![Reznor OH Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/reznor/oh/oh_installation-operation-and-maintenance-manual_1449861006.webp)
6
I-OH (01-20) PN120390R7
Dimensions
Dimensions for the unit are shown in
Table 2. Clearances
Unit Surface
Top
Front
Sides
Rear
Bottom
Flue Pipe
Required Clearance (Inches (mm))
2 (51)
48 (1219)
18 (457)
24 (610)
6 (152)
18 (457)
Figure 1. Dimensions (Refer to
GENERAL INFORMATION—CONTINUED
Clearances
⚠ WARNING ⚠
Clearances apply to ALL combustibles. DO NOT leave paper, rags, or any combustible near the
heater.
) to combustibles is defined as the minimum distance from the heater to a surface or object
so as to ensure that a surface temperature of 90°F above the surrounding ambient temperature is not exceeded. The
heater should be suspended at a height so that the heat exchanger cannot be touched. Clearance is also required
at the sides of the heater for servicing the unit.
NOTE: For additional information on installation clearances, refer to CAN/CSA-B139,
Installation
Code for Oil Burning Equipment
(paragraph 8,
Installation Clearances
).