Form 465, Page 8
Boiler
Location
Do not attempt to install this boiler until you have read and understand
this manual!
Refer to Boiler Mounting requirements for specific requirements for mount-
ing Models RAB350 and RAB500.
Measure all distances to comply with the specific code requirements and
minimum clearances listed below.
Refer to the section on Venting including vent requirements and recom-
mendations.
Locate the boiler so that suitable means shall be provided to facilitate regu-
lar cleaning and maintenance.
WARNING: You must comply with all requirements on
distance from heater to combustibles.
In Canada, for additional
information on installation
clearances, refer to CAN/
CSA-B139-M91, “Installa-
tion Code for Oil Burning
Equipment,” Clause 7.0 -
Installation Clearances.
Front
Recommended for service access -
Size 140
- 87”
(2210mm);
Size 235
- 71” (1803mm);
Size 350
- 85”
(2159mm);
Size 500
- 97” (2462mm)
Absolute
Minimum - All Sizes - 36” (914mm)
Side (with
Recommended for service access - 24” (610mm)
electrical box)
Absolute
Minimum - 15” (381mm)
Side (opposite
12” (305mm)
electrical box)
Rear
Recommended for service access - 41” (1041mm)
Absolute
Minimum - 36” (914mm)
Flue Pipe
18” (457mm)
Minimum
Clearances
(inches
and mm)
WARNING: Clearances apply to all combustibles. Do
not leave paper, rags, or any moveable combustibles near
the burner or store gasoline or any other flammable fluid
near this appliance.