42
Preparation
Check Power Supply
With multi-meter at incoming power, check voltage be-
tween:
Hot - Common (≈120 VAC)
Hot - Ground (≈120 VAC)
Common - Ground (< 1 VAC)
Attach Manometers to Measure Pressures
1. Turn off main gas valve.
2. Attach 24” scale manometer to the first main gas
shut-off valve pressure tapping.
3. Attach (1) 12” scale manometer to the outlet side
of the second main gas shut-off valve pressure
tapping.
4. Attach (1) 12” scale manometer near the fan-prov
-
ing switch. Pull black cap from air pressure switch
tee and connect the manometer. NOTE: Retain
caps for reinstallation later.
Check Gas Supply Pressure
1. Slowly turn on main gas shut-off valve.
2. Read the gas supply pressure from the manom-
eter; minimum supply pressure for natural gas is
5.0 in. WC, recommended supply is 7.0 in. WC,
minimum supply pressure for propane gas is 11.0
in. WC (dynamic readings, all stages firing).
3. If the pressure is > 14.0 in. WC, turn off the valve.
4. Check if the service regulator is installed and/or
adjust the service regulator.
A
WARNING:
Do not turn on gas at this time.
A
WARNING:
If Common - Ground is > 1 VAC,
STOP: Contact electrician to correct ground
failure. Failure to do this may burn out 120V-24V
transformer, or may cause other safety control
damage or failure.
Start-Up
Blower Adjustment
1. Turn off power.
2. Unplug cap at pressure switches and connect ma-
nometer(s) to the tee.
3. Close all manual firing valves.
4. Turn power on.
5. Check manometers attached to fan pressure
switch. The reading should be 1.4 ± 0.1 in. WC for
propane gas and natural gas. If not, adjust the air
shutter on the blowers to attain the correct value.
6. Turn power off.
7. Reconnect this cap.
Main Burner Adjustment
1. Turn off unit.
2. Open manual firing valves.
3. Turn on the unit, wait 15 seconds, and the igniter
should glow. Look into sight glass located at each
end of the heater to check igniter operation. Gas
valves should open in 45-60 seconds.
4. If burner does not light on first trial. It will retry, up
to three times.
5. Main burner ignition: Check manifold gas pressure
at gas valve outlet pressure tap. This should read
3.5 ± 0.1 in. WC for natural gas and 10.5 ± 0.1 in.
WC for propane gas on heater models 302 thru
902. 9.0 to 9.5 in. WC for Propane gas heater
models 992 thru 2342.
6. If the pressure reading differs by more than ± 0.1
in. WC, remove screw cover from the gas pressure
regulator and adjust main burner manifold pres-
sure. Replace the screw cover. Repeat steps 2 to
5 on other valves as necessary.
A
CAUTION:
Special manifold and air settings
may be required. Verify rating plate and blower
housing.
Содержание Raypak Delta Limited 399B
Страница 23: ...23 Fig 21 2 Stage Wiring Connections Fig 22 3 Stage Wiring Connections Fig 23 4 Stage Wiring Connection...
Страница 39: ...39 Wiring Diagram Models 399B 1259B...
Страница 40: ...40 Wiring Diagram Models 1529B 2339B...
Страница 51: ...51 DIAGNOSTIC DETAIL 12 J 7 J 6 J 5 J 3 0 2 0 16 S 1 F 2 F 3 F 4 F BLOWER DETAIL...
Страница 53: ...53 13 J 8 J 10 J 11 J 4 J 2 J 3 J 6 C 14 J 9 J 1 J CONTROL BOX DETAILS...
Страница 57: ...57 ILLUSTRATED PARTS LIST MODELS 989B 2339B 10 J 3 O 5 O...
Страница 58: ...58 12 H 6 H 7 H 8 H 2 H 9 H 3 H 5 H 1 H 4 H 1 P HEAT EXCHANGER DETAILS BURNER ASSEMBLY DETAILS...
Страница 59: ...59 CONTROL BOX DETAILS 9 J 8 J 23 S 13 J 10 J 3 O 10 J 3 O 5 O FRONT SWITCH DETAILS...
Страница 66: ...66...
Страница 67: ...67 Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Litho in U S A NOTES...