre sheared holes Further prospective signals or controls can be connected to the burner wiring...

Страница 9: ...pump pressure or the nozzles match could be changed The pump is set by the factory at 20 bar Combustion head adjustment Turn the screw A till the set point detected from the diagram is on line with t...

Страница 10: ...he first flame it is adjustable both for opening and closing 2nd STAGE Red and black levers The red lever controls the air damper position for the second flame it is adjustable both for closing and op...

Страница 11: ...e resistances when in case of failure of the adjustment thermostat the temperature increases inside the pre heater In case of abnormal temperature make sure of the regular functioning of control therm...

Страница 12: ...y trouble at the burner operation Supply line filter positioned on the suction line it causes the increase of the depression in the pump with the consequent flow of gas and noise Do not overcome the d...

Страница 13: ...0V Lock out Extraneous light Key Off Yellow Green Red SIGNAL PROBABLE CAUSE 2 flashes The flame does not stabilise at the end of the safety time faulty photocell faulty or soiled oil valves neutral ph...

Страница 14: ......

Страница 15: ......

Страница 16: ...RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www rielloburners com Subject to modifications...

Отзывы: