Contents 

1. General 
2. Moving 

and 

Uncrating 

3. Technical 

Data 

4. 

Configurations and Dimensions 

5. 

Location and Installation 

6. 

Combustion Air Supply and Flue System (only SDH models) 

7. Gas 

Connection 

8. Electrical 

Connection 

9. 

Commissioning, Lighting and Operation 

10. 

Two Stage Burners Setting and Adjustment 

11. Gas 

Conversion 

12. Maintenance 
13. Troubleshooting 
14. Spare 

Parts 

List 

15. User 

Instructions 

 

 

If optional equipment was ordered and supplied with this heater, please refer to additional instructions for 
option(s). 

 

 

 

 

 

GENERAL 

 
 

1.1 General 

 
Before installation, check if the appliance as described 
on the packaging label is in accordance with the correct 
type and model as specified on the data plate and 
complies with your customer order. 
 
After unpacking the appliance leave it fastened to the 
wooden blocks until just before siting to prevent damage 
to the base frame. 
 
Please read this document before commencing 
installation. 
 
These instructions are only valid for the country of use 
as indicated on the appliance. If these symbols are not 
shown, it is necessary to obtain appropriate technical 
instructions, which will provide information concerning 
the necessary modification of the appliance for the 
conditions of use in the country concerned. Such 
instructions may be obtained upon request from your 
supplier. 
Check if the local distributions conditions of electricity 
supply, type of gas and pressure of the appliance are 
compatible with the data plate.  
 
The installation must also be in accordance with the 
requirements & recommendations of all relevant national 
and local standardisations.  The installation must also be 
in accordance with the relevant electrical and IEE 
regulations. 
 
Unauthorised modification of this appliance or departure 
from use in the manner, for which it was intended by the 
manufacturer or installed in a manner contrary to these 
instructions, may constitute a hazard and jeopardize all 
warranties.  
Deviations should only be carried out after formal 
consent has been obtained from the manufacturer. 
 

 
 
 
 
 
 
 
 
 
Ensure the environment in which the air heater will be 
installed will not create a hazard i.e. where excessive 
(volatile) dust, flammable or corrosive substances and/or 
vapours and combustible materials may be present. 
 
This appliance has been tested and set according to the 
data plate before leaving the factory. 

 
 

IMPORTANT : RDH model 

Care must be taken when installing air heaters in outdoor 
locations to ensure that unauthorised access to the building 
cannot be gained via the appliance or its ductwork system. 
 
The RDH unit can be installed using full fresh air or a 
combination of fresh air and recirculation air.  In this case 
RDH unit must be provided with an additional air intake 
completed with a water separator. 
 
 
 

1.2 

Warranty 

 

Warranty is void if : 

a. 

Heaters are used in atmospheres containing 
flammable vapours or atmospheres containing 
chlorinated or halogenated hydrocarbons or any 
contaminant (silicone, aluminium oxide, etc…) 
that adheres to the spark ignition flame sensing 
probe. 

b. 

Wiring is not in accordance with the diagram 
furnished with the heater. 

c. 

Unit is installed without proper clearance to 
combustible materials or without proper 
ventilation and air for combustion. 

d. Air throughput is not adjusted within the range 

specified on the rating plate. 

 

 

 

 

Содержание RDH 025

Страница 1: ...a Lithuania Montenegro New Zealand Norway Poland Portugal Romania Russian Federation Serbia Slovakia Slovenia Spain Sweden Turkey Ukraine INSTALLATION COMMISSIONING SERVICING These appliances meet the...

Страница 2: ...tions of all relevant national and local standardisations The installation must also be in accordance with the relevant electrical and IEE regulations Unauthorised modification of this appliance or de...

Страница 3: ...s suspended Follow the instructions included in the option package When transporting the appliance after it has been unpacked i e fork lifting etc note the restrictions and recommendation indicated in...

Страница 4: ...X emission 100 G20 0 O2 mg kWh 113 21 125 27 123 42 143 39 155 23 127 60 146 14 NOX emission 50 G20 0 O2 mg kWh 74 84 68 00 65 83 68 97 99 31 67 56 89 78 Mass flow rate flue gases 100 G20 kg h 78 2 97...

Страница 5: ...60 1454 1654 140 573 190 1094 212 700 753 197 300 756 270 380 81 68 1800 102 043 1852 806 1722 1922 140 841 190 840 229 600 988 120 500 502 270 615 81 68 2500 102 055 1852 806 1722 1922 225 756 190 84...

Страница 6: ...60 140 573 190 1094 212 700 753 197 300 756 270 380 81 68 112 1800 102 043 2430 806 2300 2500 140 841 190 840 229 600 988 120 500 502 270 615 81 68 112 2500 102 055 2430 806 2300 2500 225 756 190 840...

Страница 7: ...54 840 212 600 753 120 300 502 270 380 81 68 030 1584 1060 1454 1654 1094 212 700 753 197 300 756 270 380 81 68 035 1584 1060 1454 1654 1094 212 700 753 197 300 756 270 380 81 68 043 1852 806 1722 192...

Страница 8: ...060 840 212 600 753 120 300 502 270 380 81 68 121 030 1990 1060 1860 2060 1094 212 700 753 197 300 756 270 380 81 68 121 035 1990 1060 1860 2060 1094 212 700 753 197 300 756 270 380 81 68 121 043 2430...

Страница 9: ...lding exhaust systems Where chlorine vapours are prevalent heaters with special grade 316 AISI stainless steel heat exchangers are recommended 5 1 2 Installation heater Figure 2a shows the clearances...

Страница 10: ...elements of the building Exposed ducting should be insulated and covered with a weatherproof membrane The duct connection to the appliance should be made using flexible connections to reduce noise tra...

Страница 11: ...rements may apply in addition to national requirements These unit heaters are designed to operate safely and efficiently with either a horizontal or vertical flue system when installed with the specif...

Страница 12: ...65 C when the heater is in operation The flue must be at least 150 mm away from any combustible material Single wall flue pipe exposed to cold air or run through unheated areas should be insulated Wh...

Страница 13: ...e pipe exposed to cold air or run through unheated areas should be insulated Where condensation is unavoidable provision must be made for the condensation to flow freely to a point to which it can be...

Страница 14: ...intain the nominal heat input Ensure that a gas supply line includes a filter and has been tested and purged in accordance with prescribed practice prior to commissioning and taking the air heater int...

Страница 15: ...ls The location of the room thermostat or sensor is very important It should not be positioned on a cold wall or cold surface Avoid location in draughty areas or where it may be influenced by heat sou...

Страница 16: ...andle heater motor loadings Energymizor Sensor cable 0 25mm screened Master slave cable 0 1mm bell wire type no screen necessary 8 6 7 Retain insert link wires shown solid Terminals shown may not be i...

Страница 17: ...nspect the appliance and to replace any part of the control system and any gas control o When overheating occurs or when gas supply is not turned off shut the manual gas tap before turning off the ele...

Страница 18: ...The air circulation fan will start after about 20 60 seconds In the event of the combustion air volume falling below a safe level the burner will be extinguished a re start cycle will commence after a...

Страница 19: ...is is the time of 10 seconds between burner shutdown and the moment the combustion fan venter is de energized Start pre purge Energisation of venter motor If the differential pressure switch is in nor...

Страница 20: ...clockwise to decrease pressure or clockwise to increase pressure see figure 13 Adjusting the burner pressure may only be carried out by suitably qualified persons o Set room thermostat to lowest setti...

Страница 21: ...increase and counter clockwise to decrease pressure until desired maximum pressure is obtained c Check maximum pressure setting several times Adjusting minimum pressure setting a Disconnect electrica...

Страница 22: ...2 10 1 80 1 53 Injector dia 1x mm 3 25 3 65 3 80 4 10 4 70 5 60 6 70 burner pressure 100 mbar 14 00 12 70 16 30 15 90 16 60 13 90 14 80 burner pressure 50 mbar 3 50 3 20 4 10 4 00 4 20 3 50 3 70 Natur...

Страница 23: ...terminals for all electrical controls 8 Gas connection 9 Capillary thermal overheat control with manual reset LC3 10 Cable entry connections 11 Relay two stage 12 Motor starter 13 24V relay only SDH...

Страница 24: ...e see below for removal instructions Inspect the burner control compartment annually to determine if cleaning is necessary If there is an accumulation of dirt dust and or lint clean the compartment an...

Страница 25: ...Remove 2 screws of the burner slider Disconnect wire of the ignition electrode at the burner controller Figure 23 Figure 24 Disconnect flame sensor wire at the burner controller Remove burner box toge...

Страница 26: ...vity of gas as well as the model and serial number of the unit When removing or replacing the burner orifice be careful not to damage the venturi tube and or the bracket 12 5 Ignition system The ignit...

Страница 27: ...enter motor wires at the terminal and ground screw 4 Holding the motor remove the screws that attach the motor plate to the venter housing Remove the motor and wheel assembly from the heater 5 Reassem...

Страница 28: ...f either set point is reached the limit control will interrupt the electric power to the gas valve This safety device provides protection in the case of motor failure or lack of airflow due to restric...

Страница 29: ...Check burner relay ground wire f Unit not properly grounded f Make certain unit is properly field grounded earthed and properly phased L1 to hot lead L2 to neutral g Faulty burner relay g If voltage i...

Страница 30: ...osition flame sensor Is gas flowing Is the igniter position correct in the gas flow Check gas pressure and supply voltage If either are low correct and repeat startup Reposition spark igniter Is there...

Страница 31: ...7 All Combustion fan motor with wheel for std units 35 25233 025 055 Combustion fan motor with wheel for opp units 35 25233 1 025 055 Combustion fan motor with wheel for std units 35 25224 073 100 Com...

Страница 32: ...the burner control does not require resetting An indicator light glows at the front panel of the appliance and on a remote control if fitted Reset by pushing light button on appliance or the remote c...

Страница 33: ...Sabbestraat 130 B 8930 MENEN Belgium Herewith declares that The gas fired air heaters REZNOR series SDH and RDH Are in conformity with the provisions of the Machinery Directive as amended and with nat...

Отзывы: