ZONE CONTROLLER USER MANUAL
1.4.2 LED Indicators
The following indicators are visible on the front panel:
LED # Indicator
Status
Description
1
Power
Solid
Power status
2
Heartbeat
Flashing
Indication that the kernel is active
3
Status
Flashing
Zone Controller running
4
Comms Failure
Solid
Communication failure
5
Alarm
Solid
If any of the Digital Input data points
defined as having a type = alarm is
active
6
Override
Solid
If the Override status is ON (switch or
displays or BMS) at the BMS ZC front
panel, this input will be active.
3-6
Failure Status
Fast Flashing
Zone Controller failed
7
RS485-1
Flashing
RS485 Modbus comms activity
8
RS485-2
Flashing
RS485 ms/tp comms activity
In addition to the LED indicators on the front panel, there will also be indicators next to each of the
Ethernet (RJ45) connectors for Link and Activity.
1.4.3 Electromagnetic Compatibility (preliminary, to be confirmed)
Standard
Test Method
Description
Test Levels
EN 55024
EN 61000-4-2
Electrostatic Discharge
6 kV contact
EN 55024
EN 61000-4-3
Radiated Immunity
10 V/m, 80 MHz to 1 GHz
EN 55024
EN 61000-4-4
Fast Transient Burst
1 kV clamp & 2 kV direct
EN 55024
EN 61000-4-6
Conducted Immunity
10 V (rms)
EN 55022
CISPR 32
Radiated Emissions
Class A
EN 55022
CISPR 32
Conducted Emissions
Class B