3. Installation space
3-1. Models: RP1724HJVXA and RP1730HJVXA
¢
Space requirement
Provide sufficient installation space for product safety.
Single outdoor unit installation
•
When the upper space is open:
Unit: in (mm)
When there are obstacles at the rear only.
When there are obstacles at the rear and
sides.
4 (100) or more
10 (250)
or more
12 (300)
or more
4 (100)
or more
When there are obstacles at the front only.
When there are obstacles at the front and
rear.
24 (600)
or more
24 (600)
or more
4 (100)
or more
•
When there is an obstruction in the upper space:
Unit: in (mm)
When there are obstacles at the rear
and above.
When there are obstacles at the rear, sides, and
above.
12 (300)
or more
Max. 20
(500)
24 (600)
or more
40 (1,000)
or more
4 (100)
or more
10 (250)
or more
20 (500)
or more
Max. 20
(500)
- 70 -
3-1. Models: RP1724HJVXA and RP1730HJVXA
3. Installation space
OUTDOOR UNIT
RP1724-1748HJVXA
OUTDOOR UNIT
RP1724-1748HJVXA