Humidification System 

 

19 

69-2307—01

The humidifier has internal system diagnostics that monitor system operation, maintenance sched-

ules, and faults. If a system fault is detected, the system will attempt to recover itself up to five 

times in a 24 hour period. If unable to recover in that time, the red Call Service LED light will acti

-

vate.
If the humidifier Call Service light is red, a system fault has occurred from which the humidifier 

can not recover by itself. The table below shows the possible faults, along with steps to fix the 

humidifier.

If the red Call Service LED light is on, press/release the RESET button. The red Call Service LED 

light will begin blinking in a series that indicates what fault occurred. Refer to the table below 

for the fault signified by the number of blinks that occur. To clear the fault, press and hold the 

RESET button for 5 seconds.
Press/hold the EMPTY button to clear the Service Timer light (i.e. the Press Empty button).
Press/release the EMPTY button to drain the tank.

No. of 

Red 

Light 

Blinks

Fault Description

Auto-

Recoverable?

Steps to Fix 

To be Performed by Professional HVAC Technician Only

1

Water/Heater temper-

ature sensor failed.

Yes, system will 

return to “Ready” 

if fault no longer 

exists in 1 hour.

•  Unplug the humidifier and remove cover.

•  Check water sensor connection to electronic board.

•  Reattach cover and plug the humidifier in.

•  If fault reappears, follow the cleaning steps on pages 23–25.

•  Reassemble tank and press the RESET button.

•  If fault returns, replace with applicable wattage heating 

element.

2

Water sensors failed.

Yes, system will 

return to “Ready” 

if fault no longer 

exists in 1 hour. 

Will attempt to 

reset itself 5 times 

in 24 hours. 

•  Unplug the humidifier and remove cover.

• 

 Disconnect water level sensor wiring, remove screen and 

lift snap-hinge clamp. 

 Remove water sensor assembly.

• Clean water sensor probes using warm soapy water so that 

the metal is exposed.

• Reassemble the sensor assembly in the unit, reattach and 

secure cover.

• Plug unit back in and press the RESET button.

• If fault reappears, replace sensor assembly.

3

Failure to fill tank 

with water.

Yes, system will 

return to “Ready” 

if fault no longer 

exists in 1 hour.

• Ensure inlet water is on.

• Check for leaks around the tank seal and solenoid.

• Turn off water supply and replace in-line water filter.

• Press/hold RESET button until the red Call Service light 

turns off.

• If tank still fails to fill, press the EMPTY button (if unit fails to 

drain, unplug unit and make sure water in tank is cool).

•  Follow tank cleaning instructions on page 23. Ensure you 

have a firm grip of the tank prior to releasing the tank, 

especially if water is present.

•  Clear any excess debris from the tank’s bottom orifice to the 

solenoid.

•  Reassemble tank and plug unit back in. Press the RESET 

button.

•  If water still fails to flush into the tank, replace the solenoid 

valve.

M24901

A

B

TRoubleshooTIng

dIP sWITCh seleCTIon

Содержание RXIH-AS06A

Страница 1: ...Steam Humidifier As Easy as 1 2 3 4 PROFESSIONAL INSTALLATION GUIDE See inside for detailed instruction and remote mounting options 1 Mount 2 Hang 3 Plumb 4 Wire 69 2307 01...

Страница 2: ...ud com or call 479 648 4900 Installation Recommendations 1 List of tools supplies 2 Safety Precautions 3 Duct Mount Instructions Installation 4 Remote Mount Instructions Installation 6 Plumbing and Wi...

Страница 3: ...and back flow prevention valve Check that the main water supply line is open Ensure there are no water leaks drips at any of the water connections Plug into a circuit with at least enough capacity to...

Страница 4: ...n the home depending on the amount of supplied ventilation If the remote hose is used there may be a slight rubber odor These odors will dissipate within days of installation If the homeowner sees the...

Страница 5: ...tic water line 1 2 in drain hose and clamps Mounting bracket and hardware In line water filter 50028044 001 Saddle valve Back flow valve 50030142 001 Options Remote Installation Kits 10 foot hose and...

Страница 6: ...humidifier s weight when it is full of water approximately 12 to 15 lbs and to hold the humidifier in a level position for safe reliable operation Otherwise additional duct or wall reinforcement will...

Страница 7: ...H AS09A 10 Amps RXIH AS12A 12 Amps M24745 Install duct nozzle 2 M24746 Ensure o ring gasket is properly seated in the groove M24894 Insert nozzle and twist clock wise to ensure tight seal of nozzle to...

Страница 8: ...eal in duct hole Secure bracket to duct using 8 self drilling sheet metal screws 4 M24749 5 6 Proceed to page 14 for plumbing and wiring instructions M24750 A B Foam gasket M24748 SUPPLY 12 INCHES 4 D...

Страница 9: ...pported to prevent sagging or low spots 1 Choose a location for the humidifier and the remote duct nozzle see remote installs on page 8 It should have access for Remote hose installation Steam hose mu...

Страница 10: ...ted in a conditioned space running a remote hose to the duct M24786 Living Area Remote Options M24781 Furnace or Mechanical Room Remote M24785 Garage Remote M24936 Duct Mount Remote Proper Hose Instal...

Страница 11: ...SLOPE TYPICAL INSTALLATION WHEN HUMIDIFIER IS ABOVE REMOTE NOZZLE KINKED SAG NO SLOPE NO SLOPE M29028 UNDRAINED ELBOW NOTES Minimum upward slope of hose in direction of steam flow at 2 in per foot Min...

Страница 12: ...Mount Kit sold separately Hose Adapter Duct Nozzle Hose Clamps Remote Hose M24894 Insert hose adapter and twist clockwise to ensure tight seal of nozzle to the humidifier Ensure o ring gasket is prope...

Страница 13: ...he humidifier will weigh 12 15 lbs 2 lbs with water so if mounting onto drywall or plaster position one side over a wall stud 3 4 Insert wall anchors 4 into pilot holes and secure bracket to location...

Страница 14: ...angle iron with the appropriate slope Then attach the hose to the top of this support If remote hose requires downward pitch refer to pages 7 and 9 for instruction M24771 Run remote hose from the hum...

Страница 15: ...01 Remote mount installation To install clamps onto the insulated steam hose Cut a slit in the insulation half way around the house Do not cut into the steam hose Insert the hose clamp into the slit a...

Страница 16: ...downslope To water supply Manual shutoff valve sold separately Draining water may be hot Ensure drain outlet not exposed Ensure drain or condensate pump is rated for at least 120 F water CAUTION Hot w...

Страница 17: ...y switched to call for fan GT GT connects to thermostat G terminal GF connects to fan board G terminal Thermostat G passes through the normally closed NC relay contacts to GF allowing fan activation W...

Страница 18: ...auto operation also wire W and G to thermostat W and G B HVAC DIGITAL HUMIDISTAT THERMOSTAT HUM HUM R C G Y W R Rc G Y W R C 24V 24V HUM HUM C GT R RT GF EXT RECOMMENDED AIR FLOW SWITCH AFS M29030 HV...

Страница 19: ...LL SERVICE PRESS RESET PRESS EMPTY RESET EMPTY SEE LABEL BELOW M24763 M24762 Confirm that the furnace blower turns on to circulate air This will take about 10 15 minutes upon call for humidity 16 Impo...

Страница 20: ...nd remains empty until next call for humidity 1 year of total time operational and inactive before the Press Empty light will blink indicating it is time to manually clean the water tank 30 hrs of hum...

Страница 21: ...ttach cover and plug the humidifier in If fault reappears follow the cleaning steps on pages 23 25 Reassemble tank and press the RESET button If fault returns replace with applicable wattage heating e...

Страница 22: ...w is present follow the cleaning steps on pages 23 25 Press EMPTY button to drain tank Set humidistat RH setpoint to Test mode If fault returns unplug the humidifier Loosen cover screw and remove cove...

Страница 23: ...IFYING light turning on Allow unit to run and check for steam leaks around tank and ventilation holes If steam is present replace the humidifier 13 Tank failed to drain No Water in tank may be hot 140...

Страница 24: ...e tank with water in it Flush cycle takes approximately 15 minutes to empty the tank completely To override press hold the EMPTY button while the Clean Tank light is blinking Drain Hose Operating Temp...

Страница 25: ...ight to be on solid not blinking The flush cycle takes approximately 15 minutes to empty the tank completely To override the flush cycle press hold the EMPTY button a second time for 3 seconds The tan...

Страница 26: ...ard to release the tank Note Latch does not come off humidifier with tank M24777 M24778 M24779 5 Use tap water to flush loose minerals from the tank Sediment screen at tank s bottom is removable For a...

Страница 27: ...til humidity is needed again This prevents water from stagnating within the tank The tank will refill with water upon next humidity call There are a few house cleaning steps to follow to keep your hum...

Страница 28: ...efer to installation instructions packaged with each model as well as complying with all Federal State Provincial and Local codes Part Part Number Fig Reference 10 foot Remote Hose and Nozzle Kit 5002...

Отзывы: