Mechanical Specifications

RKNL-B Series

63

Guide Specifications RKNL-B073 - 151

Note about this specification: Copying this document directly into your building specification is permissible.

GAS HEAT PACKAGED ROOFTOP

HVAC Guide Specifications

Size Range: 6 to 12

1

/

2

Nominal Tons

Section

Description

23 06 80

Schedules for Decentralized HVAC Equipment

23 06 80.13

Decentralized Unitary HVAC Equipment Schedule

23 06 80.13.A. Rooftop unit schedule

1. Schedule is per the project specification requirements.

23 07 16

HVAC Equipment Insulation

23 07 16.13

Decentralized, Rooftop Units:

23 07 16.13.A. Evaporator fan compartment:

1.  Interior cabinet surfaces shall be insulated with a minimum 3/4-in. thick, minimum 1-1/2 lb density, flexible fiberglass insulation

bonded with foil face on the air side.

2. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.

3. Insulation shall also be mechanically fastened with welded pin and retainer washer.

23 07 16.13.B. Gas heat compartment:

1. Aluminum foil-faced fiberglass insulation shall be used.

2. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.

3. Insulation shall also be mechanically fastened with welded pin and retainer washer.

23 09 13

Instrumentation and Control Devices for HVAC

23 09 13.23

Sensors and Transmitters:

23 09 13.23.A. Thermostats

1.  Thermostat must

a. energize both “W” and “G” when calling for heat.

b. have capability to energize 2 different stages of cooling, and 2 different stages of heating.

c. must include capability for occupancy scheduling.

23 09 33

Electric and Electronic Control System for HVAC

23 09 33.13

Decentralized, Rooftop Units:

23 09 13.13.A. General:

1.  Shall be complete with self-contained low-voltage control circuit protected by a fuse on the 24-V transformer side (B073-B150

units have a resettable circuit breaker).

2. Shall utilize color-coded wiring.

3. Unit shall be include self-contained low-voltage control circuit protected by a fuse on the 24-V transformer side with a reset-

table circuit breaker.

4. The heat exchanger shall be controlled by an integrated furnace controller (IFC) microprocessor. See heat exchanger section

of this specification.

5. Unit shall include a minimum of one 8-pin screw terminal connection board for connection of control wiring.

23 09 33.23.B. Safeties:

1.  Compressor over-temperature, over current.

2. Low-pressure switch.

a. Units shall have low pressure, loss of charge automatic reset device that will shut off compressor when tripped.

3. High-pressure switch.

a. Unit shall be equipped with high pressure switch manual reset device that will shut off compressor when tripped.

4. Automatic reset, motor thermal overload protector.

5. Heating section shall be provided with the following minimum protections:

a. High-temperature limit switches.

b. Induced draft motor pressure switch.

c. Flame rollout switch.

d. Flame proving controls.

Содержание RKNL-B073CL15E

Страница 1: ...M NO R11 855 REV 1 Air Package Gas Electric RKNL B Series RKNL B Series Rheem Commercial Classic Series Package Gas Electric Unit Nominal Sizes 6 12 5 Tons 21 1 44 0 kW ASHRAE 90 1 2010 Compliant Mode...

Страница 2: ...9 Selection Procedure 10 General Data RKNL Series 11 23 General Data Notes 24 Gross Systems Performance Data RKNL Series 25 27 Indoor Airflow Performance RKNL Series 28 32 Electrical Data RKNL Series...

Страница 3: ...ce Powder Paint Finish meets ASTMB117 steel coated on each side for maximum protection G90 galvanized One piece top cover and one piece base pan with drawn supply and return opening for superior water...

Страница 4: ...d on the underside of the basepan removing areas that would allow for potential moisture accumula tion which can facilitate growth of harmful bacteria All insulation is secured with both adhesive and...

Страница 5: ...dentifies the com pressor circuit high pressure connec tion and low pressure connection With the gauge ports mounted exter nally an accurate diagnostic of system operation can be performed quickly and...

Страница 6: ...t seal and provides strain relief Care is also taken to tuck raw edges of insulation behind sheet metal to improve indoor air quality The furnace compartment contains the latest furnace technology on...

Страница 7: ...it is designed for both downflow or horizontal applications for job configura tion flexibility The return air compartment can also contain an economizer Two models exits one for downflow applications...

Страница 8: ...e M Belt Drive High Static N Belt Drive High Static B090 Only Electrical Designation C 208 230 V 3 PH 60 Hz D 460 V 3 PH 60 Hz Y 575 V 3 PH 60 Hz Cooling Capacity BTUH kW 073 72 000 21 10 090 90 000 2...

Страница 9: ...ion of options If no factory option s is required nothing follows the model number Step 1 After a basic rooftop model is selected choose a two character option code from the FACTORY INSTALLED OPTION S...

Страница 10: ...apply to data obtained in step 2 to obtain gross capacity Total Capacity 118 900 x 0 98 116 522 BTUH 34 12 kW Sensible Capacity 92 268 x 0 95 87 655 BTUH 25 67 kW Power Input 8 950 x 0 99 8 861 Watts...

Страница 11: ...d Louvered Louvered Tube Type Rifled Rifled Rifled Rifled Tube Size in mm OD 0 375 9 5 0 375 9 5 0 375 9 5 0 375 9 5 Face Area sq ft sq m 13 5 1 25 13 5 1 25 13 5 1 25 13 5 1 25 Rows FPI FPcm 1 22 9 1...

Страница 12: ...0 375 9 5 0 375 9 5 0 375 9 5 Face Area sq ft sq m 13 5 1 25 13 5 1 25 27 2 51 27 2 51 Rows FPI FPcm 1 22 9 1 22 9 1 22 9 1 22 9 Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Rifl...

Страница 13: ...27 2 51 27 2 51 Rows FPI FPcm 1 22 9 1 22 9 1 22 9 1 22 9 Net Latent Capacity Btu kW 26 900 7 88 26 900 7 88 26 900 7 88 26 900 7 88 Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type...

Страница 14: ...5 9 5 0 375 9 5 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 1 22 9 1 22 9 1 22 9 1 22 9 Net Latent Capacity Btu kW 26 900 7 88 26 900 7 88 26 900 7 88 26 900 7 88 Indoor Coil Fi...

Страница 15: ...5 9 5 0 375 9 5 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 1 22 9 1 22 9 1 22 9 1 22 9 Net Latent Capacity Btu kW 26 900 7 88 26 900 7 88 26 900 7 88 26 900 7 88 Indoor Coil Fi...

Страница 16: ...375 9 5 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 1 22 9 2 18 7 2 18 7 2 18 7 Net Latent Capacity Btu kW 26 900 7 88 23 000 6 74 23 000 6 74 23 000 6 74 Indoor Coil Fin Type L...

Страница 17: ...375 9 5 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 2 18 7 2 18 7 2 18 7 2 18 7 Net Latent Capacity Btu kW 23 000 6 74 23 000 6 74 23 000 6 74 23 000 6 74 Indoor Coil Fin Type L...

Страница 18: ...375 9 5 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 2 18 7 2 18 7 2 18 7 2 22 9 Net Latent Capacity Btu kW 23 000 6 74 23 000 6 74 23 000 6 74 29 200 8 56 Indoor Coil Fin Type L...

Страница 19: ...5 0 375 9 5 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 2 22 9 2 22 9 2 22 9 2 22 9 Net Latent Capacity Btu kW 29 200 8 56 29 200 8 56 29 200 8 56 29 200 8 56 Indoor Coil Fin Ty...

Страница 20: ...9 5 0 375 9 5 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 2 22 9 2 22 9 2 22 9 2 22 9 Net Latent Capacity Btu kW 29 200 8 56 29 200 8 56 29 200 8 56 29 200 8 56 Indoor Coil Fin...

Страница 21: ...oChannel MicroChannel Tube Size in mm OD 0 375 9 5 1 25 4 1 25 4 1 25 4 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 2 22 9 2 23 9 2 23 9 2 23 9 Indoor Coil Fin Type Louvered Lou...

Страница 22: ...1 25 4 1 25 4 1 25 4 1 25 4 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 2 23 9 2 23 9 2 23 9 2 23 9 Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Rifled Rif...

Страница 23: ...nnel Tube Size in mm OD 1 25 4 1 25 4 1 25 4 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 2 23 9 2 23 9 2 23 9 Indoor Coil Fin Type Louvered Louvered Louvered Tube Type Rifled Rifled Rif...

Страница 24: ...tion program which is based on AHRI Standard 340 360 2 EER and or SEER are rated at AHRI conditions and in accordance with DOE test procedures 3 IEER is rated in accordance with AHRI Standard 340 360...

Страница 25: ...capacity x 1000 BTUH Sens Sensible capacity x 1000 BTUH Power KW input NOTES When the entering air dry bulb is other than 80 F 27 C adjust the sensible capacity from the table by adding 1 10 x CFM x...

Страница 26: ...l capacity x 1000 BTUH Sens Sensible capacity x 1000 BTUH Power KW input NOTES When the entering air dry bulb is other than 80 F 27 C adjust the sensible capacity from the table by adding 1 10 x CFM x...

Страница 27: ...kW Sens BTUH kW Power 155 9 45 7 91 7 26 9 11 9 150 4 44 1 83 9 24 6 11 7 144 9 42 5 76 22 3 11 5 146 2 42 8 112 9 33 1 11 7 141 41 3 103 3 30 3 11 5 135 9 39 8 93 6 27 4 11 3 138 2 40 5 130 5 38 2 11...

Страница 28: ...1 4 35 1 5 37 External Static Pressure Inches of Water kPa Voltage 208 230 460 575 3 phase Drive Package L M Motor H P W 1 5 1118 6 1 5 1118 6 Blower Sheave AK66 AK66 Motor Sheave 1VP 44 1VP 50 Turns...

Страница 29: ...928 1880 957 1965 987 2051 1016 2136 1045 2222 2414 1075 2307 3300 1557 592 954 628 1096 660 1168 692 731 789 1431 818 1493 848 1555 877 1617 906 1859 935 1944 965 2029 994 2115 1023 2200 1053 Capacit...

Страница 30: ...100 1935 726 1692 754 1766 781 1841 809 1915 836 1990 864 2064 922 2091 942 2204 963 2318 983 2431 1003 2545 1024 2658 1056 2772 1084 2885 1084 2999 1105 3112 1144 3226 Air Flow CFM L s 1148 2606 RPM...

Страница 31: ...1 1021 3025 1041 3138 1061 3252 1124 3365 1151 3479 1122 3592 952 2585 973 2679 993 2793 1013 2906 1033 3020 1054 3133 1110 3247 1138 3360 1115 3474 1127 3468 1135 3587 4800 2265 821 2271 848 2345 876...

Страница 32: ...3 0 1 02 0 2 05 0 3 07 0 4 10 0 5 12 0 6 15 0 7 17 0 8 20 0 9 22 1 0 25 1 1 27 1 2 30 1 3 32 1 4 35 1 5 37 1 6 40 1 7 42 1 8 45 1 9 47 2 0 50 External Static Pressure Inches of Water kPa Voltage 208 2...

Страница 33: ...450 3450 3450 3450 3450 3450 3450 3450 3450 3450 HP Compressor 1 6 6 5 6 5 6 3 1 4 3 1 4 3 1 4 3 1 4 3 1 4 Amps RLA Comp 1 19 6 19 6 19 6 19 6 8 2 8 2 6 6 6 6 13 1 13 1 13 1 13 1 13 1 13 1 6 1 6 1 Amp...

Страница 34: ...1 4 3450 3 600 2 20 20 575 518 632 38 1 7 3 8 8 2 3 208 230 1 4 7 4 7 1 2 1 2 1 3 1 208 230 2 16 16 91 91 3 3 4 3450 3 200 230 2 60 60 50 50 208 230 187 253 3 460 1 4 2 3 460 1 2 4 0 7 1 3 1 460 2 7 1...

Страница 35: ...1 3 1 460 2 9 8 52 4 1 4 3450 3 480 2 30 25 460 414 506 82 6 82 6 18 8 18 8 5 4 2 3 575 1 1 5 0 5 1 3 1 575 2 5 7 38 9 4 1 4 3450 3 575 2 20 20 575 518 632 3 208 230 1 15 15 3 3 208 230 1 5 6 5 6 1 15...

Страница 36: ...5 3 4 Amps LRA Comp 1 54 Amps RLA Comp 2 Unit Information Unit Operating Voltage Range 7 4 518 632 Condenser Motor No 2 Volts 575 Phase 1 HP 1 2 Amps FLA each 0 5 Amps LRA each 2 2 Evaporator Fan No...

Страница 37: ...Air Dimensional Data RKNL B Series 37 Designates Metric Conversions BOTTOM VIEW Illustration ST A0715 03 X1...

Страница 38: ...38 SUPPLY AND RETURN DIMENSIONS FOR DOWNFLOW APPLICATIONS SUPPLY AND RETURN DIMENSIONS FOR HORIZONTAL APPLICATIONS RECOMMENDED DUCT DIMENSIONS ARE 26 Designates Metric Conversions Illustration ST A07...

Страница 39: ...Air Dimensional Data RKNL B Series 39 Designates Metric Conversions...

Страница 40: ...5 38 60 38 17 24 Roof Curb 24 140 63 50 135 61 23 A B C D 33 27 17 23 Capacity Tons kW 6 12 5 21 1 44 0 Corner Weights by Percentage CLEARANCES The following minimum clearances must be observed for pr...

Страница 41: ...low Transition Rect to Rect 18 x 28 RXMC CE05 18 8 2 16 7 3 No Compressor Time Delay Relay Kit RXMD A04 2 1 0 1 5 No Low Ambient Control Kit 1 Per Compressor RXRZ C02 3 1 4 2 1 0 Yes Freeze Stat Kit R...

Страница 42: ...esentative Actual models may vary For detailed thermostat match up information see specification sheet form number T11 001 300 Series Deluxe Programmable 400 Series Special Applications Programmable 5...

Страница 43: ...lable CO2 Input Sensor Available Field Assembled Hood Ships with Economizer Economizer Ships Complete for Downflow Duct Application Optional Remote Minimum Position Potentiometer Honeywell S963B1128 i...

Страница 44: ...Low Leakage Dampers Slip In Design for Easy Installation Plug In Polarized 12 pin Electrical Connections Pre Configured No Field Adjustments Necessary Standard Barometric Relief Damper Single Enthalpy...

Страница 45: ...of Fans Volts Phase HP ea Low Speed RXRX BFF02C 2 208 230 1 0 33 2200 1038 1518 2500 1179 High Speed 1670 1 48 FLA ea 3 6 LRA ea RXRX BFF02D 2 460 1 0 33 2200 1038 1518 2500 1179 1670 0 75 1 8 RXRX BF...

Страница 46: ...Series 46 FRESH AIR DAMPER MOTORIZED DAMPER KIT RXRX AW02 Motor Kit for AXRF KDA1 Illustration ST A0886 38 7951 17a AXRF KDA1 Manual DOWNFLOW OR HORIZONTAL APPLICATION Illustration ST 7951 17 Designa...

Страница 47: ...ssories RKNL B Series 47 FRESH AIR DAMPER Cont AXRF JDA1 Manual AXRF JDB1 Motorized Illustration ADS 7937 58 Illustration ST A0901 01 HORIZONTAL APPLICATION DOWNFLOW APPLICATION Designates Metric Conv...

Страница 48: ...ttom pan to match the Thru the Curb electrical connection opening provided on the unit base pan 1 25 mm x 4 102 mm Nailer provided Insulating panels not required because of insulated outdoor base pan...

Страница 49: ...RXRK E50 RXRX CDCE50 RGF 200075 RGG REG RCG 075 RGF REF RCF 085 RGF REF RCF 100 RGG REG RCG 100 RXRK E54 RXRX CFCE54 RGF REF RCF 125 RXRK E56 RXRX CFCE56 NOTE Ductwork modifications may be necessary i...

Страница 50: ...Air Accessories RKNL B Series 50 ROOFCURB ADAPTERS Cont RXRX CDCE50 Illustration ADS 7952 02 Sheet 2 Illustration ADS 7952 02 Sheet 1 Designates Metric Conversions TOP VIEW...

Страница 51: ...Air Accessories RKNL B Series 51 ROOFCURB ADAPTERS Cont RXRX CFCE54 Illustration ADS 7952 01 Sheet 1 Illustration ADS 7952 01 Sheet 2 Designates Metric Conversions TOP VIEW...

Страница 52: ...Air Accessories RKNL B Series 52 ROOFCURB ADAPTERS Cont RXRX CFCE56 Illustration ADS 7952 03 Sheet 2 Illustration ADS 7952 03 Sheet 1 Designates Metric Conversions TOP VIEW...

Страница 53: ...Air Accessories RKNL B Series 53 ROOFCURB ADAPTERS Cont RXRX CGCC12 Illustration ADS 7952 04 Sheet 1 Illustration ADS 7952 04 Sheet 2 Designates Metric Conversions TOP VIEW...

Страница 54: ...L B Series 54 Illustration ST A0881 02 Designates Metric Conversions CONCENTRIC DIFFUSER APPLICATION Illustration ST A0840 02 DOWNFLOW TRANSITION DRAWINGS RXMC CE05 Used with RXRN AA61 or RXRN AA71 Co...

Страница 55: ...Air Accessories RKNL B Series 55 Designates Metric Conversions Illustration ST A0881 03 DOWNFLOW TRANSITION DRAWINGS RXMC CF06 Used with RXRN AA66 or RXRN AA76 Concentric Diffusers...

Страница 56: ...Air Accessories RKNL B Series 56 DOWNFLOW TRANSITION DRAWINGS RXMC CD04 Used with RXRN FA65 or RXRN FA75 Concentric Diffusers 795103 Illustration ADS 7951 03 Designates Metric Conversions...

Страница 57: ...Terminal Velocities using isothermal air Throw is based on diffuser blades being directed in a straight pattern Actual noise levels may vary due to duct design and do not include transmitted unit noi...

Страница 58: ...Pa Throw Feet m Neck Velocity fpm m s Noise Level dbA RXRN AA61 3600 1699 0 17 0 042 25 33 7 6 10 1 851 4 3 30 3800 1793 0 18 0 045 27 35 8 2 10 7 898 4 6 30 4000 1888 0 21 0 052 29 37 8 8 11 3 946 4...

Страница 59: ...Pa Throw Feet m Neck Velocity fpm m s Noise Level dbA RXRN AA66 4600 2171 0 31 0 077 26 31 7 9 9 4 841 4 3 30 4800 2265 0 32 0 080 27 32 8 2 9 8 878 4 5 30 5000 2359 0 34 0 085 28 33 8 5 10 1 915 4 6...

Страница 60: ...fusion council guidelines Throw data is based on 75 FPM Terminal Velocities using isothermal air Throw is based on diffuser blades being directed in a straight pattern Actual noise levels may vary due...

Страница 61: ...bA RXRN AA71 3600 1699 0 17 0 042 22 29 6 7 8 8 844 4 3 35 3800 1793 0 18 0 045 22 30 6 7 9 1 891 4 5 40 4000 1888 0 21 0 052 24 33 7 3 10 1 938 4 8 40 4200 1982 0 24 0 060 26 35 7 9 10 7 985 5 0 40 4...

Страница 62: ...ased on diffuser blades being directed in a straight pattern Actual noise levels may vary due to duct design and do not include transmitted unit noise Adequate duct attenuation must be provided to red...

Страница 63: ...13 23 A Thermostats 1 Thermostat must a energize both W and G when calling for heat b have capability to energize 2 different stages of cooling and 2 different stages of heating c must include capabi...

Страница 64: ...adhesive shall meet NFPA 90A requirements for flame spread and smoke generation 7 Unit casing shall be capable of withstanding 1000 hour salt spray exposure per ASTM B117 scribed specimen 8 Unit casin...

Страница 65: ...ing to unit gas valve shall enter the unit cabinet at a single location on side of unit horizontal plane b Thru the base capability i Standard unit shall have a thru the base gas line location using a...

Страница 66: ...l be aluminum lanced plate fins mechanically bonded to seamless internally grooved copper tubes with all joints brazed Note 12 1 2 ton utilizes MicroChannel condensing coil b Evaporator and condenser...

Страница 67: ...ls to provide free cooling with outdoor air when temperature and or humidity are below setpoints e Shall be equipped with gear driven dampers for both the outdoor ventilation air and the return air fo...

Страница 68: ...ed k Outlet shall be field installed and internally mounted with easily accessible 115 v female receptacle l Outlet shall include 15 amp GFI receptacle with independent fuse protection m Outlet shall...

Страница 69: ...fire alarm control panel ii Two Form C auxiliary alarm relays for interface with rooftop unit or other equipment iii One Form C supervision trouble relay to control the operation of the Trouble LED o...

Страница 70: ...Air Wiring Diagrams RKNL B Series 70...

Страница 71: ...Air Wiring Diagrams RKNL B Series 71...

Страница 72: ...Air Wiring Diagrams RKNL B Series 72...

Страница 73: ...Air Wiring Diagrams RKNL B Series 73...

Страница 74: ...Air Wiring Diagrams RKNL B Series 74...

Страница 75: ...Air Wiring Diagrams RKNL B Series 75...

Страница 76: ...Air Wiring Diagrams RKNL B Series 76...

Страница 77: ...Air Wiring Diagrams RKNL B Series 77...

Страница 78: ...rranties including applicable terms and conditions contact your local contractor or the Manufacturer for a copy of the product warranty certificate Compressor 3 Phase Commercial Applications Five 5 Ye...

Страница 79: ...Air Notes RKNL B Series 79...

Страница 80: ...em com In keeping with its policy of continuous progress and product improvement Rheem reserves the right to make changes without notice PRINTED IN U S A 10 12 QG FORM NO R11 855 REV 1 Rheem Canada Lt...

Отзывы: