When a mains failure occurs, the power supply no longer provides power. The battery

now supports the load without interruption of the load. Restoration of the mains restarts

the power supply which will resume support of the load and charging of the battery.
During extended mains failures the unit disconnects the battery before it becomes

excessively discharged. The battery is automatically reconnected when the mains

recovers. This feature contributes to long battery lifetime and allows unattended operation

of a system.

Protection

The power supply incorporates the following protection features
• Reverse polarity connection of the battery will not cause damage to the power supply or

the battery and the output load will remain unaffected.

• Electronic battery fusing is provided in series with battery connection to protect the load

and power supply when it is powered from the battery.

• Accurate current limit protection is provided for both load and battery. Automatic

recovery from short circuit is provided with no current tailing in short circuit operation.

• Over voltage protection provides shutdown of power supply.

• Inrush Surge limiting at turn on.

• OTP over temperature protection for blocked fuse incorrect install.

Battery LVD Operation

A low voltage disconnect (LVD) is provided to prevent deep discharge of the battery.
LVD Operation

When mains has failed and the battery is supporting the load, the battery must be

disconnected from the load if its voltage falls below the following levels:
Model

Battery Disconnect Condition

Validation time ±30%

(LVD_Disconnect)

SME240-1 2-20

1 0.25 V ±0.25 V

1 .8 sec

The battery will be connected to the charger/load output when its voltage rises above

the following levels:
Model Battery

Connect Condition

Validation time ± 30%

(LVD_Reconnect)

SME240-1 2-20

11 .90 ± 0.30 V

2.3 sec

The battery disconnect is incorporated into the Bve line.
The BATTERY output has protection incorporated against a reversed battery connection.

A reversed battery is left disconnected so that the LOAD output can still run the load from

mains power. The quiescent current drain on the battery when the main has failed is less

than 3 mA.

Содержание SME240-1 2-20

Страница 1: ...SME240 12 20 Owner s Manual...

Страница 2: ...unting 5 Installation 6 Mounting Options 6 Connectors 6 Alarm Temperature Sensor 6 DC Power Output 6 Connection 7 Cabling 7 Voltage Setting 7 Cooling 8 Specifications 8 Approvals 9 Copyright RFI 2011...

Страница 3: ...nnector Flexible mounting options Full protection for the power supply load and battery Local technical support 1 Safety Correct installation is the most critical factor in ensuring the safe use of th...

Страница 4: ...very from short circuit is provided with no current tailing in short circuit operation Over voltage protection provides shutdown of power supply Inrush Surge limiting at turn on OTP over temperature p...

Страница 5: ...Other fault conditions Battery Charging Operational requirements Trickle Charge When mains is present but the battery voltage is below the LVD Connect voltage the battery is trickle charged circuit th...

Страница 6: ...onnected backwards The battery circuit breaker has tripped The relay contacts are rated for 200 mA 60 Vdc Led Indicator Note The Battery Output is derived directly from the Load output Its loading req...

Страница 7: ...sure includes 4 x M3 threaded inserts on the bottom surface to allow the unit do be screwed to a mounting bracket Centres are located at 186 5mm x 63mm spacing Feet The SME240 12 20 has 4 x feet posit...

Страница 8: ...to suit all types of installations The maximum thread length for these screws is 4 mm from the outside edge of the power supply Hazardous Voltages exist within the power supply so it is important tha...

Страница 9: ...DC load cables must be sized to carry the maximum full load current and not exceed the system volt drop requirements Connection The requirements for wiring a SME240 12 20 into a system are as follows...

Страница 10: ...pply has inbuilt thermal cooling to maximuse fan life Please ensure that there is no restriction to the venting of the unit Approval Marking Status ACMA C Tick Yes NSW Fair Trading Approval Number U20...

Страница 11: ...021478 DOC BCE282 Series User Manual B...

Отзывы: