Product presentation CRS60

Product presentation CRS60

Circular fire damper with a fire resistance of up to 60 minutes. The damper collar and short damper tunnel guarantee quick and easy 
mounting, both in surface and remote mounting. The optimised design of this fire damper ensures excellent aeraulic and acoustic 
performance. Available in diameters 100-630 mm.
Fire dampers are installed where air ducts penetrate fire-resistant compartment walls. Their role is to restore the fire resistance grade 
of the penetrated wall and to prevent smoke propagation. Fire dampers are distinguished by their degree of fire resistance, by their 
aeraulic properties as well as by their installation ease. Rf-Technologies’ fire dampers are all CE marked. They can be equipped with 
various types of mechanisms depending on the specific needs linked to the project or to the local regulations.

 

5

easy to install

 

5

optimal free air passage and minimal pressure loss

 

5

optimal acoustic performance

 

5

air-tightness class C according to EN1751 

 

suitable for surface-mount in rigid wall and light wall (metal 

stud gypsum plasterboard wall)

 

suitable for installation remote from the wall 

 

tested according to EN 1366-2 up to 300 Pa

 

maintenance-free

 

for indoor use

 

operating temperature: max. 50°C

 

P-marking

EN 1751

  C

1.  casing in galvanised steel
2.  damper blade
3.  operating mechanism
4.  rubber sealing ring
5.  sealing ring for damper blade
6.  collar
7.  intumescent strip

1

2

5

7

4

6

4

3

Range and dimensions CRS60

ØDn [mm] 100 125 160 200 250 315 400 500 630

Exceeding blade: X = on the mechanism side, Y = on the wall side

58%

167

210

ØD

n

Y

X

A

ØDn [mm]

100

125

160

200

250

315

400

500

630

x

-

-

-

-

-

23

66

116 181

y

-

-

10

30

55

88

130 180 245

a

15

15

15

15

15

15

27

27

27

 

ONE

BFN(T)

BFL(T)

P

140

125

121

Q

136

98

80

Z

75

50

40

ØDn

P

Z

Q

70

Содержание CRS60

Страница 1: ... eu en Rf Technologies nv Lange Ambachtstraat 40 9860 Oosterzele Belgium Tel 32 9 362 31 71 Fax 32 9 362 33 07 info rft eu 0749 C16 EN A 08 2022 CRS60 Circular EI60S fire damper for surface and remote mounting ...

Страница 2: ... data 26 Correction factor ΔL 26 Sample order 26 Approvals and certificates 27 Explanation of the abbreviations and pictograms Wn nominal width Hn nominal height Dn nominal diameter E integrity I thermal insulation S smoke leakage Pa pascal ve vertical wall penetration ho horizontal floor penetration o i meets the criteria from the outside o to the inside i i o fire side not important V AC Volt al...

Страница 3: ...sealant 2 EI 60 h o i n o S 300 Pa Stone wool coating with acrylic sealant 1 EI 60 h o i n o S 300 Pa Stone wool coating with acrylic sealant 2 EI 60 h o i n o S 300 Pa Flexible wall Metal studs gypsum plasterboard Type A EN 520 100 mm Fire resistant acrylic sealant 1 EI 60 v e i n o S 300 Pa Fire resistant acrylic sealant 2 EI 60 v e i n o S 300 Pa Stone wool coating with acrylic sealant 1 EI 60 ...

Страница 4: ...depending on the specific needs linked to the project or to the local regulations 5 easy to install 5 optimal free air passage and minimal pressure loss 5 optimal acoustic performance 5 air tightness class C according to EN1751 suitable for surface mount in rigid wall and light wall metal stud gypsum plasterboard wall suitable for installation remote from the wall tested according to EN 1366 2 up ...

Страница 5: ...polar beginning and end of range switch KITS BFLT24 Spring return actuator BFL 24V with thermo electric fuse T KITS BFLT230 Spring return actuator BFL 230V with thermo electric fuse T KITS BFNT24 Spring return actuator BFN 24V with thermo electric fuse T KITS BFNT230 Spring return actuator BFN 230V with thermo electric fuse T KITS ZBAT 72 Black spare part for thermo electric fuse for BFLT BFNT FUS...

Страница 6: ...ucts Product installation always with closed damper blade Verify if the blade can move freely Please observe safety distances with respect to other construction elements The operating mechanism must also remain accessible allow for a clearance of 200 mm around the housing The air tightness class will be maintained if the damper is installed according to the installation manual Rf t fire dampers ar...

Страница 7: ...7 Installation Installation in a rigid wall sealing with acrylic sealant Dn 10 mm 100 Fire resistant acrylic sealant M6 Fire resistant acrylic sealant 1 2 3 4 ...

Страница 8: ...8 Installation Installation in a rigid wall sealing with stone wool Dn 50 mm 100 Fire resistant acrylic sealant M6 Stonewool stuffed Fire resistant acrylic sealant 1 2 3 4 ...

Страница 9: ...nstallation in flexible wall metal stud gypsum plasterboard wall sealing with acrylic sealant 50 2x12 5 1x25 mm F EN520 A EN520 100 mm Dn 10 mm Fire resistant acrylic sealant M6 Fire resistant acrylic sealant 1 2 3 4 5 ...

Страница 10: ...ation in flexible wall metal stud gypsum plasterboard wall sealing with stone wool 50 2x12 5 1x25 mm F EN520 A EN520 100 mm Dn 50 mm Fire resistant acrylic sealant M6 Stonewool stuffed Fire resistant acrylic sealant 1 2 3 4 5 ...

Страница 11: ...11 Installation Installation in shaft wall 50 2x15 1x30 mm F EN520 80 mm Dn 10 mm Fire resistant acrylic sealant M6 1 2 3 4 ...

Страница 12: ...12 Installation Installation in rigid floor sealing with acrylic sealant 100 Dn 10 mm Fire resistant acrylic sealant M6 Fire resistant acrylic sealant 1 2 3 4 5 ...

Страница 13: ...13 Installation Installation in rigid floor sealing with stone wool 100 Dn 50 mm Fire resistant acrylic sealant M6 Fire resistant acrylic sealant Stonewool stuffed 1 2 3 4 5 ...

Страница 14: ...ension where necessary in accordance with the instructions of the duct manufacturer 3 Attention Make sure that the movement of the damper blade is not impeded by the screws Silicate based adhesive 4 Apply the insulation in accordance with the manufacturer s instructions Fire resistant acrylic sealant 1 2 3 4 5 ...

Страница 15: ...e necessary in accordance with the instructions of the duct manufacturer 3 Attention Make sure that the movement of the damper blade is not impeded by the screws Silicate based adhesive 4 Apply the insulation in accordance with the manufacturer s instructions Fire resistant acrylic sealant Stonewool stuffed 1 2 3 4 5 ...

Страница 16: ...0 mm 3 Provide suspension where necessary in accordance with the instructions of the duct manufacturer 4 Attention Make sure that the movement of the damper blade is not impeded by the screws Silicate based adhesive 5 Apply the insulation in accordance with the manufacturer s instructions Fire resistant acrylic sealant 1 2 3 4 5 6 ...

Страница 17: ...ide suspension where necessary in accordance with the instructions of the duct manufacturer 4 Attention Make sure that the movement of the damper blade is not impeded by the screws Silicate based adhesive 5 Apply the insulation in accordance with the manufacturer s instructions Fire resistant acrylic sealant Stonewool stuffed 1 2 3 4 5 6 ...

Страница 18: ... acrylic sealant 3 Provide suspension where necessary in accordance with the instructions of the duct manufacturer 4 Attention Make sure that the movement of the damper blade is not impeded by the screws Silicate based adhesive 5 Apply the insulation in accordance with the manufacturer s instructions 1 2 3 4 5 ...

Страница 19: ...ealant 100 Dn 10 mm 4 Attention Make sure that the movement of the damper blade is not impeded by the screws Silicate based adhesive Silicate based adhesive 5 Apply the insulation in accordance with the manufacturer s instructions Fire resistant acrylic sealant 1 2 3 4 5 6 ...

Страница 20: ...n 50 mm 4 Attention Make sure that the movement of the damper blade is not impeded by the screws Silicate based adhesive Silicate based adhesive 5 Apply the insulation in accordance with the manufacturer s instructions Fire resistant acrylic sealant Stonewool stuffed 1 2 3 4 5 6 ...

Страница 21: ...egulations i e BS9999 Annex V NF S 61 933 and EN13306 Read the maintenance instructions on our website https www rft eu assets PIM DOCUMENTS BROCHURE 20KITS BRO_K139_MAINTENANCE_C pdf Use the damper at up to 95 humidity non condensing The fire damper can be cleaned with a dry or slightly damp cloth It is forbidden to use abrasive cleaners or mechanical cleaning techniques brush ...

Страница 22: ...h off the power supply for at least 5 sec Power the actuator respect the prescribed voltage for at least 75 sec The resetting stops automatically when the end of range is reached damper open Caution If the LED 3 flickers fast 3x sec the battery is discharged use a new battery If the LED 3 flickers slowly 1x sec the resetting is in progress If the LED 3 is continuously on the resetting is complete ...

Страница 23: ...n the thermo electric fuse automatic unlocking the thermo electric fuse reacts as soon as the temperature reaches 72 C type BFLT remote unlocking by interrupting the power supply Caution The thermo electric fuse will not move the damper into its safety position when the temperature reaches 72 C if the motor is not powered Resetting manual resetting turn the enclosed handle anti clockwise To block ...

Страница 24: ...cts as soon as the temperature reaches 72 C type BFNT remote unlocking by interrupting the power supply Caution The thermo electric fuse will not move the damper into its safety position when the temperature reaches 72 C if the motor is not powered Resetting manual resetting turn the enclosed handle anti clockwise To block the motor place the locking button on lock motorised resetting switch off t...

Страница 25: ...1mA 1A 60V 75 s cabled 85 s battery ONE T 230 FDCU L 230 V AC 15 15 N A 0 57W 4 2W 1mA 1A 60V 75 s cabled 85 s battery BFLT24 24 V AC DC N A 0 8W 2 5W 1mA 3A AC 250V 60 s BFLT230 230 V AC N A 1 4W 4W 1mA 3A AC 250V 60 s BFNT24 24 V AC DC N A 1 1W 4W 1mA 3A AC 250V 60 s BFNT230 230 V AC N A 1 8W 5 5W 1mA 3A AC 250V 60 s MEC Running time spring Noise level motor Noise level spring Cable supply contr...

Страница 26: ...069 47 11 004 54 60 dB Δp Pa 112 15 110 44 87 46 68 76 43 51 31 91 22 78 17 56 11 08 Q m h 225 36 428 97 775 21 1 227 60 1 846 66 2 898 00 3 966 52 5 793 47 7 910 05 50 dB Δp Pa 48 09 47 73 39 04 30 26 20 89 15 88 12 12 9 05 5 73 Q m h 147 60 278 76 506 67 813 60 1 292 49 2 044 80 2 799 16 4 118 16 5 685 83 40 dB Δp Pa 20 63 20 15 10 74 13 29 10 24 7 91 6 03 4 57 2 96 Q m h 96 48 176 71 337 30 540...

Страница 27: ...cates All our dampers are submitted to a number of tests by official test institutes Reports of these tests form the basis for the approvals of our dampers 0749 requested requested If the product is manipulated in any other way than described in this manual Rf Technologies will decline any responsibility and the guarantee will expire ...

Отзывы: