5894
1
1
- Suction line
2
- Return line
3
-
Pump
pressure
adjustment screw
4
- Manometer plug (G 1/8)
5
- Vacuometer plug (G 3/8)
6
- Air shutter opening motor
7
- Control box reset push-button and lock-out lamp
8
- Reset push-button of the motor overload relay
9
- Regulating bush for combustion head
10
- Sheathed filter for the thermometer
11
- Valves group
12
- Manometer with protection valve
16
- Wiring terminal board
13
- Adjustment thermostat
17
- Fair leads
14
- Pre-heater relay
18
- Back-pressure valve
15
- Ignition transformer
DIMENSIONS
Thermal power - Output
114 / 205 - 513 kW - 10 / 18 - 45 kg/h
Operation
Two stages
Fuel
Oil with max. viscosity at 50 °C: 150 mm
2
/s (20 °E)
Electrical supply
Three phase 220V +10% -10% ~ 60Hz without neutral
380V +10% -10% ~ 60Hz with neutral
Motor
2.4 A / 220V - 1.5 A / 380V
Ignition transformer
Primary: 2 A - Secondary: 2x 6.5 kV / 35 mA
Heaters
2.8 kW
Absorbed electrical power
3.7 kW
Pump
65 Kg/h at 20 bar
Fig. 1
*
For extended - head version
Quantity
Accessories
2
Flexibles tubes
2
Nipples
2
Seals
4
Screws
1
Gasket for flange
2 *