Vertical Vent Installation

A fire stop plate should be installed at every
penetration of a floor or ceiling if the vent is
not running in a fire-rated shaft. Maintain the
recommended air space clearance to
combustible materials and building insulation.

Once the vent terminal location has been
determined, make a hole through the roof and
interior ceiling to accommodate the vent pipe.
Complete the vent pipe installation to the
water heater’s vent connector fitting on the
water heater vent collar outlet. Support
vertical or horizontal runs as previously
mentioned. If required, use silicone sealant 
at the point the vent connector joins the 
water heater.

Install adequate flashing where the vent pipe
passes through the roof. Determine the vent
terminal height and install the vent pipe
accordingly. Refer to the diagram above for
proper vent terminal height. Connect vent
elbow onto vertical pipe through roof.
Connect short piece of vent pipe
(approximately 6” long [15 cm]) to 
elbow, and the terminal elbow with the
protective screen.

The vent roof system must terminate at least
1 foot (30 cm) above the roof line and at least
2 feet (61 cm) higher than any portion of the
building within 10 feet (3 m).

Install supports every 5 feet (1.5 m) vertically
along the vent pipe route. Vertical supports
are required after every transition to vertical

and are required after
every offset elbow.
When the vent is free-
standing and penetrates
a roof/ceiling, another
means of support must
be used at a second
location.

Follow the vent
manufacturer’s
recommended
installation instructions
provided with the vent
purchased from the
manufacturer. 

Chase Requires
6" (15 cm) Clearance
to Combustibles

Firestop

Firestop

Roof Jack

Adjustable
Roof Flashing

Vent
Adapter

3" (8 cm) Clearance

Support
Hanger

Condensate

Trap

To Drain. Dispose of

condensate in accordance

with local codes

Storm
Collar

Support
Clamp

1/4" per foot upward slope

2'

(61 cm)

Max

Standard Vertical Vent Termination

Vertical Vent Termination Location

The location of the vent terminal depends on the following
minimum clearances and considerations (see diagram at left):

Minimum twelve (12) inches (30 cm) above roof.

Minimum twelve (12) inches (30 cm) above anticipated
snow level.

Maximum twenty-four (24) inches (60 cm) above roof level
without additional support for vent.

Four (4) feet (1.2 m) from any gable, dormer or other 
roof structure with building interior access (i.e., vent,
window, etc.).

Ten (10) feet (3 m) from any forced air inlet to the building.
Any fresh or make-up air inlet such as a dryer or furnace
area is considered to be a forced air inlet.

Min. 12" (30 cm)
Above Roof

Min. 12" (30 cm)
Above Anticipated
Snow Level

Max. 24" (60 cm)
Above Roof (Without
Additional Support)

Vent Pipe
Through Roof

Elbow

Termination Elbow
w/ Protective Screen

Small (6” min) (15 cm)
section of vent

Notice: Only Rheem
approved termination 
and parts should be used
during installation.

Notice: Follow vent
manufacturer’s installation
instructions and their
recommended clearances to
combustibles as required.

15

Chase Requires
6" (15 cm) Clearance
to Combustibles

Firestop

Firestop

Roof Jack

Rain Cap

Adjustable

Roof 

Flashing

Vent
Adapter

3" (8 cm) Clearance

Support
Hanger

Condensate

Trap

To Drain. Dispose of

condensate in accordance

to local codes

Storm
Collar

Support
Clamp

1/4" per foot upward slope

2'

(61 cm)

Max

Alternate Vertical Vent Termination

with Rain Cap

Vent Pipe

Vent Pipe

Содержание PH-16(FISN)(FISP)

Страница 1: ...ecommendations for the proper installation and adjustment of the water heater and two to the owner operator to explain the features operation safety precautions maintenance and troubleshooting of the...

Страница 2: ...ce READ THIS MANUAL FOR YOUR RECORDS Write the model and serial numbers here You can find them on a label on the appliance Staple sales slip or cancelled check here Proof of the original purchase date...

Страница 3: ...well as other flammable materials and liquids adhesives solvents paint thinners etc and the vapors they produce are extremely dangerous DO NOT handle use or store gasoline or other flammable or combu...

Страница 4: ...emote control and a dip switch adjustment Only qualified service personnel should perform this adjustment Only factory authorized remote control s should be used Notice When this water heater is suppl...

Страница 5: ...e or LP gas must be used with great caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level Before attempting to light the water heater make sure to...

Страница 6: ...ON READ ALL INSTRUCTIONS BEFORE USING WARNING For your safety the information in this manual must be followed to minimize the risk of fire or explosion electric shock or to prevent property damage per...

Страница 7: ...which may result in severe burns death or property damage The water heater must be located so it is not subject to physical damage for example by moving vehicles area flooding etc The water heater sho...

Страница 8: ...ed or accidentally spilled The water heater should be installed as close as practical to the vent termination to minimize vent length and the number of elbows required for venting The water heater sho...

Страница 9: ...ing of conventional frame masonry or metal construction infiltration air is normally adequate for proper combustion and ventilation If the water heater is installed in a confined space provisions for...

Страница 10: ...leting the installation and putting the water heater into service DANGER Failure to install the appliance vent adapter and properly vent the water heater to the outdoors as outlined in the Venting sec...

Страница 11: ...nce vent adapter manufacturer s instructions Appliance Vent Adapter Water Heater Exhaust Flow A B High Temp Sealant Collar Clamp Draining the Condensate Provision should be made to collect and dispose...

Страница 12: ...1 foot 300 mm above opening 6 inches 15 cm for appliances 10 000 Btuh 3 kW 9 inches 23 cm for appliances 10 000 Btuh 3kW and 50 000 Btuh 15kW 12 inches 30 cm for appliances 50 000 Btuh 15kW K Clearanc...

Страница 13: ...posed vent pipe of indoor water heaters outside of building Guard vent against accidental contact with people and pets Install outdoor water heater such that air inlet and flue outlet is above anticip...

Страница 14: ...walls Reinstall the decorative sheathing around the Wall Thimble This assembly may be painted to match the exterior decor Attach a Rheem approved 3 7 6 cm screened 90 elbow termination to the female...

Страница 15: ...vent purchased from the manufacturer Chase Requires 6 15 cm Clearance to Combustibles Firestop Firestop Roof Jack Adjustable Roof Flashing Vent Adapter 3 8 cm Clearance Support Hanger Condensate Trap...

Страница 16: ...ate both cold and hot water supply lines DO NOT cover the drain or pressure relief valve To ensure proper operation of the water heater the following water pressure guidelines should be followed Opera...

Страница 17: ...nction Installation of unions or flexible copper connections are recommended on the HOT and COLD water lines so that the water heater may disconnect easily for servicing if necessary Install a Check V...

Страница 18: ...overn the installation of relief valves If local codes require that a temperature and pressure relief valve should be installed the manufacturer recommends a type 40XL Watts T P relief valve or an equ...

Страница 19: ...s Use compound sparingly on male threads only A sediment trap should be installed at the bottom of the gas line Do not use excessive force over 31 5 ft lbs 42 7 Nm in tightening the pipe particularly...

Страница 20: ...connect to the water heater Therefore a maximum of three controls can connect to the water heater No other manufacturer s controls are suitable for use with this water heater DO NOT attempt to disasse...

Страница 21: ...Place the remote control over the base plate Ensure the projections in the base plate fit into the housings in the remote control Fix the control to the base plate at the bottom of the remote control...

Страница 22: ...n servicing controls Wiring errors can cause improper and dangerous operation Verify correct operation after servicing BK 8 R GR Y B O W BR WATER FLOW SENSOR OVER HEAT LIMITER BK GND GND THE CONNECTOR...

Страница 23: ...codes or plumbing authority requirements may vary from the instructions or diagrams provided and take precedent over these instructions Vacuum Relief Valve Not Supplied If required install per local c...

Страница 24: ...uce the standby heat loss encountered with storage tank heaters This water heater does not store water making an insulation blanket unnecessary The manufacturer s warranty does not cover any damage or...

Страница 25: ...upply Gas type matches rating plate Gas supply pressure is sufficient for the water heater Gas line equipped with shut off valve union and sediment trap Approved pipe joint compound used Soap and wate...

Страница 26: ...s label 2 Turn off all electric power to the appliance 3 Do not attempt to light the burner by hand 4 Turn the Gas Shutoff Valve located on the outside of the unit clockwise to the OFF position 5 Wait...

Страница 27: ...alves are available for reducing point of use water temperature by mixing hot and cold water in branch water lines Contact a licensed plumber or the local plumbing authority for further information Se...

Страница 28: ...otter water increases the risk of scald injury Always supervise young children or others who are incapacitated The water heater is equipped with a device that will shut off the gas supply to the burne...

Страница 29: ...nance and or cleaning ensure proper operation by turning on a hot water faucet Housekeeping Before performing Housekeeping tasks to this water heater turn the unit off and disconnect the power supply...

Страница 30: ...inspect the burner flame Blue flames should be seen when the main burner is firing See figure on left for location of sight glass If any unusual burner operation is noted the water heater should be s...

Страница 31: ...eezing conditions even for a short period of time be sure to drain all water from the unit as instructed above Exposure to freezing conditions can occur from down draft of venting system or from insta...

Страница 32: ...functions if applicable Check and replace if necessary Error code displayed on remote control See instructions for Error Code and if required contact a dealer for service Not enough water demand Incre...

Страница 33: ...as type Improper venting vent material or vent configuration Open the Gas shutoff valve fully Contact gas utility company Fill up LP Gas container or replace with a new cylinder of LP Gas Bleed all ai...

Страница 34: ...t connectors or other safety devices Refer repairs to qualified service personnel WARNING For your safety DO NOT attempt to disassemble this unit for any reason Indoor Water Heater Gas Supply Unit Cov...

Страница 35: ...then continue as listed below Press the SW2 button on the left hand side of the PCB for more than 1 second The LED on the PCB starts illuminating continuously At the same time the display of the Main...

Страница 36: ...f completion of installation the owner shall have a period of thirty 30 days to comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon mono...

Отзывы: