Rheem RQMP 14 Series Скачать руководство пользователя страница 9

9

3. Unit is design certified for application on combustible flooring with 0" minimum

clearance.

4. See Figure 2 for illustration of minimum installation-service clearances.

D. ROOFTOP INSTALLATION

1. Before locating the unit on the roof, make sure that the strength of the roof and

beams is adequate at that point to support the weight involved. (See specification
sheet for weight of unit.) This is very important and user’s responsibility.

2. The unit should be placed on a solid and level platform of adequate strength.

IMPORTANT:

Avoid blocking openings in bottom of unit. (See Figure 3).

Provision for disposal of outdoor coil defrost water runoff must be provided.

3. The location of the unit on the roof should be such as to provide proper access for

inspection and servicing.

IMPORTANT:

If unit will not be put into service immediately, cover supply and return

openings to prevent excessive condensation.

VII. DUCTWORK

Ductwork should be fabricated by the installing contractor in accordance with local codes
and NFPA90A. Industry manuals may be used as a guide when sizing and designing the
duct system - contact Air Conditioning Contractors of America, 1513 16th St. N.W.,
Washington, D.C. 20036.

Place the unit as close to the space to be air conditioned as possible allowing clearance
dimensions as indicated. Run ducts as directly as possible to supply and return outlets.
Use of non-flammable waterproof flexible connectors on both supply and return connec-
tions at the unit to reduce noise transmission is recommended.

It is preferable to install the unit on the roof of the structure if the registers or diffusers
are located on the wall or in the ceiling. Consider a slab installation when the registers
are low on a wall or in the floor.

On ductwork exposed to outside air conditions of temperature and humidity, use a mini-
mum of 2" of insulation and a vapor barrier. Distribution system in attic, furred space or
crawl space should be insulated with at least 2" of insulation with vapor barrier. One-half
to 1" thickness of insulation is usually sufficient for ductwork inside the air conditioned
space.

Provide balancing dampers for each branch duct in the supply system. Properly support
the ductwork from the structure.

VIII.FILTERS

Filters are not provided with this unit. They must be supplied and installed in the return
air duct by the installer. A field installed filter grille is recommended for easy and conve-
nient access to the filters for periodic inspection and cleaning. Filters must have ade-
quate face area for the rated air quantity of the unit. See General Database for recom-
mended filter size.

IX. CONDENSATE DRAIN

The indoor coil condensate drain ends with a PVC stub. A trap is provided in for proper
condensate drainage and to prevent debris from being drawn into the unit. Do not con-
nect drain to closed sewer line. It is not recommended that a PVC cement or other per-
manent installation be used so that the drain line and/or drain pan can be easily cleaned
in the future. The drain trap is located in the control box during shipping. To install, slide
clear plastic tube over drain pan connection. The white PVC trap can be oriented as
required by installation.

!

WARNING

DO NOT, UNDER ANY CIRCUMSTANCES, CONNECT RETURN DUCTWORK TO
ANY OTHER HEAT PRODUCING DEVICE SUCH AS A FIREPLACE INSERT,
STOVE, ETC. UNAUTHORIZED USE OF SUCH DEVICES MAY RESULT IN FIRE,
CARBON MONOXIDE POISONING, EXPLOSION, PROPERTY DAMAGE,
SEVERE PERSONAL INJURY OR DEATH.

Содержание RQMP 14 Series

Страница 1: ...AREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICEMAN WARNING ANT SAFETY INFORMA THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED LICENSED SERVICE PERSONNEL FOR PROPER INSTALLAT...

Страница 2: ...eater Kit Instructions 10 C Control Wiring 11 D Internal Wiring 11 E Grounding 11 F Thermostat 12 XII Indoor Air Flow Data 12 XIII Pre Start Check 12 XIV Startup 12 XV Operation 13 XVI Auxiliary Heat...

Страница 3: ...H UNAUTHO RIZED COMPONENTS ACCESSORIES OR DEVICES WARNING DISCONNECT ALL POWER TO THE UNIT BEFORE STARTING MAINTE NANCE FAILURE TO DO SO CAN RESULT IN SEVERE ELECTRICAL SHOCK OR DEATH WARNING DO NOT U...

Страница 4: ...mixture of R 410A and nitrogen 2 Quick Reference Guide For R 410A R 410A refrigerant operates at approximately 60 higher pressure 1 6 times than R 22 Ensure that servicing equipment is designed to ope...

Страница 5: ...ACCESS 211 16 266 7 mm CONDENSATE DRAIN PAN ACCESS FRONT VIEW BOTTOM VIEW ELECTRICAL CONNECTIONS PRIMARY HIGH VOLTAGE ENTRANCE 123 32 43 7 mm 413 32 111 8 mm 59 64 130 5 mm 197 8 505 mm 57 8 149 5 mm...

Страница 6: ...NS 14 00 355 6 mm 14 00 355 6 mm 19 05 mm 3 4 14 00 355 6 mm 14 00 355 6 mm 19 05 mm 3 4 IMPORTANT DO NOT SCREW OR DRILL OUTSIDE THE DESIGNATED AREAS ROUND DUCT CONNECTIONS 14 355 6 mm 14 355 6 mm DO...

Страница 7: ...ld up on the unit 2 Regular cleaning and waxing of the cabinet with an automobile polish will provide some protection 3 A liquid cleaner may be used several times a year to remove matter that will not...

Страница 8: ...for conden sate drainage and possible refreezing of condensation Provide a base pad which is slightly pitched away from the structure Route condensate off base pad to an area which will not become sl...

Страница 9: ...e wall or in the ceiling Consider a slab installation when the registers are low on a wall or in the floor On ductwork exposed to outside air conditions of temperature and humidity use a mini mum of 2...

Страница 10: ...ch cover from control bulkhead and discard Retain screw 5 Remove heater element cover plate from blower outlet opening and discard Retain screws 6 Mount heater fuse block assembly in location indicate...

Страница 11: ...se 16 AWG thermostat wire The low voltage wires are connected to the unit pigtails which are supplied with the unit in the low voltage connection box located within the unit control box See Figure 5 3...

Страница 12: ...free to travel to and from outdoor coil See Figure 1 4 Is the wiring correct tight and according to unit wiring diagram 5 Is unit grounded 6 Are field supplied air filters in place and clean 7 Do the...

Страница 13: ...ped with start relay or start capacitor It is impor tant that such systems be off for a minimum of 5 minutes before restarting to allow equalization of pressures Do not move the thermostat to cycle un...

Страница 14: ...ature has reached the terminate temperature The terminate temperature is factory set at 70 F although the temperature can be changed to 50 F 60 F 70 F or 80 F by relocating a jumper on the board TEMPE...

Страница 15: ...eller Propeller Propeller Propeller No Used Diameter in mm 1 24 609 6 1 24 609 6 1 24 609 6 1 24 609 6 Drive Type No Speeds Direct 1 Direct 1 Direct 1 Direct 1 CFM L s 3200 1510 3200 1510 3200 1510 32...

Страница 16: ...Outdoor Fan Type Propeller Propeller Propeller Propeller No Used Diameter in mm 1 24 609 6 1 24 609 6 1 24 609 6 1 24 609 6 Drive Type No Speeds Direct 1 Direct 1 Direct 1 Direct 1 CFM L s 4200 1982...

Страница 17: ...6 Drive Type No Speeds Direct 1 Direct 1 CFM L s 4000 1888 4000 1888 No Motors HP 1 at 1 3 HP 1 at 1 3 HP Motor RPM 1075 1075 Indoor Fan Type FC Centrifugal FC Centrifugal No Used Diameter in mm 1 11x...

Страница 18: ...4 Outdoor Fan Type Propeller Propeller Propeller Propeller No Used Diameter in mm 1 24 609 6 1 24 609 6 1 24 609 6 1 24 609 6 Drive Type No Speeds Direct 1 Direct 1 Direct 1 Direct 1 CFM L s 3200 1510...

Страница 19: ...25 4 1 1 25 4 Outdoor Fan Type Propeller Propeller Propeller Propeller No Used Diameter in mm 1 24 609 6 1 24 609 6 1 24 609 6 1 24 609 6 Drive Type No Speeds Direct 1 Direct 1 Direct 1 Direct 1 CFM...

Страница 20: ...6 Drive Type No Speeds Direct 1 Direct 1 CFM L s 4000 1888 4000 1888 No Motors HP 1 at 1 3 HP 1 at 1 3 HP Motor RPM 1075 1075 Indoor Fan Type FC Centrifugal FC Centrifugal No Used Diameter in mm 1 11...

Страница 21: ...4 4 5 4 5 RPM 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 Amps RLA 13 5 13 5 14 1 14 1 10 4 10 4 16 7 16 7 14 1 14 1 21 8 21 8 13 7 13 7 21 8 21 8 17 9 17 9 26 4 26 4 Amps LRA 58 3 58 3 73 73 88...

Страница 22: ...RPM 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 Amps RLA 13 5 13 5 14 1 14 1 10 4 10 4 16 7 16 7 14 1 14 1 21 8 21 8 13 7 13 7 21 8 21 8 17 9 17 9 26 4 26 4 Amps LRA 58 3 58 3 73 73 88 88 79 79...

Страница 23: ...6 1335 1283 1231 1180 1128 1076 11x9 RPM 598 617 662 714 758 800 849 876 913 951 1 2 Watts 244 231 237 254 270 285 304 313 326 340 2 Speed CFM 1740 1695 1649 1604 1558 1513 1467 1422 1376 1331 X 13 Mo...

Страница 24: ...1101 1047 11x9 RPM 602 619 668 715 757 801 844 878 918 954 1 2 Watts 238 227 236 251 266 281 296 307 320 333 2 Speed CFM 1724 1678 1632 1586 1540 1495 1449 1403 1357 1311 X 13 Motor RPM 639 671 715 7...

Страница 25: ...7 946 972 999 1028 1049 1091 1108 Watts 826 806 784 762 734 702 658 626 546 512 CFM 1431 1394 1348 1302 1258 1208 1140 1030 849 557 11x9 Low RPM 540 579 633 686 724 776 831 868 1035 1076 3 5 Low 1225...

Страница 26: ...097 Watts 704 694 675 655 638 606 581 548 464 440 CFM 1279 1237 1196 1151 1098 1032 950 846 717 13 557 65 11x9 Low RPM 490 539 598 653 709 772 811 887 928 978 3 5 Low 1225 1575 1 2 Watts 401 400 393 3...

Страница 27: ...0 50 40 50 C05J 1 1 3 6 4 8 12 28 16 38 17 33 20 54 58 60 70 60 70 22 25 25 25 C07J 1 1 5 4 7 2 18 42 24 56 26 30 65 70 70 70 70 80 33 38 35 40 C10J 2 1 7 2 9 6 24 57 32 76 34 7 40 76 83 80 80 90 90 4...

Страница 28: ...80 80 90 90 50 58 50 60 No Heat 23 23 30 35 30 35 23 23 30 35 30 35 C10C 2 1 7 2 9 6 24 57 32 76 20 23 1 48 52 50 50 60 60 25 29 25 30 C15C 3 2 10 8 14 4 36 85 49 13 30 1 34 7 60 66 60 60 70 70 38 44...

Страница 29: ...45 50 45 50 C05J 1 1 3 6 4 8 12 28 16 38 17 33 20 47 61 60 70 70 70 22 25 25 25 C07J 1 1 5 4 7 2 18 42 24 56 26 30 68 73 70 80 80 80 33 38 35 40 C10J 2 1 7 2 9 6 24 57 32 76 34 7 40 79 86 80 90 90 90...

Страница 30: ...80 80 90 90 50 58 50 60 No Heat 26 26 30 35 30 35 26 26 30 35 30 35 C10C 2 1 7 2 9 6 24 57 32 76 20 23 1 51 54 60 60 60 60 25 29 25 30 C15C 3 2 10 8 14 4 36 85 49 13 30 1 34 7 63 69 70 70 70 70 38 44...

Страница 31: ...31 FIGURE 7 WIRING DIAGRAM RQNM SERIES...

Страница 32: ...32 FIGURE 8 WIRING DIAGRAM RQNM SERIES...

Страница 33: ...33 FIGURE 9 WIRING DIAGRAM RQPM SERIES...

Страница 34: ...34 FIGURE 10 WIRING DIAGRAM RQPM SERIES...

Страница 35: ...OUTDOOR AMBIENT F DB DISCHARGE PRESSURE PSIG INDOOR AMBIENT F DB 55 60 70 80 65 75 85 95 105 115 SUCTION PRESSURE PSIG 200 250 300 350 400 450 500 550 100 120 140 160 180 200 220 200 250 300 350 400 4...

Страница 36: ...OUTDOOR AMBIENT F DB DISCHARGE PRESSURE PSIG INDOOR AMBIENT F DB 55 65 75 85 95 105 115 SUCTION PRESSURE PSIG 60 70 80 200 250 300 350 400 450 500 550 100 120 140 160 180 200 220 SYSTEM CHARGE CHART C...

Страница 37: ...450 500 550 20 40 60 80 100 120 140 160 180 200 220 92 102273 03 01 3 0 TON HP R410A SUCTION PRESSURE PSIG DISCHARGE PRESSURE PSIG OUTDOOR AMBIENT F DB DISCHARGE PRESSURE PSIG INDOOR AMBIENT F DB 55...

Страница 38: ...F DB DISCHARGE PRESSURE PSIG INDOOR AMBIENT F DB 55 55 65 65 75 75 85 85 95 95 105 105 115 115 SUCTION PRESSURE PSIG 60 60 70 70 80 80 200 250 300 350 400 450 500 550 20 40 60 80 100 120 140 160 180 2...

Страница 39: ...OUTDOOR AMBIENT F DB DISCHARGE PRESSURE PSIG INDOOR AMBIENT F DB 55 65 75 85 95 105 115 SUCTION PRESSURE PSIG 60 70 80 200 250 300 350 400 450 500 550 100 120 140 160 180 200 220 200 250 300 350 400 4...

Страница 40: ...RE PSIG 60 70 80 2 20 00 0 2 25 50 0 3 30 00 0 3 35 50 0 4 40 00 0 4 45 50 0 5 50 00 0 5 55 50 0 1 10 00 0 1 12 20 0 1 14 40 0 1 16 60 0 1 18 80 0 2 20 00 0 2 22 20 0 2 20 00 0 2 25 50 0 3 30 00 0 3 3...

Отзывы: