6. Heater Manual Mode and Adjust (Ht) 

• The current re-heater output value is displayed as a % of maximum. 

• “Ht” indicates the unit is in Heater Manual mode. 

• Select the required output with the “UP” and “DOWN” buttons. 
Press “ENTER” to activate heater at the required level. 

• Pressing the “MENU” button deactives manual mode and moves to 
next feature. 

 

 

 

 

 

 

 

 

 

7. Control Zone Setup 

NOTE: Rickard recommends the MLM Application loaded on a PC 
to  zone  diffusers.  See  the  MLM  Commissioning  Guide  for  more 
information. 

a. 

Loop Select (LS) 

To bind a diffuser to a control zone the following steps is required: 

• The top left character display will indicate ‘LS’ for Loop Select. 

• Keep the enter button pressed until the unit beeps. 

• The menu will display ‘L and a zone number, ‘00’. If the zone has 
been  set  up  previously,  that  particular  zone number  will  display  in-
stead of ‘00’. 

• Press enter again and the zone number will flash. 

• Use the up/down arrow to select a zone number. A new installation 
should always start with zone ‘1’. 

•Press enter and observe the ‘L’ flashing. 

•  Go  to  the  first  diffuser  in  that  zone  and  press  the  button  on  the 
MLM Diffuser Controller board, this is normally situated on the trim 
disk. 

• After a few seconds the Setup Module will beep and the flashing 
LED  on  the  MLM  DC  board  will  stay  switched  on  momentarily  this 
indicates the diffuser is set up for that control zone. 

• Go to the next diffuser in that zone and press the button again and 
observe the same result. During this time the ‘L’ indicator will flash 
and the zone number will be on displayed. 

• Continue the process until all the diffusers in the control zone have 
been selected. 

•Press  the  enter  button  and  observe  the  ‘L’  steady  and  the  zone 
number flashing. 

• Using the up/down arrows, select the next zone number and con-

firm by pressing enter. 

• Using the same procedure, set each diffuser in the control zone. 

• A maximum of fifteen control zones (one diffuser per zone) can be 
set. A minimum of one zone with one to fifteen diffusers (slaves) can  
be set up. 

• Press enter again to exit the last zone that was set. 

• To advance to the next menu, press the menu button. 

 

 

 

 

 

 

 

 

 

 

 

 

b. Control Input Select (rS) 

The  next  function  is  to  select  the  setpoint,  control  and  supply  air 
temperatures for a particular control zone. As mentioned, to use this 
function  the  setup  module  must  be  connected  to  a  diffuser  in  the 
control zone of interest. In a default system with only one wall-stat 
or one analog module connected to a control zone this function will 
not be required.  

• The display will indicate ‘tS’ in the top left character display.  

•  The  character  display  will  indicate  the  current  status  of  the  three 
control inputs as follows:  

‘o’ - indicates ‘on-board’ for analog module. 

‘r’ - indicates ‘remote’ for wall-stat 

‘-‘ - indicates not selected 

• Press and hold the enter button until the unit beeps. The first char-
acter will flash with the display indicating ‘t’ for control temperature 
selection. 

•  Pressing  the  up/down  arrows  will  toggle  between  remote  or  on-
board  temperature  selections.  Be  sure  to  select  a  valid  option,  i.e. 
when selecting ‘remote’ there must be a wall-stat connected to that 
particular control zone. 

• Press enter and the character ‘S’ will show to indicate setpoint se-
lection. The up/down arrows will toggle this function. 

• Press enter to select the supply air input, character ‘C’. The arrow 
buttons will toggle between ‘o’, ‘r’ and ‘-‘ if supply air measurement 
is not required. 

•  On  pressing  enter  again  the  three  characters  will  flash  until  the 
system has accepted the new setup. 

• Press the menu button to exit this function. 

•To advance to the next menu, press the menu button. 

 