RHINO PSL-24-BCM240 Скачать руководство пользователя страница 3

RHINO PSL-24-BCM240 Battery Control Module

Buffering Time

0.5 1

2

3

4

5

6

7

8

9

10

0

200

400

600

800

1,000

1,200

1,400

1,600

Bu

er

in

g T

im

(m

in

)

Output Current (A)

Bu

ering Time

3.3 AH

7.5 AH

12AH

Figure 8

Buffering Time (minutes)

Output Current

3.3 AH 7.5 AH

12AH

0.5 A

400

900

1400

1A

180

398

654

2A

70

165

323

4A

28

72

160

6A

19

55

103

8A

11

22

49

10A

7

18

37

Signal wiring diagram

Contact relay rating: 1A/30VDC. 
No polarity requirement.

DC

+

DC OK

1

2

Voc

Isc

+

BCM

Device

Discharging

3

4

Voc

Isc

BAT Fail

5

6

Voc

Isc

Battery

Figure 7

Signal wiring diagram

Status Indicators

BCM Status

Relay Output Connector

LED Display 

Status

Discharging BAT Fail DC OK

Battery Fully Charged

Open

Open

Closed

Green LED On

Battery Charging

Open

Open

Closed

Green LED 

Flashing

Battery Discharging* 

(Buffering Mode)

Closed*

Open

Closed

Orange LED 

Flashing

No Battery Connected

Open

Closed

Open

Red LED On

Output Shutdown

Open

Open

Open

No Light

* With output current 0.1 A to 10A.

Typical application notes

Figure 9

Battery

24V

+

+  

Power

Supply

L  N  PE

BCM

+  

  

  +  

  +

I/P   O/P   BAT

AC Input

Load 1

Unbuffered Load

+

PE

Load 2

Buffered Load

+

PE

Typical Application Notes

9.1 Provide backup power during AC source interruption or failure

9.2 Can be combined with redundancy module (PSB60-REM20S)

Battery

24V

+

+  

Power

Supply 2

L  N  PE

BCM

+  

  

  +  

  +

I/P   O/P   BAT

Load 1

Unbuffered Load

+

PE

Load 2

Buffered Load

+

PE

+  

Power

Supply 1

L  N  PE

AC Input

 

 

Redundancy 

Module

+  +  

+

OK

Out

Vin2

Vin1

Com

3

1st Edition, Rev. A 1/2019