LCSC-3E--EN
32/40
9.2 Air heater does not operate and lockout indicator light is on
Does venter motor
operate ?
Breakdown of appliance
- signal lamp H3 burns
Reset appliance - Check if there is 230V at
terminals (5) J2 & (2) J1.
NO
Check venter motor.
YES
Breakdown of appliance -
signal lamp H3 burns
YES
Reset appliance
Is differential air pressure
switch (S3) active ?
Overheat control LC3
in open position ?
YES
NO
See 2A
See 2C
Do you observe
flame failure :
consult 2B
NO
YES
NO
Check burner
controller.
2A :Faulty differential air
pressure switch
Check flue pipe system (see
table 5) - Flue blocked or too
long ?
Reference tube to differential air
pressure switch is not airtight or
blocked ?
YES
YES
Check differential air pressure
switch (S3). Check switch point
eltaP. Does burner ignite?
Correct if necessary.
NO
Check connection (2)+(3)
J2 at burner controller (E).
If necessary correct. Does
burner ignite?
NO
Faulty differential air
pressure switch S3 :
replace.
YES
NO
Faulty burner
controller (E).
Содержание LCSC-3E 100
Страница 6: ...LCSC 3E EN 6 40 2 3 Blower curves LCSC 3E...
Страница 7: ...LCSC 3E EN 7 40...
Страница 8: ...LCSC 3E EN 8 40...
Страница 10: ...LCSC 3E EN 10 40...
Страница 11: ...LCSC 3E EN 11 40...
Страница 12: ...LCSC 3E EN 12 40 2 4 2 Mixing cabinet and filters LCSC 3E...
Страница 13: ...LCSC 3E EN 13 40...
Страница 14: ...LCSC 3E EN 14 40...
Страница 16: ...LCSC 3E EN 16 40 2 5 Dimensions standard unit...
Страница 17: ...LCSC 3E EN 17 40 Dimensions unit with mixing cabinet option 526...