background image

22

I-RIH (05-21) 131793-A

TROUBLESHOOTING

Refer to 

Table 8

 for general troubleshooting symptoms, probable causes, and remedies .

Table 8.  General Troubleshooting

Symptom

Probable Cause

Remedy

A . Gas odor 1 .  Gas pipe joints loose

Leak test joints and tighten as necessary

B . New 

installation 

of heaters 

not working

1 .  Heaters not isolated during high pressure leak 

    testing of gas lines

Replace combination gas valve(s) on each heater

2 .  All gas lines not completely bled of air

Disconnect flex hose at each heater until gas is present
Connect flex hose and leak test

3 .  Gas supply regulator reversed

Remove gas supply regulator and install properly

4 .  Electrical supply line voltage and neutral polarity 

    reversed

Correct electrical supply polarity

C . No gas

1 .  Gas supply valves not open

Open all manual gas supply valves

2 .  Gas supply regulator sticking

Replace gas supply regulator

D . Electrical 

circuit 

closed but 

heater not 

working

1 .  Gas supply lacking caused control system lockout

Ensure that all gas supply valves are open
Purge air from gas supply line
Turn thermostat off, wait 5 minutes, and then reset thermostat

2 .  Line fuse blown or tripped circuit breaker

Replace line fuse or reset breaker

3 .  Electrical power short

Trace and correct short

4 .  Wiring disconnected

Ensure that wiring connections are in accordance with wiring diagram

5 .  No electrical earth ground

Provide electrical earth ground

6 .  Electrical supply line voltage and neutral polarity 

    reversed

Correct electrical supply polarity

7 .  Exhaust fan interlock (if used) is defective

Replace exhaust fan interlock

E . Direct 

spark fails 

to ignite 

main 

burner(s)

1 .  Combination gas valve not in ON position

Turn combination gas valve to ON position

2 .  Electrode wire loose

Reconnect wire

3 .  Electrode wire broken or frayed

Replace electrode

4 .  Electrode ceramic cracked

Replace electrode

5 .  Electrode improperly located

Relocate to correct position

6 .  Gas valve fails to open when power is applied

Replace combination gas valve

7 .  Supply/manifold gas pressure too low

Adjust pressure in accordance with rating plate

8 .  Ignition detection control defective

Replace ignition detection control

F . Unit 

cycles on 

and off 

(erratic 

operation)

1 .  Drafty condition

Shield heater and/or thermostat from drafts

2 .  Flame sensor wire loose or damaged

Replace wire harness to ignition detection control

3 .  No electrical earth ground

Provide electrical earth ground

4 .  Electrical supply line voltage and neutral polarity 

    reversed

Correct electrical supply polarity

5 .  Heat on pilot flame sensor insufficient

Clean pilot and check pilot orifice and alignment

G . No pilot

1 .  Gas line contains air

Purge air from gas line

2 .  Pilot line, orifice, or passage blocked

Check and clean in accordance with 

Annual Maintenance

 section

3 .  Pilot solenoid valve inoperative

Replace combination gas valve

H . Pilot 

goes out on 

100% shut-

off when 

hold-down 

button is 

released

1 .  Heat on pilot flame sensor insufficient

Clean pilot and check pilot orifice and alignment

2 .  Pilot flame sensor location improper

Correct position with respect to pilot

3 .  Manifold gas pressure low

Adjust pressure in accordance with rating plate

4 .  Poor contact at valve end of sensing element

Ensure clean and proper sensing element contact

5 .  Pilot flame sensor defective

Replace pilot flame sensor

6 .  Pilot interrupter in combination gas valve defective Replace combination gas valve

I . Pilot 

burning 

but no gas 

to main 

burner(s)

1 .  Thermostat or manual switch open

Raise thermostat setting or close switch

2 .  Manual valve closed on combination gas valve

Turn valve to ON position

3 .  No power to solenoid in combination gas valve

Check power supply and furnish proper voltage

4 .  Heat on pilot flame sensor insufficient

Clean pilot and check pilot orifice and alignment

5 .  Pilot flame sensor defective

Replace pilot flame sensor

6 .  Combination gas valve defective

Replace combination gas valve

J . Heater 

will not turn 

OFF

1 .  Thermostat defective

Replace thermostat

K . Controls 

overheated

1 .  Heater mounted incorrectly

Ensure that heater is mounted in accordance with 

Installation

 section

Содержание RIHL

Страница 1: ...u la mort Read these instructions thoroughly before installing or servicing this equipment Lisez attentivement les instructions d installation de fonctionnement et d entretien avant de proc der l inst...

Страница 2: ...with 24VAC Direct Spark Ignition DSI Single Stage Controls 15 Wiring for Units with 24VAC Direct Spark Ignition DSI Two Stage Controls 16 FIELD INSTALLED OPTIONS 17 Thermostat Option CL34 17 Thermost...

Страница 3: ...ss DANGER A danger statement describes a potentially hazardous situation that if not avoided will result in severe personal injury or death and or property damage WARNING A warning statement describes...

Страница 4: ...micile intended for use by one or more persons and that includes one or more areas such as those used for cooking eating living sleeping or a sanitary facility A residential dwelling does not include...

Страница 5: ...the area is within the clearance to combustible material as marked on the heater rating plate Both NFPA 409 latest edition and CAN CSA B149 1 latest edition specify a minimum clearance of 8 feet 2 5...

Страница 6: ...ater cannot operate unless the supply and exhaust system is operating Mechanical exhaust fans are typically located at high points of the building For flat roof areas a series of small exhausters shou...

Страница 7: ...learances between the combustion surface and combustibles The stated clearance to combustibles represents a surface temperature of 90 F 50 C above room temperature If the unit must be close to the roo...

Страница 8: ...8 68 1727 140 3556 180 4572 Propane RIHL 050 30 762 60 1524 80 2032 48 1219 34 864 110 2794 RIHVL 090 36 914 30 762 62 1575 105 2667 50 1270 38 965 135 3429 120 46 1168 33 838 64 1635 125 3175 58 1473...

Страница 9: ...24 5 6 6 7 5 160 25 0 28 5 7 7 8 7 22 5 25 5 6 9 7 8 200 27 0 31 0 8 2 9 4 24 5 28 0 7 5 8 5 Table 6 Recommended Distances for Units Mounted at 5 Degree Angle Model Unit Size Reflector Type Maximum Di...

Страница 10: ...d at 5 or 30 degrees The heater is NOT design certified for use above 30 degrees and voids the manufacturer s warranty as well A horizontal or zero degree angle is not recommended because flue gases c...

Страница 11: ...e Piping joint compound must be resistant to the action of liquefied petroleum gases DO NOT install any gas piping in heat zones CAUTION All piping must be installed according to local codes Use new c...

Страница 12: ...ion immediately upstream of the gas supply connection to the heater see Figure 4 Test all piping joints for leaks using a non corrosive leak detecting solution Do not subject gas pressure regulators f...

Страница 13: ...the Canadian Electrical Code CSA C22 1 latest edition Theelectricalsupplywiringtotheheatersusing120VACor24VACmustbeinstalledinaccordance with local codes or the National Electric Code ANSI NFPA 70 la...

Страница 14: ...ng a temperature rating of at least 302 F 150 C and a minimum size of 16 AWG 1 0 mm2 Si l un des c bles d origine fournis avec cet appareil doit tre remplac le remplacer par un c ble convenant pour un...

Страница 15: ...ol is polarity sensitive GND 24 GGS BL BL GGS VR SW MV LEGEND 24 24 VAC Supply Voltage GND Earth Ground MV Mechanical Ventilation VR Ventilation Relay SW Ventilation Interlock Switch normally opened G...

Страница 16: ...polarity sensitive Field wiring Thermostat cable 18 4 18AWG 0 8 mm2 4 conductor solid class 2 Minimum insulation temperature 140 F 60 C between thermostat and heater Maximum length 125 feet 38 meters...

Страница 17: ...its use The installer user owner employer must determine the specific safety requirements The specific safety requirements will vary depending on the location and operating procedures Therefore approp...

Страница 18: ...entrance of foreign objects This option is not for use with a parabolic reflector option DM2 If a protective screen is required with a parabolic reflector contact the factory Figure 13 Protective Scr...

Страница 19: ...itive Proper grounding and proper electrical polarity are essential to the operation of these heaters Light the heater as folows 1 Turn manual gas valve to OFF position 2 Turn electrical supply OFF 3...

Страница 20: ...seconds Shutdown To shutdown the heater for one week or less turn OFF electrical supply to heater for more than one week turn OFF electrical supply to heater and turn OFF gas supply at gas isolation...

Страница 21: ...re 15 DETAIL B 3 Check to ensure that there is spark gap clearance of 0 219 0 032 inches 5 6 mm from ceramic tile surface to the sparking tips of electrode direct spark assembly see Figure 15 DETAIL C...

Страница 22: ...r is applied Replace combination gas valve 7 Supply manifold gas pressure too low Adjust pressure in accordance with rating plate 8 Ignition detection control defective Replace ignition detection cont...

Страница 23: ...nturi obstructed by spider web Clean venturi using bottle brush 2 Foreign matter in venturi Check and clean in accordance with Annual Maintenance section 3 Orifice partially blocked 4 Supply gas press...

Страница 24: ...________________________________________ ________________________________________________________ Phone ________________________________________________________ Model ________________ Serial No ______...

Отзывы: