End time of radiation start
The time after which a radiation start may no longer take place:
Real time: fixed point in time.
Sunrise: time before (-) or after sunrise.
Sunset: time before (-) or after sunset.
No start will be executed if 00:00:00 (real time) is set for the end time.
Minimum radiation level 0 - 2000 W/m²
The minimum radiation intensity (in W/m²) that must be reached for the radiation
sum counter to be increased.
Radiation sum level for radiation start 0 - 1000 J/cm²
The radiation sum (in J/cm²) above which a radiation start will be executed.
Reset radiation sum counter
The desired reset option for the radiation sum counter:
Rad.start: The radiation sum counter will only be reset when a radiation start is
executed.
Every start: The radiation sum counter will be reset after every start (when a
valve group is queued).
00:00:00: The radiation sum counter will be reset at midnight.
3.3.1.11
Frost prevention sprinkling
To enable the control for frost prevention sprinkling, enter the following setting:
Set 'Outside temperature measurement' (in system definition) to 'Yes'.
Frost prevention sprinkling
Start time
End time
Temperature for start
Temperature zone for stop
Sprinkling duration
Delay time for stop
Ignore main pause time
Path: Settings>Programs>Program name>Frost prevention sprinkling
Frost prevention sprinkling
Not active: Frost prevention sprinkling is disabled.
Active: Frost prevention sprinkling will start automatically when the outside
temperature drops too low. Frost prevention sprinkling can also be started manually.
Alarm: An alarm will be triggered when the outside temperature drops too low.
Aqua CX300
40