INSTALLATION – SOLAR COLLECTOR
38
Pressure Testing
The solar water heater, including the collector circuit, is to be isolated during the testing and commissioning of
the heated water reticulation system in a building, in accordance with Clause 9.3 (a) of AS/NZS 3500.4:2015
and 2018 or Clause 3.34.2 (a) of AS/NZS 3500.5:2012 for a Class 1a or Class 10 building as applicable under
the Plumbing Code of Australia. The collector circuit includes the solar hot and solar cold pipes and solar
collectors.
It may be necessary to pressure test the collector circuit to comply with codes and regulatory authority
requirements or on other occasions where the solar collectors and solar hot and solar cold pipes are installed
prior to the solar storage tank, such as on a building site.
Collector Circuit
Warning:
The pressure applied to the collector circuit during a pressure test of a closed circuit system
MUST NOT
exceed 1000 kPa where a CSA2013 or LCS or NPT200 solar collectors is installed, otherwise
damage may result. The solar circuit and solar collectors are to be isolated from the solar storage tank for the
duration of the pressure test.
Closed Circuit System
If the solar collectors, solar pipe work and solar storage tank are installed and commissioned together, then
the flooding of the collector circuit with closed circuit fluid for a closed circuit system and checking the pipe
work for leaks during the commissioning procedure can be substituted for the pressure testing of the collector
circuit.