Electrical installation
3-9
DOK-RD500*-RD42*******-IB03-EN-P
Control terminal strip X11 on SN11027
Terminal X11 Designation
Digital inputs
1
P24 V output (80 mA load capacity)
2
“ON” control command
3
“Fault acknowledgement” control command
(a positive edge is required to acknowledge a fault)
4
Checkback signal, slave for parallel operation; when supplied,
there is a jumper between X11.4 – X11.9
5
External fault (low active)
6
P24 V output (80 mA load capacity)
7
Ground
Digital outputs
8
Ground
9
“Enable slave” control signal for a parallel configuration as
master; when supplied a jumper is inserted between X11.4 –
X11.9
10
“Enable inverter” control signal or
“Slave checkback signal” for parallel operation as slave
Relay
11
12
13
Relay with changeover contact; “Fault” signal
Terminal 12/13 closed -> fault
Terminal 11/13 closed -> no fault
Load capacity: 250 V AC, 7 A; 30 V DC, 7A
Contact in
the quiescent
position:
14
Ground
15
Protective conductor
When supplied:
Jumper X11.14 – X11.15
Fig. 3-9: Control terminal strip X11
Input voltage:
min.
max.
High
13 V
33 V
-3 V
5 V
Low
or open-circuit terminal
Input current at 24 V
8.6 mA
Fig. 3-10: Digital inputs
Output voltage
min.
max.
High
16 V
30 V
Low
High-ohmic
Load capacity
50 mA
Fig. 3-11: Digital outputs
ATTENTION
Demages by overloading of the electronic
component!
To comply with the EMC-requirements it is absolute
essential to use shielded cable for the control wire.
Digital inputs
Digital outputs