Rheem Residential Electric Models Скачать руководство пользователя страница 8

The complete wiring schematic diagram for 240 Volt and 120 Volt

units is shown below in Figure 6 & 7.

qualified electrician. The voltage requirements and wattage load for the
water heater is specified on the rating plate on front of heater. Be certain
that the power supply provided is equivalent to that marked on the water
heater’s rating plate. All wiring must conform to local codes or, in the
absence of local codes, the latest edition of National Electrical Code
ANSI/NFPA 70.

The Specification Table (supplied separately with the water heater) recom-
mends minimum branch circuit sizing based on National Electric Code.

The branch circuit wiring must include either:

A.

Metallic conduit or metallic sheathed cable approved for use as a
grounding conductor and installed with fittings approved for the pur-
pose. (refer to Figure 5A)

B.

Non-metallic sheathed cable or metallic conduit or metallic sheathed
cable not approved for use as a ground conductor shall include a
separate conductor for grounding. It should be attached to the ground
terminals of the water heater and the electrical distribution box. (Refer
to Fig. 5B)

Be sure to follow local and national codes as well as any electric utility
requirements when making the connections.

Tank MUST BE full of water before power is turned on. Heating
elements WlLL BE DAMAGED if energized for even a short time
while tank is dry. The water heater’s warranty does not cover
damage or failure resulting from operation with an empty or
partially empty tank. (Refer to the limited warranty for complete
terms and conditions.)

8. PIPE WRAP — 

To realize maximum energy savings, all exposed pipes

should be insulated. However, most of the energy losses occur close to the
water heater.  Install one piece of insulation on the cold water supply line and
one piece on the hot water line. (Refer to Figure 8). Install the pipe wrap as
close to the water heater as the installation allows. Make sure fittings are cov-
ered and the joint in the pipe wrap is sealed.

The water heater tank is insulated with 2 

1

/

2

” of foam insulation to stop heat

loss. More insulation is not needed. DO NOT install an insulating blanket.

6

Installation

Figure 7  — Complete Wiring Schematic Diagram — 120 Volt

Units

3

4

BLACK

GROUND

RED

YELLOW

BLUE

From 240 V

Power Source

Water Heater

Junction Box

High Limit
Switch

Temperature Control
Thermostat

BLACK

GROUND

WHITE

YELLOW

WHITE

From 120 V

Power Source

Water Heater

Junction Box

High Limit
Switch

Temperature Control
Thermostat

Figure 6  — Complete Wiring Schematic Diagram —240 Volt Units

Figure 8 — Pipe Wrap 

Pipe Wrap 
(Seal Tightly)

NOTE!
Do Not Cover or Block
This Opening on
Vacuum Valve

CAUTION

!

Содержание Residential Electric Models

Страница 1: ...es a parts list sup plement It is imperative that all persons who are expected to install maintain operate or adjust this water heater read the instructions carefully so that they may understand how t...

Страница 2: ...Shut Down 9 Draining the Water Heater 10 Maintenance Routine Preventive Maintenance 11 Temperature and Pressure Relief Valve 11 Heating Elements 12 Trouble Shooting Guide 13 Wiring Schematic Diagrams...

Страница 3: ...operating properly you have properly installed the drain pipe on the temperature and pressure relief valve the vacu um relief valve has been installed and you have complete ly filed the water heater w...

Страница 4: ...result in damage to the area adjacent to it or to lower floors of the structure Where such areas cannot be avoided it is recommended that a suitable drain pan adequately drained be installed under the...

Страница 5: ...COLD Inlet Hex Union Nut HOT Outlet Hex Union Nut T P Relief Valve COLD Inlet Hex Union Nut HOT Outlet Hex Union Nut T P Relief Valve COLD Inlet Hex Union Nut Hot Water Outlet Cold Water Inlet Shut Of...

Страница 6: ...tion between the extension fitting and the water heater uses a seal ring If unions are not used on the water supply lines the extension fitting can be removed from the heater to accommodate final conn...

Страница 7: ...heck all plumbing work for leaks and repair as necessary before proceeding with installation Tank MUST BE full of water before power is turned on Heating ele ments WlLL BE DAMAGED if energized for eve...

Страница 8: ...he connections Tank MUST BE full of water before power is turned on Heating elements WlLL BE DAMAGED if energized for even a short time while tank is dry The water heater s warranty does not cover dam...

Страница 9: ...thorized energy saving devices may short en the life of the water heater and may endanger life and property The manufacturer disclaims any responsibility for such loss or injury resulting from the use...

Страница 10: ...usion non metallic water heaters are designed and built to provide years of service Having them properly installed and accurately adjusted is essential if they are to perform reliably in the many chal...

Страница 11: ...heater remove jacket access panel and insulation and the access panel and insulation to expose the Thermostat and High Limit Switch Refer to Figure 9 The plastic personnel protector SHOULD NOT be rem...

Страница 12: ...hen turn off cold water supply Next it is necessary to open a hot water faucet or lift the han dle on the relief valve to admit air to the tank and KEEP OPEN Attach a garden hose to the drain valve on...

Страница 13: ...need replacing use only a valve specified by local codes but not less than a new combina tion temperature and pressure relief valve complying with the Standard for Relief Valves and Automatic Gas Shu...

Страница 14: ...nt for removal lift up the hinged portion of the ther mostat protective cover by gently pulling the lower corners up and away from the thermostat Be careful to avoid pulling the thermostat from its mo...

Страница 15: ...esulting from operation with an empty or partially empty tank Reference is made to the limited warranty for com plete terms and conditions After a very long shut down period the water heater s operati...

Страница 16: ...nting plate Inspect and insure that retaining spring s or mounting screws hold thermostat s tightly to mounting plates 5 Element not installed with tubes at lowest position Inspect and repair Up arrow...

Отзывы: