Rheem RXRZ-B01 Скачать руководство пользователя страница 2

H. Check all connections for refrigerant leaks and repair as

necessary.

II. ELECTRICAL CONNECTIONS

A. Route leads from low ambient control up through the

plastic bushing installed in the upper condenser bulkhead
to the area behind the control box. From this point route
the wires through the opening in the left side of the con-
trol box.

B. Disconnect black lead from fan motor at T1 on contactor.

(Refer to Figure 3.) Connect low ambient control lead with
flat terminal to T1 on contactor.

FIGURE 3. LOW AMBIENT CONTROL WIRING

CM 0406

WIRE TIES

WIRE FROM
COMPRESSOR

SEE DETAIL

SUCTION 
TUBE

LOW AMBIENT
PRESSURE
CONTROL
47-100571-02

LIQUID LINE

VALVE
ADAPTER
83-21457-02

WIRES FROM COMPRESSOR

WIRES FROM COMPRESSOR

WIRE TIES

COMPRESSOR

I513

VALVE ADAPTER
83-21457-02

SUCTION TUBE

SERVICE PORT

LIQUID LINE

FIGURE 2. LOW AMBIENT CONTROL INSTALLATION

DETAIL

C. Remove terminal from fan motor black lead and strip the

insulation back 1/2

from end of wire.

D. Connect the black lead from fan motor to the stripped

lead from control using wire nut provided.

E. Secure leads from control to a convenient wire bundle

using the wire tie provided in package.

F. Reinstall condenser fan assembly and control box cover.

G. Restore power to the unit and check unit operation.

III. UNIT CHECK

A. Restore power and check unit for proper operation.

B. Outdoor fan cycles off when liquid pressure drops below

250, ± 10 PSIG.

C. Outdoor fan cycles on when liquid pressure rises above

450, ± 10 PSIG.

This accessory is used when unit operation is required during
low ambient conditions. Installation of this control provides a
means of de-energizing the condenser fan motor. This permits
the suction (low side) to remain above the point which can
cause icing of evaporator (inside coil).

OFM

OFM

CC CONTACTOR
LAC LOW AMBIENT CONTROL
OFM OUTDOOR FAN MOTOR

LAC

LAC

Отзывы: