GENERAL DATA - RKNL MODELS
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Model RKNL- Series
A048CM13E
A048DK08E
A048DK10E
A048DK13E
Cooling Performance
1
Continued ->
Gross Cooling Capacity Btu [kW]
50,000 [14.65]
50,000 [14.65]
50,000 [14.65]
50,000 [14.65]
EER/SEER
2
11.45/13
11.45/13
11.45/13
11.45/13
Nominal CFM/ARI Rated CFM [L/s]
1600/1600 [755/755]
1600/1600 [755/755]
1600/1600 [755/755]
1600/1600 [755/755]
ARI Net Cooling Capacity Btu [kW]
48,000 [14.06]
48,000 [14.06]
48,000 [14.06]
48,000 [14.06]
Net Sensible Capacity Btu [kW]
35,600 [10.43]
35,600 [10.43]
35,600 [10.43]
35,600 [10.43]
Net Latent Capacity Btu [kW]
12,400 [3.63]
12,400 [3.63]
12,400 [3.63]
12,400 [3.63]
Net System Power kW
4.19
4.19
4.19
4.19
Heating Performance (Gas)
Heating Input Btu [kW]
135,000 [39.56]
80,000 [23.44]
100,000 [29.3]
135,000 [39.56]
Heating Output Btu [kW]
109,400 [32.05]
64,800 [18.99]
81,000 [23.73]
109,400 [32.05]
Temperature Rise Range ºF [ºC]
50-80 [27.8/44.4]
30-60 [16.7/33.3]
30-60 [16.7/33.3]
50-80 [27.8/44.4]
80
80
80
80
Steady State Efficiency (%)
81
81
81
81
No. Burners
6
4
5
6
No. Stages
1
1
1
1
Gas Connection Pipe Size in. [mm]
0.5 [12.7]
0.5 [12.7]
0.5 [12.7]
0.5 [12.7]
Compressor
No./Type
1/Copeland Scroll
1/Copeland Scroll
1/Copeland Scroll
1/Copeland Scroll
Outdoor Sound Rating (dB)
78
78
78
78
Outdoor Coil - Fin Type
Louvered
Louvered
Louvered
Louvered
Tube Type
Rifled
Rifled
Rifled
Rifled
Tube Size in. [mm] OD
0.375 [9.5]
0.375 [9.5]
0.375 [9.5]
0.375 [9.5]
Face Area sq. ft. [sq. m]
16.56 [1.54]
16.56 [1.54]
16.56 [1.54]
16.56 [1.54]
Rows / FPI [FPcm]
2 / 22 [9]
2 / 22 [9]
2 / 22 [9]
2 / 22 [9]
Indoor Coil - Fin Type
Corrugated
Corrugated
Corrugated
Corrugated
Tube Type
Rifled
Rifled
Rifled
Rifled
Tube Size in. [mm]
0.375 [9.5]
0.375 [9.5]
0.375 [9.5]
0.375 [9.5]
Face Area sq. ft. [sq. m]
5.17 [0.48]
5.17 [0.48]
5.17 [0.48]
5.17 [0.48]
Rows / FPI [FPcm]
3 / 15 [6]
3 / 15 [6]
3 / 15 [6]
3 / 15 [6]
Refrigerant Control
TX Valves
TX Valves
TX Valves
TX Valves
Drain Connection No./Size in. [mm]
1/0.75 [19.05]
1/0.75 [19.05]
1/0.75 [19.05]
1/0.75 [19.05]
Outdoor Fan - Type
Propeller
Propeller
Propeller
Propeller
No. Used/Diameter in. [mm]
1/24 [609.6]
1/24 [609.6]
1/24 [609.6]
1/24 [609.6]
Drive Type/No. Speeds
Direct/1
Direct/1
Direct/1
Direct/1
CFM [L/s]
3680 [1737]
3680 [1737]
3680 [1737]
3680 [1737]
No. Motors/HP
1 at 1/3 HP
1 at 1/3 HP
1 at 1/3 HP
1 at 1/3 HP
Motor RPM
1075
1075
1075
1075
Indoor Fan - Type
FC Centrifugal
FC Centrifugal
FC Centrifugal
FC Centrifugal
No. Used/Diameter in. [mm]
1/10x10 [254x254]
1/10x10 [254x254]
1/10x10 [254x254]
1/10x10 [254x254]
Drive Type/No. Speeds
Belt/Variable
Direct/3
Direct/3
Direct/3
No. Motors
1
1
1
1
Motor HP
3/4
1/2
1/2
1/2
Motor RPM
1725
1075
1075
1075
Motor Frame Size
56
48
48
48
Filter - Type
Disposable
Disposable
Disposable
Disposable
Furnished
Yes
Yes
Yes
Yes
(NO.) Size Recommended in. [mm x mm x mm]
(1)1x16x25 [25x406x635]
(1)1x16x25 [25x406x635]
(1)1x16x25 [25x406x635]
(1)1x16x25 [25x406x635]
(1)1x16x25 [25x406x635]
(1)1x16x25 [25x406x635]
(1)1x16x25 [25x406x635]
(1)1x16x25 [25x406x635]
Refrigerant Charge Oz. [g]
165 [4678]
165 [4678]
165 [4678]
165 [4678]
Weights
Net Weight lbs. [kg]
580 [263]
580 [263]
580 [263]
585 [265]
Ship Weight lbs. [kg]
587 [266]
587 [266]
587 [266]
592 [269]
3
4
AFUE %
NOTES:
1. Cooling Perform
a
nce is r
a
ted
a
t 95° F
a
mbient,
8
0° F entering dry bulb, 67° F entering wet bulb. Gross c
a
p
a
city does not include the effect of f
a
n motor he
a
t. ARI c
a
p
a
city
is net
a
nd includes the effect of f
a
n motor he
a
t. Units
a
re suit
a
ble for oper
a
tion to ±20% of nomin
a
l cfm. Units
a
re certified in
a
ccord
a
nce with the Unit
a
ry Air Conditioner
Equipment certific
a
tion progr
a
m, which is b
a
sed on ARI
S
t
a
nd
a
rd 210/240 or 360.
2. EER
a
nd/or
S
EER
a
re r
a
ted
a
t ARI conditions
a
nd in
a
ccord
a
nce with DOE test procedures.
3. He
a
ting Perform
a
nce limit settings
a
nd r
a
ting d
a
t
a
were est
a
blished
a
nd
a
pproved under l
a
bor
a
tory test conditions using Americ
a
n N
a
tion
a
l
S
t
a
nd
a
rd Institute st
a
nd
a
rds.
R
a
tings shown
a
re for elev
a
tions up to 2000 feet. For elev
a
tions
a
bove 2000 feet, r
a
tings should be reduced
a
t the r
a
te of 4% for e
a
ch 1000 feet
a
bove se
a
level.
4. Outdoor
S
ound R
a
ting shown is tested in
a
ccord
a
nce with ARI
S
t
a
nd
a
rd 270.
Содержание RKNL 13 SEER (3-5 TONS) SERIES
Страница 6: ...6 FIGURE 3 CABINET DIMENSIONS AND ACCESS LOCATIONS FIGURE 4 SUPPLY AND RETURN DIMENSIONS I282 I288 ...
Страница 25: ...25 FIGURE 20 FIGURE 21 INTEGRATED FURNACE CONTROL SPEED TAP BLOCK FIGURE 22 ...
Страница 26: ...26 FIGURE 22 Continued ...
Страница 79: ...79 FIGURE 23 WIRING DIAGRAM ...
Страница 80: ...80 FIGURE 24 WIRING DIAGRAM ...
Страница 81: ...81 FIGURE 25 WIRING DIAGRAM ...
Страница 82: ...82 FIGURE 26 WIRING DIAGRAM ...
Страница 83: ...83 FIGURE 27 WIRING DIAGRAM ...
Страница 84: ...84 FIGURE 28 WIRING DIAGRAM ...
Страница 85: ...85 FIGURE 29 WIRING DIAGRAM ...
Страница 87: ...87 FIGURE 31 SYSTEM CHARGE CHARTS 3 5 TON COOLING 13 14 SEER ...
Страница 88: ...88 FIGURE 32 SYSTEM CHARGE CHARTS 4 TON COOLING 13 14 SEER ...
Страница 89: ...89 FIGURE 33 SYSTEM CHARGE CHARTS 5 TON COOLING 13 SEER ...
Страница 94: ...94 ...
Страница 95: ...95 ...
Страница 96: ...96 CM 0606 ...