IMPORTANT INSTRUCTIONS 

Installation and maintenance personnel should familiarize themselves with this manual and all the 

IMPORTANT INSTRUCTIONS 

before installing or working on this heater to avoid potential unsafe 

conditions, severe property damage, personal injury or death.  
 
1.  Read all instructions before installing and 

operating this heater.  

2.  Verify that the supply voltage and phase to 

the heater matches the nameplate rating 
before energizing.  

3.  Potentially lethal voltages are present. Be 

sure to lock the branch circuit disconnect 
switch in the OFF position and tag the 
circuit “Out for Maintenance” before 
working on this equipment.  

4.  Keep electrical enclosure cover tightly 

closed while in operation.  

5.  Hazard of Electric Shock. Heater must be 

grounded in accordance with both local and 
national codes. 

6.  This heater should be installed by a licensed 

electrician familiar with all applicable 
national and local codes having jurisdiction. 
It is the responsibility of the installer to 
verify the safety and suitability of the 
installation.  

7.  Disassembly of the unit for installation is 

not required or authorized.  

8.  Replacement electrical components must 

be obtained from the factory in order to 
maintain any applicable Agency Listings.  

9.  Use this heater only as described in this 

manual. Any other use is not recommended  

 

by the manufacturer and may result in fire, 
electric shock or personal injury.  

10.  The heater and discharge air are hot when 

in use. To avoid burns, do not let bare skin 
touch hot surfaces.  

11.  To prevent a possible fire, do not block or 

allow foreign objects to enter air intakes or 
exhaust in any manner.  

12.  Risk of fire due to high temperatures. Keep 

electrical cords, drapery, furnishings, 
insulation and other combustibles at least 3 
feet (0.9m) from the front of the heater and 
away from the sides, rear and top.  

13.  Installation minimum mounting clearances 

specified both on heater nameplate and in 
this owner’s manual must be maintained.  

14.  Use copper wire rated 90°C min. for supply 

connections.  

15.  This heater should not be used in 

potentially explosive atmospheres. Do not 
use in areas where gasoline, paint, or 
flammable liquids are used or stored.  

16.  Do not use outdoors. Heater may be 

washed down with water for cleaning. Do 
not use high pressure cleaning systems. 

17.  Risk of fire. Do not use as a residential or 

household heater.  

18.   Heater is designed to be controlled by a 

room thermostat located within the 
operating space that will control the room 
temperature below 80°F (26.7°C). Do not 
allow heater to cycle on the built-on limit 
controls. 

19.  The heaters are designed for permanent 

wall or ceiling mounting in a horizontal 
position only. 

20.  Do not operate heater after it malfunctions.  

Disconnect power at service panel and have 
heater inspected by a reputable electrician 
before reusing. 

21.   SAVE THESE INSTRUCTIONS. 

 

 

 

WARRANTY WILL BE VOID IF INSTRUCTIONS ARE NOT FOLLOWED.

Содержание EWHB

Страница 1: ...ater Owner s Manual This manual covers installation operation and maintenance Read carefully before attempting to install operate or service the EWHB Series Unit Heater IMPORTANT INSTRUCTIONS SAVE THE...

Страница 2: ...use is not recommended by the manufacturer and may result in fire electric shock or personal injury 10 The heater and discharge air are hot when in use To avoid burns do not let bare skin touch hot su...

Страница 3: ...The unit is designed to give years of safe trouble free operation when properly installed and maintained A Site Selection The heaters are intended for elevated mounting locations so that they blow war...

Страница 4: ...installation such that the outlet air is not directed at an adjacent wall Louvered grills can be installed to deflect the discharge air up down or sideways TABLE 2 KW Cabinet Size Air Volume Air Throw...

Страница 5: ...INSTRUCTIONS Continued Ceiling or wall mount using swivel bracket cont TABLE 4 KW BH BL M 12 4 25 108mm 19 50 495mm 8 50 216mm 12 1 to 47 7 125 181mm 22 25 565mm 3 25 83mm Optional Ceiling Installati...

Страница 6: ...k hazards 4 Confirm that the electrical power supply matches the nameplate voltage phase amperage and frequency rating of the heater to be connected 5 Field supply conductors must be sized for at leas...

Страница 7: ...ervice or clean heater while unit is operating as there is a hazard from electric shock injury from operating fan blade and burns from hot heating elements The unit is designed to give years of safe t...

Страница 8: ...re reliable operation 10 During normal operation the limit controls are not supposed to cycle the heater ON and OFF If frequent cycling of the limit controls occurs verify the minimum mounting clearan...

Страница 9: ...meter to check the current draw of each input line Adjust the room thermostat to its highest temperature to energize heater All input lines should draw approximately equal current which should agree w...

Отзывы: