CONNECTIONS – PLUMBING
CONNECTION SIZES
Model
15kW
35kW
Heat pump water heater inlet connection
R1¼ BSPM
R2 BSPM
Heat pump water heater outlet connection
R1¼ BSPM
R2 BSPM
Condensate drain connection
20mm O.D
All plumbing work must be carried out by a qualified person and in accordance
with the Plumbing Standard AS/NZS 3500.4 and local authority requirements.
WATER INLET AND OUTLET
The pipe work must be cleared of foreign matter before connection and purged
before attempting to operate the water heater. All olive compression fittings must
use brass or copper olives. Use thread sealing tape or approved thread sealant
on all screwed fittings.
An isolation valve and non-return
valve must be installed on the cold
water line to the water heater system.
An acceptable arrangement is shown
in the diagram. Refer also to
page 21
page 21
Disconnection unions are provided at
the cold side and hot side water inlets and outlets on the water heater to allow
for disconnection of the water heater. Use a spanner on the back nut when
tightening unions to prevent the pipe from rotating or twisting within the heat
pump.
PIPE SIZES
To achieve true mains pressure operation, the cold water line to the storage
tanks should be the same size or bigger than the hot water line from the storage
tanks.
The pipe sizing for hot water supply systems should be carried out by persons
competent to do so, choosing the most suitable pipe size for each individual
application. Reference to the technical specifications of the water heater and
local regulatory authority requirements must be made.
Refer to the table on
for correct primary flow and return pipe sizing.
Содержание W2W Series
Страница 24: ...INSTALLATION 24 Typical Installation with Recirculation ...
Страница 25: ...INSTALLATION 25 Typical Installation with Inline Auxiliary Boost ...
Страница 26: ...INSTALLATION 26 Typical Installation with Rheem Guardian Warm Water System ...
Страница 27: ...INSTALLATION 27 Dimensions and Technical Data RHEEM W2W Model 15kW 95401500 ...
Страница 28: ...INSTALLATION 28 Dimensions and Technical Data RHEEM W2W Model 35kW 95403500 ...
Страница 29: ...INSTALLATION 29 Dimensions and Technical Data RHEEM W2W Stackable Model 15kW 9540150S ...
Страница 30: ...INSTALLATION 30 Dimensions and Technical Data RHEEM W2W Stackable Model 35kW 9540350S ...
Страница 48: ...15KW HEAT PUMP INTERNAL WIRING DIAGRAM ...
Страница 49: ...CONNECTIONS ELECTRICAL 49 35KW HEAT PUMP INTERNAL WIRING DIAGRAM ...
Страница 50: ...CONNECTIONS ELECTRICAL 50 Controller and Display Information ...