Radio Frequency Systems
BD550W Series Air Dryers User’s Guide
Page 73 of 104
100518833 – Rev. B
Allow the Humidity reading to rise over 10.0%.
9.11.5
After three (3) minutes, verify that a Humidity Alarm appears, and the
Dryer goes into
SHUTDOWN
mode.
9.11.6
Replace the Humidity
Sensor into the Humidity
Block.
9.11.7
Press the
RESET Button
to clear the Humidity alarm.
If you are unable to create a Humidity / Shutdown alarm as described, see section
13.12 for troubleshooting information.