C. 137NP Non-Submersible Network Protectors
The non-submersible 137NP network protectors are generally similar to the submersible
except that non-submersible enclosures are provided. These protector units are for
applications in clear dry vaults. Equipment mounted enclosures (open framework) protectors
are also available.
As in the case of submersible protectors the non-submersible type may be arranged for wall
or framework mounting, or for bolting directly to the network transformers. Terminal
facilities may be arranged for connection of one to four cables per phase, or for bus bar
connections.
All protectors are arranged to permit the ready removal of the breaker unit without disturbing
the cable connections.
II. INSTALLATION
CAUTION: ALL NETWORK PROTECTORS MUST BE MOUNTED VERTICALLY.
It may be well for original users of this device to set one up temporarily in a service shop, so as
to become familiar with its characteristics and construction before installation on the system.
See section on
Opening Enclosures
.
A. Receiving, Handling and Storage
Care should be exercised when unpacking a protector so that no damage is caused in any
way, and a careful inspection made to see that no parts are damaged, missing or destroyed
with the packing material. Mounting hardware (transformer mounted protectors) is shipped
in separate cartons. Relays are shipped in separate cartons.
In handling or storing network protectors, always keep top up as marked on packaging.
Unsupported network protectors are unstable. Before removing shipping packaging, it is
recommended that a protector be supported from a sling or other suitable means to keep it
from falling over when the crating is removed.
Lift and handle the uncrated protector by the lifting eyes at the top of the case.
NOTE: Do not use the lifting eyes provided on the breaker unit for handling the complete
equipment mounted protector. These lifting eyes are provided for handling the breaker unit
only. Slings with spreaders are recommended to prevent damage to the upper terminals and
barriers of the protectors.
Transformer-mounted, top-connected, submersible and non-submersible protectors are
provided with permanent feet so that these protectors will rest upright on the floor.
Separately mounted submersible protectors are provided with temporary feet to protect the
Содержание 137NP
Страница 2: ......
Страница 5: ...iii Submersible Transformer Mounted ...
Страница 6: ...iv ...
Страница 14: ...6 Figure 2 Removable Unit Supported From Lifting Eyes ...
Страница 24: ...16 Figure 5 Removable Unit On Network Protector Stand ...
Страница 25: ...17 Figure 6 Contact 800 to 1875 Amp Units Figure 7 Contact 2000 to 3500 Amp Units ...
Страница 38: ...30 Figure 15 Trip Solenoid Figure 16 Buffer Assembly ...
Страница 46: ...38 ...
Страница 47: ...39 ...
Страница 48: ...40 ...
Страница 49: ...41 ...
Страница 50: ...42 ...
Страница 51: ...43 ...
Страница 52: ...44 ...
Страница 53: ...45 ...