4

520/820i/920i 

DeviceNet Installation and Programming Manual

2.2

DeviceNet Network Connections

Feed DeviceNet network cable through cord grip. 
Allow enough cable for routing along inside of 
enclosure to connector on the DeviceNet module. 
Connect network cables to connector on the DeviceNet 
module (see Figure 2-4), then use cable ties to secure 
network cables to the cable tie mounts.

Table 2-1shows the wiring color codes used for 
DeviceNet connections. 

Note

Verify the color-coding or wiring scheme for 
your network equipment before wiring to the 
DeviceNet Interface.

Table 2-1. DeviceNet Color Codes

Signal

Description

 Color Code 

V+

Positive supply

Red

CAN_H

CAN_H bus line

White

SHIELD

Cable shield

Bare

CAN_L

CAN_L bus line

Light blue

V–

Negative supply

Black

2.3

DIP Switch Configuration

A DIP switch is used to configure the DeviceNet 
network baud rate and node address. Figure 2-7 shows 
the DIP switch assignments.

Baud

Rate

Node Addre

ss

M

S

B

L

S

B

ON

1

2

8

5

3

4

6

7

Figure 2-7. DIP Switch Assignments

Baud Rate

Switches 1 and 2 set the baud rate of the DeviceNet 
network. Use Table 2-2 to select the correct switch 
settings for the network.

Table 2-2. Network Data Rate

DeviceNet

Data Rate

Switch Settings

1

2

125 Kbps

OFF

OFF

250 Kbps

OFF

ON

500 Kbps

ON

OFF

Reserved

ON

ON

Node Address (MAC ID)

Switches 3–8 set the node address (MAC ID) of the 
DeviceNet interface. Use Table 2-3 on page 5 to select 
the switch setting for the node address. 

Note

Setting a switch ON acts as a logical “1” and 
that SW1-3 represents the most significant bit 
(MSB) of the node address.

Содержание DeviceNet Series

Страница 1: ...69949 Rev A DeviceNet Interface for 520 720i 820i and 920i Indicators Installation and Programming Manual...

Страница 2: ......

Страница 3: ...Net Key Press toggle mode 9 Zero 9 Display Tare 9 Enter Tare integer 9 Acquire Tare simulate TARE key press 9 Clear Tare 9 Primary Units 9 Secondary Units 9 Tertiary Units 9 Units Key Press toggle uni...

Страница 4: ...eight as Float 12 Read Tare as Float 12 Read Piece Count as Float 12 Read Current Display as Float 12 Read Accumulator as Float 12 Read Rate of Change as Float 12 Read Peak Value as Float 12 Set Setpo...

Страница 5: ...w ricelake com 1 0 Introduction The DeviceNet Interface returns weight and status information from a 520 720i 820i or 920i indicator to a master controller and provides limited control of indicator fu...

Страница 6: ...or models with backplates place indicator face down on an antistatic work mat Remove screws that hold the backplate to the enclosure body Use a wrist strap to ground yourself and protect components fr...

Страница 7: ...rap to ground yourself and protect components from electrostatic discharge ESD when working inside the indicator enclosure 3 Carefully align the large option card connector with connector J2 on the CP...

Страница 8: ...SHIELD Cable shield Bare CAN_L CAN_L bus line Light blue V Negative supply Black 2 3 DIP Switch Configuration A DIP switch is used to configure the DeviceNet network baud rate and node address Figure...

Страница 9: ...FF OFF ON ON OFF OFF 44 54 ON OFF ON ON OFF OFF 13 15 OFF OFF ON ON OFF ON 45 55 ON OFF ON ON OFF ON 14 16 OFF OFF ON ON ON OFF 46 56 ON OFF ON ON ON OFF 15 17 OFF OFF ON ON ON ON 47 57 ON OFF ON ON O...

Страница 10: ...2 Network Status Off Not powered or not online Steady Red Critical link failure Flashing Red Connection time out Flashing Green Online not connected Steady Green Online connected LED 3 Module Status...

Страница 11: ...ation Decimal Hex Command 0 0x000 Return Status and Weight integer 1 0x001 Display Channel 2 0x002 Display Gross Weight 3 0x003 Display Net Weight 4 0x004 Display Count 9 0x009 Gross Net key press tog...

Страница 12: ...place of the low byte see Table 3 5 Setpoint commands return batch status in the low byte of the status word and the setpoint number in the high byte Table 3 4 Indicator Status Data Format Word 2 Bit...

Страница 13: ...current scale Display Tare Command 11 0x00B Parameter Scale number Command 11 causes the tare weight on the specified scale to be displayed If a scale number other than 0 is specified the indicator fi...

Страница 14: ...ter Scale number Command 33 returns the net weight value for the specified scale as an integer Return Tare as Integer Command 34 0x022 Parameter Scale number Command 34 returns the tare weight value f...

Страница 15: ...r Slot number Value Bit number Command 115 sets the specified digital output OFF inactive Use slot number 0 for onboard digital outputs Indicator status is returned with the current weight for the las...

Страница 16: ...scale in floating point format This command is only valid for the 820i or 920i Read Peak Value as Float Command 296 0x128 Parameter Scale number Command 296 returns the net peak value for the specifie...

Страница 17: ...e setpoint is enabled and requires a bandwidth value Read Setpoint Preact as Float Command 323 0x143 Parameter Setpoint number Command 323 returns the preact value for the specified setpoint in floati...

Страница 18: ...Current TRMS 28 9mA 920i Power TRMS 2 18 W Current TRMS 28 9 mA Communications Specifications DeviceNet Network Communications Twisted pair cabling at 125 250 or 500 Kbps Update rate is dependent on...

Страница 19: ...d was not caused by accident misuse neglect alteration improper installation improper repair or improper testing RLWS shall be the sole judge of all alleged non conformities Such equipment has not bee...

Страница 20: ...16 520 820i 920i DeviceNet Installation and Programming Manual...

Страница 21: ...Rice Lake Weighing Systems August 7 2013 PN 69949 Rev A...

Отзывы: