REME HALO®Zero
has a unique feature which allows the adjustment of the
hydrogen peroxide output by way of an adjustable shroud built into the
REME HALO®Zero
Cell. By sliding the shroud apertures open or closed,
the
can be custom adjusted to the needs of a specific area.
REME HALO®Zero
Input 24VDC to the
REME HALO®Zero Unit
3c. Optional Electrical Connection: (For Installation using 24VDC
Power Supply)
®
RGF recommends for optimal performance and maximum cell life that
the
REME HALO®Zero
product line operates continuously.
REME HALO®Zero
may be connected to the optional 24VDC power
supply. This power supply runs universally from 100-240VAC 50/60Hz.
For international installations the power cord may be replaced with
approved cords having the appropriate regional plug. (International
cords may be purchased at RGF that are approved for this adapter).
Refer to
. All units must be plugged into to outlets fully
Figure 7b
accessible to disconnect for servicing and maintenance. Only use the
24VDC power supply included with the unit. Do not use if the power
supply or appliance is damaged.
Figure 7b
THIS EQUIPMENT MUST ONLY BE INSTALLED BV A QUALIFIED INSTALLER.
CET EQUIPEMENT DOIT ETRE INSTALLE UNIQUEMENT PAR UN
INSTALLATEUR QUALIFIE.
Only use the 24VDC power supply provided.
U lisez uniquement l'alimenta on 24VDC fournie.
REME HALO®Zero Unit
®
REME HALO Zero Output Adjustment
800 - 1,000 CFM fully closed
1,000 - 1,200 CFM 1/4 open
1,200 - 1,600 CFM 1/2 open
1,600 - 2,000 CFM 3/4 open
2,000 - 2,400 CFM fully open
To adjust shroud, loosen small
hilips head screw on bottom of
s h r o u d a n d s l i d e t o d e s i r e d
position. Tighten screw.