Problem 2
The LogicDrive RLD80 keeps starting and stopping on receiving a ‘fixed’ control
signal.
Observation 2
The RLD80 continuously moves back and forth in both directions in quick
succession.
Cause 1
The control signal from the climate controller is unstable.
Solution 1
Make sure the climate controller is sending a stable control signal; check the
connections.
Cause 2
The shield of the control cable has not been connected, making the 0-10 V DC
input susceptible to interference from external signal sources.
Solution 2
Connect the shield of the control cable in the control box.
Cause 3
The control cable is not shielded and, therefore, susceptible to interference from
external signal sources.
Solution 3
Replace the control cable with a shielded cable and connect the shield in the
control box.