During Point C procedure, safety devices (photocells and safety strip),
stop button and encoder input are not active.
(#) In Point D and Point E procedures, all of them will be active, so they must
be properly installed and connected to the control board. Any changing of the
safety devices input state, will stop the Point D and Point E procedure that must
be repeated from the beginning.
POINT D
- PROGRAMMING (#)
1 - The gate must be fully closed.
2 - Turn
DIP2 to ON
position, LED DL1 starts blinking
3 -
Press PROG.Button
, motor opens.
4 - Once reached the open position, the open limit switch will cut out motor and
the gate travelling will be stored. The gap of time between now (stop of
motor) and the next pressing of the PROG.Button (see step 5 below) will be
then stored as waiting time for Automatic Closing feature.
5 -
Press PROG.Button
, gate closes and the Automatic Closing time is stored
(see DIP3 function to enable or disable the Automatic Closing feature).
6 - The LED DL1 will turn OFF, signalling exit from the Point D procedure.
Closing of the gate will be carried out at normal speed and only on
approaching total closing at low speed (depending on the adjustment of
LOW SPEED trimmer).
7 - When the gate leaf reaches the close limit switch plate, the motor stops.
8 -
Turn DIP2 to OFF
position.
IN CASE OF PLUS OPERATORS EQUIPPED WITH ENCODER, THE DIP7
MUST BE TURNED ON DURING THE PROGRAMMING PROCEDURES.
POINT E
- PROGRAMMING OF PEDESTRIAN OPENING (#)
1 - The gate must be fully closed.
2 - Turn
DIP2 to ON
position, the LED DL1 starts blinking quickly
3 - Immediately, turn also
DIP1 to ON
position, the LED DL1 starts blinking
slowly
4 - Press the pedestrian pushbutton
PED.Button
, the gate opens
5 - When the gate leaf is opened enough for the pedestrian crossing, press the
pedestrian pushbutton
PED.Button
to stop the travel (thus defining the
opening stroke of the motor). The gap of time between now (stop of the
motor) and the next pressing of the PROG.Button (see step 6 below) will be
stored as waiting time for Pedestrian Automatic Closing feature.
6 -
Press the pedestrian pushbutton PED.Button,
gate closes and the
Pedestrian Automatic Closing time is stored (see DIP3 function to enable or
disable the Automatic Closing feature).
7 - Turn
DIP1 to OFF
position
8 - Turn
DIP2 to OFF
position
F
UNCTIONING OF CONTROL ACCESSORIES
STEP BY STEP or AUTOMATIC commands (K BUTT, PED.Button)
DIP5 - ON
The K BUTT and PED.Button perform the step by step cyclic
command open-stop-close-open-stop-etc.
DIP5 - OFF
The K BUTT and PED.Button perform the automatic command:
- the open command, if pressed with the gate completely closed
- the close command, if pressed with the gate completely opened
- no effect, if pressed during the gate opening
- the gate re-open, if pressed while the gate is closing
The K BUTT opens the gate completely, whereas the PED.Button opens the
gate partially as described in Point E.
STEP BY STEP or AUTOMATIC commands (radio command)
DIP4 - ON
The RADIO COMMAND perform the step by step cyclic command
open-stop-close-open-stop-etc.
DIP4 - OFF
The RADIO COMMAND perform the automatic command:
- the open command, if pressed with the gate completely closed
- the close command, if pressed with the gate completely opened
- no effect, if pressed during the gate opening
- the gate re-open, if pressed while the gate is closing
CLOCK FUNCTION (OPEN input)
The Clock Function permits to keep the gate opened even if, for example, the
Automatic Closing is enabled (DIP3 ON) or somebody commands the gate
closing. It is useful during rush hours, when traffic is heavy and the flow is slow
(e.g. entrance/exit of employees, emergencies in residential areas or car parks
and, temporarily, for removal vans) and it’s necessary to keep the gate opened.
It can be done by connecting a switch and/or a daily/weekly clock either in
parallel to the OPEN button or instead of the OPEN button. When the control
board receives this command, the gate will open and by keeping this contact
closed for all the time of the gate opening, the Clock Function is automatically
activated. In fact, once reached the open position, the gate will remain opened
and all of the control board functions are blocked. Only when OPEN contact is
released, the control board functions are re-activated and the gate will close
immediately.
PEDESTRIAN command (PED.Button - COM)
This command is useful to open the gate partially, just enough, for example, to
permit a pedestrian crossing, see Point E procedure.
From the Pedestrian opening position the Automatic Closing can be enabled or
disabled with DIP3. From the Pedestrian opening position, the gate can be
completely opened by the OPEN or by the K BUTT button or by the RADIO
button.
AUTOMATIC CLOSING (from the COMPLETE open position)
The Automatic Closing from the complete open position can be enabled turning
ON the DIP3.
The maximum gap of time that can be programmed is 5 minutes (see Point D).
AUTOMATIC CLOSING (from the PEDESTRIAN open position)
The Automatic Closing from the pedestrian open position can be enabled
turning ON the DIP3. The maximum gap of time that can be programmed is 5
minutes (see Point E).
F
UNCTIONING OF SAFETY ACCESSORIES
PHOTOCELL (PHOT - COM)
In case the switch DIP6 is in the OFF position, the photocells are active both in
gate opening and in gate closing. In this configuration, if an obstacle cuts the
photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will stop and will restart opening when
the obstacle is removed
- while the gate is still, it will not move neither in opening nor in closing
In case of the switch DIP6 is in the ON position, the photocells are active only
in gate closing.
In this configuration, if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will continue open
- while the gate is still, it will open if a open command is request, it will
remain still if a close command is request.
The photocell input (PHOT - COM) is a NORMALLY CLOSED contact.
In case there are more couple of photocells, the contacts from all the photocell
receivers could be connected in series.
In case the photocells are not installed, this contact must be short circuited with
a wire jump (from PHOT to COM) to permit the gate to operate.
AUTOMATIC CLOSING after the transit through the photocell (DIP17 ON)
This option could be useful to close automatically the gate when the vehicle left
and disengaged the photocell beam. If the DIP17 is turned ON, this function is
activated and the PHOTO input will have two purposes:
- detect the obstacle and prevent the gate movement in according with the DIP6
position
- close the gate as soon as the vehicle leaves the photocell beam
If DIP17 ON and DIP6 OFF
If the gate is opening and a vehicle crosses the photo beam, the gate will
stop. When the vehicle leaves, the gate will close automatically after