COMMISSIONING 

22 

 

 

 

Switch on the electrical supply to the circulator(s). 

 

If necessary, remove the temperature knob and hub using the 3mm allen key supplied. 

 

Rotate the spindle(s) of the thermostatic mixing valve(s) fully anti-clockwise (ie full hot) 

 

Measure the temperature at the cold water inlet test point in the warm water unit. 

 

When  the  system  has  reached  at  least  60

C  allow  the  water  to  circulate  for  at  least  1  hour.  During  this 

period it is recommended the pipe work be checked again for leaks. 

Note:

 if the system temperature fails to reach 60

C check the temperature setting of the water heating plant. 

 

SETTING THE TEMPERATURE 

For multiple valve systems, each valve should be set individually and then the whole system checked for overall 
performance. 
Test points are provided for convenient temperature measurements. 
 
1.  Ensure the warm water return circulator is turned off and isolated during this procedure.  
2.  Open the cold and hot water isolating valves on the first mixing valve and isolate the second & third mixing 

valve, if applicable. 

3.  Remove the temperature knob using the 3 mm Allen key (supplied)  
4.  Pull off the hub (refer to Figure 1) 
5.  Open a warm water tap or the test/drain tap so that a flow rate in excess of 8 L/min is achieved. 
6.  Rotate the spindle until the required maximum blend temperature is obtained at the test point. 

(CLOCKWISE = DECREASE TEMPERATURE, ANTICLOCKWISE = INCREASE TEMPERATURE) 

 

When  resistance  is  felt  do  not  use  force  to  turn  any 
further, as this can damage the internal parts. 

 
7.  Once  the  desired  maximum  blend  temperature  is 

achieved,  re-fit  the  hub  without  disturbing  the  spindle, 
positioning it so that the centre stop slot in the hub fits over 
the top of the cartridge stop (refer to 

Figure 2

), preventing 

any further rotation in either direction. Check that the blend 
temperature has not altered.  

8.  Refit  the  temperature  knob.  Make  sure  that  the  indicator 

points to 6 o'clock. 

9.  Record  the  temperature  measured  at  the  test  point  in  the 

Commissioning Log on page 23. 

10.  Isolate  the  first  valve  and  repeat  steps  2  to  9  for  the 

second and third valves in turn. 

11.  When  complete,  open  all  mixing  valves  in  the  system. 

Open  sufficient  taps  to  at  least  exceed  the  minimum  flow 
rate  required  for  the  system  (refer  pg  7)  and  check 
temperature  at  the  test  point  on  the  warm  water  system, 
and the nearest warm water outlet in the building. 

12.  Open more taps in the building to create a high flow and check and record temperatures at the test point and 

nearest warm water outlet. 

Note:

 depending on the layout of the establishment, it may be necessary to adjust the temperature leaving the 

warm water system to achieve the required temperature at the nearest outlet.  

 
CHARGING THE SYSTEM 

Turn on the warm water return circulator and set to the highest speed. 
Water in the warm line will begin to return to the mixing plant. Monitor the return temperature. Rheem Guardian 
is capable of maintaining system temperature with a differential between outlet and return of 2

C. System design 

will dictate the actual differential achievable. 
 

Note:

  if  the  system  was  filled  with  hot  water  for  sanitising,  the  system  may  need  to  be  flushed  at  the  furthest 

outlet prior to turning on the pump, until all hot water is removed from the system. 
 

 

Fig 2 

centre stop slot 

Содержание Guardian Warm Water

Страница 1: ...This warm water system must be installed and serviced by a qualified person Please leave this guide with a responsible officer Owner s Guide and Installation Instructions Rheem Guardian Warm Water...

Страница 2: ...a licensed person will give you a Compliance Certificate showing that the work complies with all the relevant Standards Only a licensed person will have insurance protecting their workmanship for 6 ye...

Страница 3: ...ead pages 4 10 The other pages are intended for the installer but may be of interest Contents 3 About your warm water system 4 Operating parameters 6 Water supplies 6 Save a service call 10 Installati...

Страница 4: ...ifferential of approximately 50oC between the hot and cold inlet temperatures and with differentials of 15 35oC between the blend setting and either supply installation and usage environment not subje...

Страница 5: ...rm water system must be installed by a qualified person and in accordance the installation instructions and in compliance with Standards AS NZS 3500 4 AS NZS 3000 and all local codes and regulatory au...

Страница 6: ...valves to give the total system flow at a given pressure loss TEMPERATURES Minimum Cold Water Temperature 1 C Maximum Hot Water Temperature 70 C Minimum Hot Water Supply Temperature Blend water tempe...

Страница 7: ...of the water TDS in mg L is approximately 70 of the conductivity in S cm CHLORIDE AND PH In a high chloride water supply the water can corrode stainless steel parts and cause them to fail Where the ch...

Страница 8: ...or scaling properties In a corrosive water supply the water can attack copper parts and cause them to fail Where the saturation index is less than 1 0 the water is very corrosive and the Rheem warrant...

Страница 9: ...l Range 35 C 50 C Note For optimum performance reasons it is recommended that the maximum hot water temperature is limited to 65 C Caution During thermal disinfection the mixing valve can operate up t...

Страница 10: ...er supply to another can have a detrimental effect on the operation and or life expectation of the warm water system Where there is a changeover from one water supply to another e g a rainwater tank s...

Страница 11: ...ate Have you checked the heat loss in the system As warm water is supplied at or near user temperatures heat loss reduction is a critical factor in ensuring suitable temperatures are delivered at the...

Страница 12: ...om the same source for the correct operation of system recirculation This will also help ensure balanced inlet pressures to the warm water unit Clearance must be allowed for servicing of the thermosta...

Страница 13: ...avity fed tank supply systems If a tank supply is used a booster pump must be installed to supply cold water to the water heating plant and warm water unit REDUCING HEAT LOSSES PIPE SIZING Maintaining...

Страница 14: ...INSTALLATION 14 WARM WATER UNIT DIMENSIONS...

Страница 15: ...ATER RHEEM COMMERCIAL WATER HEATERS LEGEND LEGEND GUARDIAN WARM WATER WITH RAYPAK WATER HEATERS TYPICAL INSTALLATION WARM WATER WITH RHEEM COMMERCIAL WATER HEATERS TYPICAL INSTALLATION WARM WATER WITH...

Страница 16: ...INSTALLATION 16 TYPICAL INSTALLATION MANIFOLDED WARM WATER UNITS TYPICAL INSTALLATION WARM WATER WITH LOLINE SOLAR PRE HEAT RHEEM GUARDIAN WARM WATER UTILISING COMMERCIAL LOLNE SOLAR PRE HEAT LEGEND...

Страница 17: ...INSTALLATION 17 TYPICAL INSTALLATION WARM WATER WITH HILINE SOLAR PRE HEAT TYPICAL INSTALLATION WARM WATER WITH COMMPAK RHEEM GUARDIAN WARM WATER UTILISING COMMERCIAL HILNE SOLAR PRE HEAT LEGEND...

Страница 18: ...let to the water heating plant The pipe work must be cleared of foreign matter before connection Where solar preheat forms a part of the system particular attention needs to be given to the cold water...

Страница 19: ...to the building warm water flow line Note If a UV system is not a part of the installation an isolating valve MUST be fitted before connecting to the building flow line WARM WATER BY PASS To facilita...

Страница 20: ...culator s Air will begin to be forced out of the taps As water flows freely from each tap close it Open the cold water isolation valve s at the inlet s to the thermostatic mixing valve s Open the near...

Страница 21: ...perature is pre set at the factory to approximately 43oC under ideal installation conditions Site conditions sanitising prior to commissioning or personal preference will mean the maximum blend temper...

Страница 22: ...mum blend temperature is achieved re fit the hub without disturbing the spindle positioning it so that the centre stop slot in the hub fits over the top of the cartridge stop refer to Figure 2 prevent...

Страница 23: ...stem will automatically shut down Record the maximum and stabilised temperature recorded at the test point and at the first outlet in the building Reinstate the cold water supply to the mixing valves...

Страница 24: ...emperature Hot water 60 70 o C Supply pressure Temperature Warm Water Valves exercised Test point temperature Valve 1 Valve 2 Valve 3 Combined valves Full Flow Min Flow Return temperature Pump speed s...

Страница 25: ...UMBER____________ SERIAL NUMBER___________ Signature Comments UV tube cleaned UV hours run Shut off test final max Return test point temp Nearest outlet temp Valve 3 test point temp Valve 2 test point...

Страница 26: ...26 WATER QUALITY TEST RESULT LOG RHEEM GUARDIAN WARM WATER Model Number______________ Serial Number____________ Date Sample Point ID Report No Result Report Filed Signature Sample 1 Sample 2...

Страница 27: ...onella Sampling Unless prescribed by a regulating authority sampling at the following rates is recommended 1st 3 months 2 samples once per month Month 6 2 samples 6 monthly there after 2 samples The a...

Страница 28: ...arried out in accordance with these instructions and must be conducted by designated qualified and competent personnel This mixing valve is designed for minimal maintenance under conditions of normal...

Страница 29: ...artridge is replaced the In service test should be repeated as if it was a new valve Note In service tests should be carried out with a frequency which identifies a need for service work before an uns...

Страница 30: ...structions 3 Measure and record blend temperature flow rate at maximum flow 4 Measure and record blend temperature and flow rate at minimum flow Has mixed water temperature changed by more than 1K 5 C...

Страница 31: ...31 This page is left intentionally blank...

Страница 32: ...shall be the owner s responsibility 2 5 Where the Rheem warm water system is installed in a position that does not allow safe or ready access the cost of that access including the cost of additional m...

Страница 33: ...b Is not installed in Australia 5 HOW TO MAKE A CLAIM UNDER THIS WARRANTY 5 1 If you wish to make a claim under this warranty you need to a Contact Rheem on 131031 and provide owner s details address...

Отзывы: