
AP18733 REV. 3.2.17
34
This appliance requires fresh, uncontaminated air for safe operation and must be installed in a mechanical room where there is adequate
combustion and ventilating air.
NOTE: To prevent combustion air contamination, see Table 9.
Follow the National Fuel Gas Code (ANSI
Z223.1 / NFPA 54).
Combustion air from the indoor space can be used if the space has adequate area or when air is provided through a duct or louver to supply
sufficient combustion air based on the appliance input. Never obstruct the supply of combustion air to the appliance. If the appliance is installed
in areas where indoor air is contaminated (see Figure 12) it is imperative that the appliance be installed as direct vent so that all combustion air
is taken directly from the outdoors into the appliance intake connection.
Unconfined space is space with volume greater than 50 cubic feet per 1,000 Btu/hour (4.8 cubic meters per kW) of the total input rating of
all fuel-burning appliances installed in that space. Rooms connected directly to this space, through openings not furnished with doors, are
considered part of the space.
Confined space is space with volume less than 50 cubic feet per 1,000 Btu/hour (4.8 cubic meters per kW) of the total input rating of all fuel-
burning appliances installed in that space. Rooms connected directly to this space, through openings not furnished with doors, are considered
part of the space.
When drawing combustion air from inside a conventionally constructed building to a confined space, such space should be provided with two
permanent openings: one located 6" (15 cm) below the space ceiling, the other 6" (15cm) above the space floor. Each opening should have a
free area of one square inch per 1,000 Btu/hr (22cm
2
/kW) of the total input of all appliances in the space, but not less than 100 square inches
(645).
If the confined space is within a building of tight construction, air for combustion must be obtained from the outdoors as outlined in the Venting
section of this manual. See Figure 13.
DO NOT PLACE
DRYER IN PROXIMITY
TO WATER HEATER
Figure 12 – LP-325-X
4. Power Venting, Indoor Combustion Air Installation in Confined or Unconfined Space
NOTE:
This water heater should be installed using direct venting in any instance where there are or may be flammable vapors in the area.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. To do so may result in an explosion
or fire.
Содержание RTGH-RH10DV
Страница 14: ...AP18733 REV 3 2 17 14 THE FOLLOWING ARE INSTALLATION INSTRUCTIONS FOR THE CONTRACTOR...
Страница 37: ...AP18733 REV 3 2 17 37 2 RECOMMENDED EXHAUST PIPE TRANSITIONS Figure 14 Recommended Exhaust Pipe Transitions...
Страница 52: ...AP18733 REV 3 2 17 52...
Страница 53: ...AP18733 REV 3 2 17 53...
Страница 82: ...AP18733 REV 3 2 17 82...
Страница 83: ...AP18733 REV 3 2 17 83...
Страница 85: ...AP18733 REV 3 2 17 85 MAINTENANCE NOTES...