12
SYSTEMS PERFORMANCE—RRKA- SERIES
GROSS SYSTEMS PERFORMANCE DATA—RRKA-A048
ENTERING INDOOR AIR @ 80°F [26.7°C]
wbE
71°F [21.7°C]
67°F [19.4°C]
63°F [17.2°C]
CFM [L/s]
1650 [779]
1500 [708]
1280 [604]
1650 [779]
1500 [708]
1280 [604]
1650 [779]
1500 [708]
1280 [604]
DR
➀
.22
.21
.19
.22
.21
.19
.22
.21
.19
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
57.0 [16.71]
29.5 [8.65]
4.2
56.1 [16.44]
27.9 [8.18]
4.1
54.8 [16.06]
25.5 [7.47]
4.1
54.5 [15.97]
35.2 [10.32]
4.1
53.6 [15.71]
33.6 [9.85]
4.1
52.3 [15.33]
31.2 [9.14]
4.0
51.4 [15.06]
40.4 [11.84]
4.0
50.5 [14.80]
38.8 [11.37]
4.0
49.2 [14.42]
36.4 [10.67]
3.9
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
55.7 [16.32]
31.7 [9.29]
4.4
54.8 [16.06]
30.1 [8.82]
4.3
53.5 [15.68]
27.7 [8.12]
4.3
53.2 [15.59]
37.5 [10.99]
4.3
52.3 [15.33]
35.9 [10.52]
4.2
51.0 [14.95]
33.5 [9.82]
4.2
50.1 [14.68]
42.7 [12.51]
4.2
49.2 [14.42]
41.1 [12.05]
4.2
47.9 [14.04]
38.7 [11.34]
4.1
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
54.4 [15.94]
32.2 [9.44]
4.5
53.5 [15.68]
30.6 [8.97]
4.5
52.2 [15.30]
28.2 [8.26]
4.4
51.9 [15.21]
38.0 [11.14]
4.5
51.0 [14.95]
36.4 [10.67]
4.4
49.7 [14.57]
34.0 [9.96]
4.4
48.8 [14.30]
43.2 [12.66]
4.4
47.9 [14.04]
41.6 [12.19]
4.4
46.6 [13.66]
39.2 [11.49]
4.3
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
53.2 [15.59]
31.5 [9.23]
4.7
52.3 [15.33]
29.9 [8.76]
4.7
51.0 [14.95]
27.5 [8.06]
4.6
50.6 [14.83]
37.3 [10.93]
4.7
49.7 [14.57]
35.7 [10.46]
4.6
48.4 [14.18]
33.3 [9.76]
4.6
47.5 [13.92]
42.5 [12.46]
4.6
46.7 [13.69]
40.9 [11.99]
4.5
45.3 [13.28]
38.5 [11.28]
4.5
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
51.8 [15.18]
30.1 [8.82]
4.9
50.9 [14.92]
28.5 [8.35]
4.9
49.6 [14.54]
26.1 [7.65]
4.8
49.3 [14.45]
35.8 [10.49]
4.8
48.4 [14.18]
34.3 [10.05]
4.8
47.1 [13.80]
31.9 [9.35]
4.7
46.2 [13.54]
41.0 [12.02]
4.8
45.3 [13.28]
39.4 [11.55]
4.7
44.0 [12.90]
37.0 [10.84]
4.7
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
50.4 [14.77]
28.3 [8.29]
5.1
49.5 [14.51]
26.7 [7.82]
5.1
48.2 [14.13]
24.3 [7.12]
5.0
47.9 [14.04]
34.1 [9.99]
5.0
47.0 [13.77]
32.5 [9.52]
5.0
45.7 [13.39]
30.1 [8.82]
4.9
44.8 [13.13]
39.2 [11.49]
5.0
43.9 [12.87]
37.6 [11.02]
4.9
42.6 [12.48]
35.2 [10.32]
4.9
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
48.8 [14.30]
26.7 [7.82]
5.3
48.0 [14.07]
25.1 [7.36]
5.2
46.6 [13.66]
22.7 [6.65]
5.2
46.3 [13.57]
32.4 [9.50]
5.2
45.4 [13.31]
30.9 [9.06]
5.2
44.1 [12.92]
28.5 [8.35]
5.1
43.2 [12.66]
37.6 [11.02]
5.1
42.3 [12.40]
36.0 [10.55]
5.1
41.0 [12.02]
33.6 [9.85]
5.0
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
47.1 [13.80]
25.7 [7.53]
5.5
46.2 [13.54]
24.1 [7.06]
5.4
44.9 [13.16]
21.7 [6.36]
5.4
44.5 [13.04]
31.5 [9.23]
5.4
43.6 [12.78]
29.9 [8.76]
5.4
42.3 [12.40]
27.5 [8.06]
5.3
41.5 [12.16]
36.6 [10.73]
5.3
40.6 [11.90]
35.0 [10.26]
5.3
39.3 [11.52]
32.6 [9.55]
5.2
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
45.1 [13.22]
25.8 [7.56]
5.7
44.2 [12.95]
24.2 [7.09]
5.6
42.9 [12.57]
21.8 [6.39]
5.6
42.5 [12.46]
31.6 [9.26]
5.6
41.6 [12.19]
30.0 [8.79]
5.5
40.3 [11.81]
27.6 [8.09]
5.5
39.5 [11.58]
36.7 [10.76]
5.5
38.6 [11.31]
35.1 [10.29]
5.5
37.3 [10.93]
32.7 [9.58]
5.4
GROSS SYSTEMS PERFORMANCE DATA—RRKA-A060
ENTERING INDOOR AIR @ 80°F [26.7°C]
wbE
71°F [21.7°C]
67°F [19.4°C]
63°F [17.2°C]
CFM [L/s]
2200 [1038]
2000 [944]
1700 [802]
2200 [1038]
2000 [944]
1700 [802]
2200 [1038]
2000 [944]
1700 [802]
DR
➀
.27
.26
.24
.27
.26
.24
.27
.26
.24
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
74.1 [21.72]
43.5 [12.75]
4.9
73.0 [21.39]
41.5 [12.16]
4.8
71.3 [20.90]
38.6 [11.31]
4.8
68.8 [20.16]
49.4 [14.48]
4.8
67.7 [19.84]
47.4 [13.89]
4.7
66.0 [19.34]
44.4 [13.01]
4.6
64.9 [19.02]
56.9 [16.68]
4.7
63.8 [18.70]
54.9 [16.09]
4.6
62.1 [18.20]
52.0 [15.24]
4.6
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
70.4 [20.63]
50.7 [14.86]
5.1
69.3 [20.31]
48.8 [14.30]
5.1
67.6 [19.81]
45.8 [13.42]
5.0
65.1 [19.08]
56.6 [16.59]
5.0
64.0 [18.76]
54.6 [16.00]
4.9
62.3 [18.26]
51.6 [15.12]
4.9
61.2 [17.94]
61.2 [17.94]
4.9
60.1 [17.61]
60.1 [17.61]
4.9
58.5 [17.14]
58.5 [17.14]
4.8
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
68.4 [20.05]
50.7 [14.86]
5.4
67.2 [19.69]
48.7 [14.27]
5.3
65.6 [19.23]
45.7 [13.39]
5.3
63.1 [18.49]
56.6 [16.59]
5.2
62.0 [18.17]
54.6 [16.00]
5.2
60.3 [17.67]
51.6 [15.12]
5.1
59.2 [17.35]
59.2 [17.35]
5.2
58.1 [17.03]
58.1 [17.03]
5.1
56.4 [16.53]
56.4 [16.53]
5.0
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
67.4 [19.75]
45.9 [13.45]
5.6
66.3 [19.43]
43.9 [12.87]
5.6
64.7 [18.96]
41.0 [12.02]
5.5
62.1 [18.20]
51.8 [15.18]
5.5
61.0 [17.88]
49.8 [14.59]
5.4
59.4 [17.41]
46.8 [13.72]
5.4
58.2 [17.06]
58.2 [17.06]
5.4
57.1 [16.73]
57.1 [16.73]
5.3
55.5 [16.27]
55.5 [16.27]
5.3
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
67.0 [19.64]
38.8 [11.37]
5.9
65.9 [19.31]
36.8 [10.79]
5.8
64.3 [18.84]
33.8 [9.91]
5.7
61.8 [18.11]
44.6 [13.07]
5.7
60.6 [17.76]
42.6 [12.48]
5.7
59.0 [17.29]
39.7 [11.63]
5.6
57.9 [16.97]
57.9 [16.97]
5.6
56.8 [16.65]
56.8 [16.65]
5.6
55.1 [16.15]
55.1 [16.15]
5.5
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
66.7 [19.55]
31.8 [9.32]
6.1
65.6 [19.23]
29.8 [8.73]
6.0
63.9 [18.73]
26.8 [7.85]
6.0
61.4 [17.99]
37.6 [11.02]
6.0
60.3 [17.67]
35.6 [10.43]
5.9
58.6 [17.17]
32.7 [9.58]
5.8
57.5 [16.85]
57.5 [16.85]
5.9
56.4 [16.53]
56.4 [16.53]
5.8
54.8 [16.06]
54.8 [16.06]
5.8
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
65.8 [19.28]
27.3 [8.00]
6.3
64.7 [18.96]
25.4 [7.44]
6.3
63.1 [18.49]
22.4 [6.56]
6.2
60.5 [17.73]
33.2 [9.73]
6.2
59.4 [17.41]
31.2 [9.14]
6.1
57.8 [16.94]
28.2 [8.26]
6.1
56.6 [16.59]
56.6 [16.59]
6.1
55.5 [16.27]
55.5 [16.27]
6.1
53.9 [15.80]
53.9 [15.80]
6.0
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
63.9 [18.73]
27.9 [8.18]
6.6
62.8 [18.40]
25.9 [7.59]
6.5
61.1 [17.91]
22.9 [6.71]
6.5
58.6 [17.17]
33.8 [9.91]
6.4
57.5 [16.85]
31.8 [9.32]
6.4
55.8 [16.35]
28.8 [8.44]
6.3
54.7 [16.03]
54.7 [16.03]
6.4
53.6 [15.71]
53.6 [15.71]
6.3
51.9 [15.21]
51.9 [15.21]
6.2
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
60.3 [17.67]
36.0 [10.55]
6.8
59.2 [17.35]
34.0 [9.96]
6.8
57.6 [16.88]
31.0 [9.09]
6.7
55.0 [16.12]
41.8 [12.25]
6.7
53.9 [15.80]
39.8 [11.66]
6.6
52.3 [15.33]
36.8 [10.79]
6.6
51.1 [14.98]
51.1 [14.98]
6.6
50.0 [14.65]
50.0 [14.65]
6.5
48.4 [14.18]
48.4 [14.18]
6.5
DR —Depression ratio
dbE —Entering air dry bulb
wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power—KW input
NOTES:
➀
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
[
] Designates Metric Conversions